SECTION 2 - SYSTEM OPERATING PROCEDURES

denser water temperature) may be an indication of 

dirty condenser tubes.

OPERATING INSPECTIONS

By following a regular inspection using the display 

readings of the YKEP Control Center, and maintenance 

procedure, the operator will ensure smooth operation 

of the unit. The following list of inspections and proce-

dures should be used as a guide.

Daily

1.  Check the YKEP Control Center displays for sta-

tus and error messages.

2.  If either compressor is in operation, check the 

bearing oil pressure on the SYSTEM screen and 

then check the oil level in the oil reservoir. The 

oil level should be within the operating range as 

marked on the oil indicator. Drain or add oil if 

necessary.

3.  Check the entering and leaving condenser water 

pressure and temperatures. Condenser water tem-

peratures can be checked on the SYSTEM Screen. 

4.  Check the entering and leaving chilled liquid tem-

peratures and evaporator pressure on the SYS-

TEM Screen.

5.  Check the condenser saturation temperature 

(based upon condenser pressure sensed by the 

condenser transducer) on the SYSTEM Screen.

6.  Check the compressor discharge temperature on 

the SYSTEM Screen. During normal operation 

discharge temperature should not exceed 220°F 

(104°C).

7.  Check the compressor motor current on the ap-

plicable MOTOR Screen.

8.  Check for signs of dirty or fouled condenser 

tubes. The temperature difference between water 

leaving the condenser and the saturated condens-

ing temperature should not exceed the difference 

recorded for a new unit by more than 4°F (2.2°C).

Weekly

1.  Check the refrigerant charge. Refer to 

Checking 

the Refrigerant Charge During Unit Shutdown

 in 

SECTION 3 - MAINTENANCE

.

Monthly

1.  Leak check the entire chiller.

leaving chilled liquid temperature. Pressure and motor 

current overrides also apply as necessary to maintain 

operating limits.

CONDENSER WATER TEMPERATURE CONTROL

The YKEP chiller is designed to use less power by tak-

ing advantage of lower than design water temperatures 

that are naturally produced by cooling towers through-

out the operating year. Exact control of condenser wa-

ter, such as a cooling tower bypass, is not necessary for 

most installations. The minimum entering condenser 

water temperature for full and part load conditions is 

specified in the chiller engineering guide.
Where:

ECWT = Entering Condensing Water Temperature 

LCWT = Leaving Chilled Water Temperature 

C Range = Condensing water temperature range at the  

 

     given load condition.

Min. ECWT = LCWT – C RANGE + 5ºF + 12 (            )

Min. ECWT = LCWT – C RANGE + 2.8ºC + 6.6 (          )

% Load

100

% Load

100

At start-up, the entering condenser water temperature 

may be as much as 25°F (14°C) colder than the stand-

by return chilled water temperature. Cooling tower fan 

cycling will normally provide adequate control of the 

entering condenser water temperature on most instal-

lations.

OPERATING LOGS

A permanent daily record of system operating condi-

tions (temperatures and pressures) recorded at regular 

intervals throughout each 24-hour operating period 

should be kept. Automatic data logging is possible by 

connecting the optional printer and programming the 

DATA LOGGER function. An optional status printer 

is available for this purpose. 

Figure 7 on Page 17 

shows an example log sheet used for recording data 

on chiller systems. Log sheets are available in pads 

of 50 sheets and may be obtained through the nearest 

YORK/Johnson Controls office; request the 

Liquid 

Chiller Log Sheets (Form 16.44-F7)

.

An accurate record of readings serves as a valuable ref-

erence for operating the system. Readings taken when 

a system is newly installed will establish normal condi-

tions with which to compare later readings.
For example, an increase in condenser approach tem-

perature (condenser temperature minus leaving con-

Содержание York YKEP

Страница 1: ...LD15101 CENTRIFUGAL LIQUID CHILLER WITH ECONOMIZER COMPRESSOR OPERATION AND MAINTENANCE Supersedes 160 77 O1 1111 Form 160 77 O1 1020 R 134a Issue Date October 22 2020 MODEL YKEP 2700 3200 TON...

Страница 2: ...This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in th...

Страница 3: ...ior to performing any work on the chiller ASSOCIATED LITERATURE MANUAL DESCRIPTION FORM NUMBER YKEP Installation Re assembly 160 77 N1 YKEP Unit Operation Maintenance 160 77 O1 YKEP Control Center Ope...

Страница 4: ...c needs for the chiller operating conditions and annualized impact realized by the chiller Your lo cal Johnson Controls Branch can propose a customized Planned Service Agreement that leverages real ti...

Страница 5: ...vice 18 Stopping The System 18 Prolonged Shutdown 18 SECTION 3 MAINTENANCE 19 Renewal Parts 19 Oil Return System 19 Checking System For Leaks 21 Conducting An R 22 Pressure Test 22 Vacuum Testing 23 V...

Страница 6: ...am 13 FIGURE 6 Oil Livel Indicator 15 FIGURE 7 Liquid Chiller Log Sheets 17 FIGURE 8 Oil Return System 19 FIGURE 9 Charging Oil Reservoir With Oil 20 FIGURE 10 Evacuation of Chiller 21 FIGURE 11 Satur...

Страница 7: ...city COMPONENTS YKEP chillers are equipped with Single Stage Flash Economizer Primary Compressor K7 Model YDHA119 Economizer Compressor Q3 Model HF416 YORK Unit Mounted Low Voltage Solid State Starter...

Страница 8: ...plied by the customer Available YORK starters include a Floor Mounted Medium Voltage Variable Speed Drive MV VSD Figure 3 on Page 8 and a Unit Mounted MV SSS Figure 4 on Page 8 Customer supplied start...

Страница 9: ...t load ef ficiency by analyzing information fed to it by sensors located throughout the chiller Operational information for the VSD can be found in MV VSD 2300v 6600v Operation Form 160 00 O6 and MV V...

Страница 10: ...sig 16 2 barg Water Boxes The removable water boxes are fabricated of steel The design working pressure is 150 psig 10 3 barg and the boxes are tested at 225 psig 15 5 barg Integral steel water baffle...

Страница 11: ...a combination of prerotation vanes PRV located at the entrance to the compressor impeller op tional hot gas bypass and variable compressor speed to control capacity The position of the vanes is automa...

Страница 12: ...high pressure re frigerant vapor rejects heat to the cooling liquid that is passing through the tubes The cooling liquid will reject its heat to the environment in a cooling tower When the refrigerant...

Страница 13: ...JOHNSON CONTROLS 13 FORM 160 77 O1 ISSUE DATE 10 22 2020 Section 1 System Fundamentals Figure 5 YKEP SYSTEM FLOW DIAGRAM LD15103 1 2 3 4 5 1...

Страница 14: ...FORM 160 77 O1 ISSUE DATE 10 22 2020 JOHNSON CONTROLS 14 This page intentionally left blank...

Страница 15: ...rging Procedure page 20 Always comply with EPAand Local regu lations when removing or disposing of Refrigeration System Oil Figure 6 OIL LIVEL INDICATOR LD08647 PRE STARTING Prior to starting the chil...

Страница 16: ...temperature Pressure and motor current overrides also apply as necessary to maintain operating limits CONDENSERWATERTEMPERATURECONTROL The YKEP chiller is designed to use less power by tak ing advant...

Страница 17: ...3 Inspect the Compressor Drive Motors see motor manufacturers maintenance and service instruc tion supplied with the unit a Meg motor windings Refer to Figure 12 on Page 26 for details 4 Inspect and...

Страница 18: ...ll er is not running brine should not be run through the evaporator However if there is brine running through the evaporator there must be flow through the condenser to prevent tubes from freezing 3 O...

Страница 19: ...inducing the low pressure oil rich liquid to flow from the evaporator through the dehy drator to the compressor sump Changing The Dehydrator To change the dehydrator use the following procedure 1 Iso...

Страница 20: ...onnection to the oil charg ing valve located on the remote oil reservoir cover plate see Figure 8 on Page 19 Do not tighten the connection at the charging valve until after the air is forced out by pu...

Страница 21: ...at section in the fol lowing manner if the location is not definite all the tubes will need to be checked 2 Wash off both tube heads and the ends of all tubes with water Do not use carbon tetrachlorid...

Страница 22: ...ely 75 to 100 PSIG 517 to 690 kPa To be sure that the concentration of refrigerant has reached all parts of the system test for the pres ence of refrigerant with a leak detector at an ap propriate ser...

Страница 23: ...f gauge plus atmospheric pressure Water Freezes bulb temperature of 32 F 0 C or a pressure of 5 mm Hg is reached Refer to Table 1 on Page 23 for corresponding pressure values 4 To improve evacuation c...

Страница 24: ...le vacuum on the system OPERATION Dehydration of a refrigerant system can be obtained by this method because the water present in the sys tem reacts similar to refrigerant By pulling down the pressure...

Страница 25: ...the freezing point is 29 PSIG 200 kPa for R 134a at sea level While charging every precaution must be taken to pre vent moisture laden air from entering the system Fab ricate a suitable charging conn...

Страница 26: ...um during the megging procedure CONDENSERS AND EVAPORATORS Maintenance of condenser and evaporator shells is im portant to provide trouble free operation of the chiller The water side of the tubes in...

Страница 27: ...JOHNSON CONTROLS 27 FORM 160 77 O1 ISSUE DATE 10 22 2020 Section 3 Maintenance Figure 13 MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES LD00476 3...

Страница 28: ...chilled water remove the heads and thoroughly clean each tube with a soft bristle bronze or nylon brush DO NOT USE A STEEL BRISTLE BRUSH A steel brush may damage the tubes Improved results can be obta...

Страница 29: ...er side of the condenser and evaporator in a clean condi tion The use of untreated water in cooling towers closed water systems etc frequently results in one or more of the following Scale Formation C...

Страница 30: ...nalysis 1 X Perform vibration analysis X Clean tubes X 2 Perform Eddy current testing and inspect tubes 2 5 Years Lubricate motor Refer to motor manufacturer s recommendations 1 2 MAINTENANCE REQUIREM...

Страница 31: ...rough the condenser to proper value Abnormally Low Suction Pressure Temperature difference between leaving chilled water and refrigerant in evapo rator greater than normal with high discharge temperat...

Страница 32: ...y inlet Check oil inlet for blockage Symptom Oil Pressure Gradually Decreases Noted by Observation of Daily Log Sheets When oil pump VSD frequency in creases to 55 hz to maintain target oil pressure O...

Страница 33: ...elsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 4 ANALOG INPUT RANGES LOW PRESSURE CHILLERS MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity...

Страница 34: ...ennsylvania USA 17349 Subject to change without notice Printed in USA Copyright by Johnson Controls 2020 ALL RIGHTS RESERVED Form 160 77 O1 1020 Issue Date October 22 2020 Supersedes 160 77 O1 1111 1...

Отзывы: