SECTION 3 - MAINTENANCE

Cleaning Evaporator and Condenser Tubes

Evaporator

It is difficult to determine by any particular test wheth-

er possible lack of performance of the water evaporator 

is due to fouled tubes alone or due to a combination of 

other issues. Trouble which may be due to fouled tubes 

is indicated when, over a period of time, the cooling 

capacity decreases and the approach (temperature dif-

ference between water leaving the evaporator and the 

refrigerant temperature in the evaporator) increases. A 

gradual drop-off in cooling capacity can also be caused 

by a gradual leak of refrigerant from the system or by 

a combination of fouled tubes and shortage of refriger-

ant charge.

Condenser

In a condenser, trouble due to fouled tubes is usually 

indicated by a steady rise in head pressure, over a pe-

riod of time, accompanied by a steady rise in condens-

ing temperature, and noisy operation. These symptoms 

rarely may also be due to improper evacuation before 

charging refrigerant during system breach.

Tube Fouling

Fouling of the tubes can be due to deposits of two types 

as follows:

1. 

Rust or sludge – which finds its way into the tubes 

and accumulates there. This material usually does 

not build up on the inner tube surfaces as scale, 

but does interfere with the heat transfer. Rust or 

sludge can generally be removed from the tubes 

by a thorough brushing process.

2.  Scale – due to mineral deposits. These deposits, 

even though very thin and scarcely detectable 

upon physical inspection, are highly resistant to 

heat  transfer.  They  can  be  removed  most  effec

-

tively by circulating an acid solution through the 

tubes.

Tube Cleaning Procedures

Brush Cleaning of Tubes

If the tube fouling consists of dirt and sludge, it can 

usually be removed by means of the brushing pro-

cess. Drain the water sides of the circuit to be cleaned 

(cooling water or chilled water) remove the heads and 

thoroughly clean each tube with a soft bristle bronze 

or nylon brush. DO NOT USE A STEEL BRISTLE 

BRUSH. A steel brush may damage the tubes.

Improved results can be obtained by admitting water 

into the tube during the cleaning process. This can be 

done by mounting the brush on a suitable length of 1/8" 

pipe with a few small holes at the brush end and con-

necting the other end by means of a hose to the water 

supply.

Acid Cleaning of Tubes

Tubes that are fouled with a hard scale deposit, may re-

quire acid cleaning. The tubes should always be brush 

cleaned before acid cleaning. If the relatively loose 

foreign material is removed before the acid cleaning, 

the acid solution will have less material to dissolve and 

flush from the tubes resulting in a better cleaning job.

Acid cleaning should only be performed 

by an expert. Please consult your local 

water treatment representative for as-

sistance in removing scale buildup and 

preventative maintenance programs to 

eliminate future problems.

Commercial Acid Cleaning

In many major cities, commercial organizations now 

offer a specialized service of acid cleaning evaporators 

and condensers. If acid cleaning is required, Johnson 

Controls recommends the use of this type of organiza-

tion. The Dow Industries Service Division of the Dow 

Chemical Company, Tulsa, Oklahoma, with branches 

in principal cities is one of the most reliable of these 

companies.

COMPRESSORS

Maintenance for the compressor assembly consists of 

the following checks:

•  checking the operation of the oil return system 

and changing the dehydrator

•  checking and changing the oil
• 

checking and changing the oil filters

•  checking the operation of the oil heater
•  checking the operation of the oil pump
•  observing the operation of the compressor.

Internal wearing of compressor parts could be caused 

by improper lubrication, brought about by restricted oil 

lines, passages, or dirty oil filters. If the unit is shut-

ting down on High Oil Temperature (HOT) or Low Oil 

Pressure (LOP), change the oil filter element. Exam-

ine the oil filter element for the presence of aluminum 

Содержание York YKEP

Страница 1: ...LD15101 CENTRIFUGAL LIQUID CHILLER WITH ECONOMIZER COMPRESSOR OPERATION AND MAINTENANCE Supersedes 160 77 O1 1111 Form 160 77 O1 1020 R 134a Issue Date October 22 2020 MODEL YKEP 2700 3200 TON...

Страница 2: ...This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in th...

Страница 3: ...ior to performing any work on the chiller ASSOCIATED LITERATURE MANUAL DESCRIPTION FORM NUMBER YKEP Installation Re assembly 160 77 N1 YKEP Unit Operation Maintenance 160 77 O1 YKEP Control Center Ope...

Страница 4: ...c needs for the chiller operating conditions and annualized impact realized by the chiller Your lo cal Johnson Controls Branch can propose a customized Planned Service Agreement that leverages real ti...

Страница 5: ...vice 18 Stopping The System 18 Prolonged Shutdown 18 SECTION 3 MAINTENANCE 19 Renewal Parts 19 Oil Return System 19 Checking System For Leaks 21 Conducting An R 22 Pressure Test 22 Vacuum Testing 23 V...

Страница 6: ...am 13 FIGURE 6 Oil Livel Indicator 15 FIGURE 7 Liquid Chiller Log Sheets 17 FIGURE 8 Oil Return System 19 FIGURE 9 Charging Oil Reservoir With Oil 20 FIGURE 10 Evacuation of Chiller 21 FIGURE 11 Satur...

Страница 7: ...city COMPONENTS YKEP chillers are equipped with Single Stage Flash Economizer Primary Compressor K7 Model YDHA119 Economizer Compressor Q3 Model HF416 YORK Unit Mounted Low Voltage Solid State Starter...

Страница 8: ...plied by the customer Available YORK starters include a Floor Mounted Medium Voltage Variable Speed Drive MV VSD Figure 3 on Page 8 and a Unit Mounted MV SSS Figure 4 on Page 8 Customer supplied start...

Страница 9: ...t load ef ficiency by analyzing information fed to it by sensors located throughout the chiller Operational information for the VSD can be found in MV VSD 2300v 6600v Operation Form 160 00 O6 and MV V...

Страница 10: ...sig 16 2 barg Water Boxes The removable water boxes are fabricated of steel The design working pressure is 150 psig 10 3 barg and the boxes are tested at 225 psig 15 5 barg Integral steel water baffle...

Страница 11: ...a combination of prerotation vanes PRV located at the entrance to the compressor impeller op tional hot gas bypass and variable compressor speed to control capacity The position of the vanes is automa...

Страница 12: ...high pressure re frigerant vapor rejects heat to the cooling liquid that is passing through the tubes The cooling liquid will reject its heat to the environment in a cooling tower When the refrigerant...

Страница 13: ...JOHNSON CONTROLS 13 FORM 160 77 O1 ISSUE DATE 10 22 2020 Section 1 System Fundamentals Figure 5 YKEP SYSTEM FLOW DIAGRAM LD15103 1 2 3 4 5 1...

Страница 14: ...FORM 160 77 O1 ISSUE DATE 10 22 2020 JOHNSON CONTROLS 14 This page intentionally left blank...

Страница 15: ...rging Procedure page 20 Always comply with EPAand Local regu lations when removing or disposing of Refrigeration System Oil Figure 6 OIL LIVEL INDICATOR LD08647 PRE STARTING Prior to starting the chil...

Страница 16: ...temperature Pressure and motor current overrides also apply as necessary to maintain operating limits CONDENSERWATERTEMPERATURECONTROL The YKEP chiller is designed to use less power by tak ing advant...

Страница 17: ...3 Inspect the Compressor Drive Motors see motor manufacturers maintenance and service instruc tion supplied with the unit a Meg motor windings Refer to Figure 12 on Page 26 for details 4 Inspect and...

Страница 18: ...ll er is not running brine should not be run through the evaporator However if there is brine running through the evaporator there must be flow through the condenser to prevent tubes from freezing 3 O...

Страница 19: ...inducing the low pressure oil rich liquid to flow from the evaporator through the dehy drator to the compressor sump Changing The Dehydrator To change the dehydrator use the following procedure 1 Iso...

Страница 20: ...onnection to the oil charg ing valve located on the remote oil reservoir cover plate see Figure 8 on Page 19 Do not tighten the connection at the charging valve until after the air is forced out by pu...

Страница 21: ...at section in the fol lowing manner if the location is not definite all the tubes will need to be checked 2 Wash off both tube heads and the ends of all tubes with water Do not use carbon tetrachlorid...

Страница 22: ...ely 75 to 100 PSIG 517 to 690 kPa To be sure that the concentration of refrigerant has reached all parts of the system test for the pres ence of refrigerant with a leak detector at an ap propriate ser...

Страница 23: ...f gauge plus atmospheric pressure Water Freezes bulb temperature of 32 F 0 C or a pressure of 5 mm Hg is reached Refer to Table 1 on Page 23 for corresponding pressure values 4 To improve evacuation c...

Страница 24: ...le vacuum on the system OPERATION Dehydration of a refrigerant system can be obtained by this method because the water present in the sys tem reacts similar to refrigerant By pulling down the pressure...

Страница 25: ...the freezing point is 29 PSIG 200 kPa for R 134a at sea level While charging every precaution must be taken to pre vent moisture laden air from entering the system Fab ricate a suitable charging conn...

Страница 26: ...um during the megging procedure CONDENSERS AND EVAPORATORS Maintenance of condenser and evaporator shells is im portant to provide trouble free operation of the chiller The water side of the tubes in...

Страница 27: ...JOHNSON CONTROLS 27 FORM 160 77 O1 ISSUE DATE 10 22 2020 Section 3 Maintenance Figure 13 MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES LD00476 3...

Страница 28: ...chilled water remove the heads and thoroughly clean each tube with a soft bristle bronze or nylon brush DO NOT USE A STEEL BRISTLE BRUSH A steel brush may damage the tubes Improved results can be obta...

Страница 29: ...er side of the condenser and evaporator in a clean condi tion The use of untreated water in cooling towers closed water systems etc frequently results in one or more of the following Scale Formation C...

Страница 30: ...nalysis 1 X Perform vibration analysis X Clean tubes X 2 Perform Eddy current testing and inspect tubes 2 5 Years Lubricate motor Refer to motor manufacturer s recommendations 1 2 MAINTENANCE REQUIREM...

Страница 31: ...rough the condenser to proper value Abnormally Low Suction Pressure Temperature difference between leaving chilled water and refrigerant in evapo rator greater than normal with high discharge temperat...

Страница 32: ...y inlet Check oil inlet for blockage Symptom Oil Pressure Gradually Decreases Noted by Observation of Daily Log Sheets When oil pump VSD frequency in creases to 55 hz to maintain target oil pressure O...

Страница 33: ...elsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 4 ANALOG INPUT RANGES LOW PRESSURE CHILLERS MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity...

Страница 34: ...ennsylvania USA 17349 Subject to change without notice Printed in USA Copyright by Johnson Controls 2020 ALL RIGHTS RESERVED Form 160 77 O1 1020 Issue Date October 22 2020 Supersedes 160 77 O1 1111 1...

Отзывы: