69
JOHNSON CONTROLS
FORM 100.50-EG12 (918)
TABLE 34 -
THREE PHASE POWER SUPPLY CONDUCTOR SIZE RANGE
70–75 TON UNITS
SUPPLY
VOLTAGE
SINGLE POINT
TB
SINGLE POINT
DISCONNECT
DUAL POINT TB
TB1
TB2
208V
(2-in.) 250 kcmil-500 kcmil (2-in.) 2 AWG-500 kcmil
4 AWG-500 kcmil
6 AWG-350 kcmil
230V
(2-in.) 250 kcmil-500 kcmil (2-in.) 2 AWG-500 kcmil
6 AWG-400 kcmil
6 AWG-350 kcmil
380V-60
(2-in.) 3/0-250 kcmil
4 AWG-500 kcmil
6 AWG-400 kcmil
14 AWG-2/0
460V
(2-in.) 3/0-250 kcmil
4 AWG-500 kcmil
14 AWG-2/0
14 AWG-2/0
575V
6 AWG-400 kcmil
6 AWG-350 kcmil
14 AWG-2/0
14 AWG-2/0
80 TON UNITS
SUPPLY
VOLTAGE
SINGLE POINT
TB
SINGLE POINT
DISCONNECT
DUAL POINT TB
TB1
TB2
208V
(2-in.) 2/0-400 kcmil
(2-in.) 2 AWG-500 kcmil (2-in.) 2 AWG-500 kcmil
6 AWG-350 kcmil
230V
(2-in.) 250 kcmil-500 kcmil (2-in.) 2 AWG-500 kcmil
4 AWG-500 kcmil
6 AWG-350 kcmil
380V-60
(2-in.) 3/0-250 kcmil
4 AWG-500 kcmil
6 AWG-400 kcmil
14 AWG-2/0
460V
(2-in.) 3/0-250 kcmil
4 AWG-500 kcmil
6 AWG-400 kcmil
14 AWG-2/0
575V
(2-in.) 3/0-250 kcmil
6 AWG-350 kcmil
14 AWG-2/0
14 AWG-2/0
90–105 TON UNITS
SUPPLY
VOLTAGE
SINGLE POINT
TB
SINGLE POINT
DISCONNECT
DUAL POINT TB
TB1
TB2
208V
(2-in.) 2/0-400 kcmil
(2-in.) 2 AWG-500 kcmil (2-in.) 2 AWG-500 kcmil
4 AWG-600 kcmil
230V
(2-in.) 2/0-400 kcmil
(2-in.) 2 AWG-500 kcmil (2-in.) 2 AWG-500 kcmil
4 AWG-600 kcmil
380V-60
(2-in.) 3/0-250 kcmil
4 AWG-500 kcmil
4 AWG-500 kcmil
14 AWG-2/0
460V
(2-in.) 3/0-250 kcmil
4 AWG-500 kcmil
6 AWG-400 kcmil
14 AWG-2/0
575V
(2-in.) 3/0-250 kcmil
6 AWG-350 kcmil
14 AWG-2/0
14 AWG-2/0
Содержание YPAL070
Страница 4: ...JOHNSON CONTROLS 4 THIS PAGE INTENTIONALLY LEFT BLANK FORM100 50 EG12 918 ...
Страница 73: ...73 JOHNSON CONTROLS FORM 100 50 EG12 918 Field Control Wiring Figure 9 FIELD CONTROL WIRING ld08184 ...
Страница 74: ...JOHNSON CONTROLS 74 FORM100 50 EG12 918 Figure 10 FIELD CONTROL WIRING Field Control Wiring Cont d ...