SECTION 3 - MAINTENANCE

3

particles. Aluminum gas seal rings can contact the im-

peller and account for some aluminum particles accu-

mulating in the oil filter, especially during the initial 

start up and first several months of operation. How-

ever, if aluminum particles continue to accumulate and 

the same conditions continue to stop the unit operation 

after a new filter is installed, notify the nearest Johnson 

Controls office to request a Johnson Controls Service 

Technician.

ELECTRICAL CONTROLS

For information covering the YKEP Control Center op-

eration, refer to the 

YKEP Control Center Operations 

Manual (Form 160.77-O2)

.Preventative Maintenance

It is the responsibility of the owner to provide the nec-

essary daily, monthly and yearly maintenance require-

ments of the system.

If a unit failure occurs due to improper 

maintenance during the warranty period; 

Johnson Controls will not be liable for 

costs incurred to return the system to 

satisfactory operation.

In any operating system it is most important to provide 

a planned maintenance and inspection of functioning 

parts to keep the unit operating at its peak efficiency. 

Therefore, the following maintenance should be per-

formed as prescribed in 

Table 3 on Page 31

.

COMPRESSOR MOTORS

1.  Check mounting screws and piping joint nuts fre-

quently to insure tightness.

2.  Meg motor windings annually to check for dete-

rioration of windings.

LEAK TESTING

The unit should be leak tested monthly. Any leaks 

found must be repaired immediately.

EVAPORATOR AND CONDENSER

The major portion of maintenance on the condenser 

and evaporator will deal with maintaining the water 

side of the condenser and evaporator in a clean condi-

tion.

The use of untreated water in cooling towers, closed 

water systems, etc. frequently results in one or more of 

the following:

•  Scale Formation.
•  Corrosion or Rusting.
•  Slime and Algae Formation.

Therefore, proper water treatment is essential to 

provide for longer and more economical life of the 

equipment. The following recommendations should be 

followed in determining the condition of the water side 

of the condenser and evaporator tubes.

1.  The condenser tubes should be cleaned annually 

or earlier if conditions warrant. If the temperature 

difference  between  the  water  off  the  condenser 

and the condenser liquid refrigerant temperature 

is more than 4°F (2°C) greater than the difference 

recorded on a new unit, it is a good indication 

that the condenser tubes require cleaning. Refer 

to 

Cleaning Evaporator and Condenser Tubes 

on Page 28 

in this section for condenser tube 

cleaning instructions.

2.  The evaporator tubes under normal circumstances 

will not require cleaning. If the temperature dif-

ference between the refrigerant and the chilled 

water increases slowly over the operating season, 

it is an indication that the evaporator tubes may be 

fouling or that there may be a water bypass in the 

water box requiring gasket replacement or refrig-

erant may have leaked from the chiller.

OIL RETURN SYSTEM

1.  Change the dehydrator in the oil return system 

semi-annually or earlier if the oil return system 

fails to operate.

2.  When the dehydrator is changed, use care that any 

foreign particles that may obstruct the eductor ori-

fices are removed.

ELECTRICAL CONTROLS

1.  All electrical controls should be inspected for ob-

vious malfunctions.

2.  It is important that the factory control settings (op-

eration and safety) not be changed. If the settings 

are changed without Johnson Controls approval, 

the warranty may be voided.

Содержание York YKEP

Страница 1: ...LD15101 CENTRIFUGAL LIQUID CHILLER WITH ECONOMIZER COMPRESSOR OPERATION AND MAINTENANCE Supersedes 160 77 O1 1111 Form 160 77 O1 1020 R 134a Issue Date October 22 2020 MODEL YKEP 2700 3200 TON...

Страница 2: ...This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in th...

Страница 3: ...ior to performing any work on the chiller ASSOCIATED LITERATURE MANUAL DESCRIPTION FORM NUMBER YKEP Installation Re assembly 160 77 N1 YKEP Unit Operation Maintenance 160 77 O1 YKEP Control Center Ope...

Страница 4: ...c needs for the chiller operating conditions and annualized impact realized by the chiller Your lo cal Johnson Controls Branch can propose a customized Planned Service Agreement that leverages real ti...

Страница 5: ...vice 18 Stopping The System 18 Prolonged Shutdown 18 SECTION 3 MAINTENANCE 19 Renewal Parts 19 Oil Return System 19 Checking System For Leaks 21 Conducting An R 22 Pressure Test 22 Vacuum Testing 23 V...

Страница 6: ...am 13 FIGURE 6 Oil Livel Indicator 15 FIGURE 7 Liquid Chiller Log Sheets 17 FIGURE 8 Oil Return System 19 FIGURE 9 Charging Oil Reservoir With Oil 20 FIGURE 10 Evacuation of Chiller 21 FIGURE 11 Satur...

Страница 7: ...city COMPONENTS YKEP chillers are equipped with Single Stage Flash Economizer Primary Compressor K7 Model YDHA119 Economizer Compressor Q3 Model HF416 YORK Unit Mounted Low Voltage Solid State Starter...

Страница 8: ...plied by the customer Available YORK starters include a Floor Mounted Medium Voltage Variable Speed Drive MV VSD Figure 3 on Page 8 and a Unit Mounted MV SSS Figure 4 on Page 8 Customer supplied start...

Страница 9: ...t load ef ficiency by analyzing information fed to it by sensors located throughout the chiller Operational information for the VSD can be found in MV VSD 2300v 6600v Operation Form 160 00 O6 and MV V...

Страница 10: ...sig 16 2 barg Water Boxes The removable water boxes are fabricated of steel The design working pressure is 150 psig 10 3 barg and the boxes are tested at 225 psig 15 5 barg Integral steel water baffle...

Страница 11: ...a combination of prerotation vanes PRV located at the entrance to the compressor impeller op tional hot gas bypass and variable compressor speed to control capacity The position of the vanes is automa...

Страница 12: ...high pressure re frigerant vapor rejects heat to the cooling liquid that is passing through the tubes The cooling liquid will reject its heat to the environment in a cooling tower When the refrigerant...

Страница 13: ...JOHNSON CONTROLS 13 FORM 160 77 O1 ISSUE DATE 10 22 2020 Section 1 System Fundamentals Figure 5 YKEP SYSTEM FLOW DIAGRAM LD15103 1 2 3 4 5 1...

Страница 14: ...FORM 160 77 O1 ISSUE DATE 10 22 2020 JOHNSON CONTROLS 14 This page intentionally left blank...

Страница 15: ...rging Procedure page 20 Always comply with EPAand Local regu lations when removing or disposing of Refrigeration System Oil Figure 6 OIL LIVEL INDICATOR LD08647 PRE STARTING Prior to starting the chil...

Страница 16: ...temperature Pressure and motor current overrides also apply as necessary to maintain operating limits CONDENSERWATERTEMPERATURECONTROL The YKEP chiller is designed to use less power by tak ing advant...

Страница 17: ...3 Inspect the Compressor Drive Motors see motor manufacturers maintenance and service instruc tion supplied with the unit a Meg motor windings Refer to Figure 12 on Page 26 for details 4 Inspect and...

Страница 18: ...ll er is not running brine should not be run through the evaporator However if there is brine running through the evaporator there must be flow through the condenser to prevent tubes from freezing 3 O...

Страница 19: ...inducing the low pressure oil rich liquid to flow from the evaporator through the dehy drator to the compressor sump Changing The Dehydrator To change the dehydrator use the following procedure 1 Iso...

Страница 20: ...onnection to the oil charg ing valve located on the remote oil reservoir cover plate see Figure 8 on Page 19 Do not tighten the connection at the charging valve until after the air is forced out by pu...

Страница 21: ...at section in the fol lowing manner if the location is not definite all the tubes will need to be checked 2 Wash off both tube heads and the ends of all tubes with water Do not use carbon tetrachlorid...

Страница 22: ...ely 75 to 100 PSIG 517 to 690 kPa To be sure that the concentration of refrigerant has reached all parts of the system test for the pres ence of refrigerant with a leak detector at an ap propriate ser...

Страница 23: ...f gauge plus atmospheric pressure Water Freezes bulb temperature of 32 F 0 C or a pressure of 5 mm Hg is reached Refer to Table 1 on Page 23 for corresponding pressure values 4 To improve evacuation c...

Страница 24: ...le vacuum on the system OPERATION Dehydration of a refrigerant system can be obtained by this method because the water present in the sys tem reacts similar to refrigerant By pulling down the pressure...

Страница 25: ...the freezing point is 29 PSIG 200 kPa for R 134a at sea level While charging every precaution must be taken to pre vent moisture laden air from entering the system Fab ricate a suitable charging conn...

Страница 26: ...um during the megging procedure CONDENSERS AND EVAPORATORS Maintenance of condenser and evaporator shells is im portant to provide trouble free operation of the chiller The water side of the tubes in...

Страница 27: ...JOHNSON CONTROLS 27 FORM 160 77 O1 ISSUE DATE 10 22 2020 Section 3 Maintenance Figure 13 MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES LD00476 3...

Страница 28: ...chilled water remove the heads and thoroughly clean each tube with a soft bristle bronze or nylon brush DO NOT USE A STEEL BRISTLE BRUSH A steel brush may damage the tubes Improved results can be obta...

Страница 29: ...er side of the condenser and evaporator in a clean condi tion The use of untreated water in cooling towers closed water systems etc frequently results in one or more of the following Scale Formation C...

Страница 30: ...nalysis 1 X Perform vibration analysis X Clean tubes X 2 Perform Eddy current testing and inspect tubes 2 5 Years Lubricate motor Refer to motor manufacturer s recommendations 1 2 MAINTENANCE REQUIREM...

Страница 31: ...rough the condenser to proper value Abnormally Low Suction Pressure Temperature difference between leaving chilled water and refrigerant in evapo rator greater than normal with high discharge temperat...

Страница 32: ...y inlet Check oil inlet for blockage Symptom Oil Pressure Gradually Decreases Noted by Observation of Daily Log Sheets When oil pump VSD frequency in creases to 55 hz to maintain target oil pressure O...

Страница 33: ...elsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 4 ANALOG INPUT RANGES LOW PRESSURE CHILLERS MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity...