Johnson Controls York YKEP Скачать руководство пользователя страница 24

FORM 160.77-O1  

ISSUE DATE: 10/22/2020

JOHNSON CONTROLS

24

SECTION 3 - MAINTENANCE

and out the condenser vent. To avoid the possi-

bility of causing leaks, the temperature should be 

brought up slowly so that the tubes and shell are 

heated evenly.

5.  Close the system charging valve and the stop 

valve between the vacuum indicator and the vac-

uum pump. Then disconnect the vacuum pump 

leaving the vacuum indicator in place.

6.  Hold the vacuum pressure obtained in 

Step 3

 in 

the system for 8 hours; the slightest rise in pres-

sure indicates a leak or the presence of moisture, 

or both. If after 24 hours the wet bulb temperature 

in the vacuum indicator has not risen above 40°F 

(4.4°C) or a pressure of 6.3 mm Hg, the system 

may be considered tight.

Be sure the vacuum indicator is valved off 

while holding the system vacuum and be 

sure to open the valve between the vacuum 

indicator and the system when checking 

the vacuum after the 8 hour period.

7.  If the vacuum does not hold for 8 hours within the 

limits specified in 

Step 6

, the leak must be found 

and repaired.

VACUUM DEHYDRATION

To obtain a sufficiently dry system, the following in-

structions have been assembled to provide an effective 

method for evacuating and dehydrating a system in the 

field. Although there are several methods of dehydrat-

ing a system, we are recommending the following, as 

it produces one of the best results, and affords a means 

of obtaining accurate readings as to the extent of de-

hydration.
The equipment required to follow this method of dehy-

dration consists of 

•  a wet bulb indicator or vacuum gauge.
•  a chart showing the relation between dew point 

temperature and pressure in inches of mercury 

(vacuum), (refer to 

Table 1 on Page 23

). 

•  a vacuum pump capable of pumping a suitable 

vacuum on the system.

OPERATION

Dehydration of a refrigerant system can be obtained 

by this method because the water present in the sys-

tem reacts similar to refrigerant. By pulling down the 

pressure in the system to a point where its saturation 

temperature is considerably below that of room tem-

perature, heat will flow from the room through the 

walls of the system and vaporize the water, allowing 

a large percentage of it to be removed by the vacuum 

pump. The length of time necessary for the dehydra-

tion of a system is dependent on the size or volume of 

the system, the capacity and efficiency of the vacuum 

pump, the room temperature and the quantity of water 

present in the system. By using a vacuum indicator, 

the test tube will be evacuated to the same pressure as 

the system, and the distilled water will be maintained 

at the same saturation temperature as any free water in 

the system. This temperature can be observed on the 

thermometer.
If the system has been pressure tested and found to be 

tight prior to evacuation, then the saturation tempera-

ture recordings should follow a curve similar to the 

typical saturation curve shown in 

Figure 11 on Page 

24

.

The temperature of the water in the test tube will drop 

as the pressure decreases, until the boiling point is 

reached, at which point the temperature will level off 

and remain at this level until all of the water in the 

shell is vaporized. When this final vaporization has 

taken place, the pressure and temperature will continue 

to drop until eventually a temperature of 35°F (1.6°C) 

or a pressure of 5 mm Hg. is reached.

LD00474

FIGURE 11 - 

SATURATION CURVE

When this point is reached, practically all of the air 

has been evacuated from the system, but there is still 

a small amount of moisture left. In order to provide 

a medium for carrying this residual moisture to the 

vacuum pump, nitrogen should be introduced into the 

system to bring it to atmospheric pressure and the indi-

Содержание York YKEP

Страница 1: ...LD15101 CENTRIFUGAL LIQUID CHILLER WITH ECONOMIZER COMPRESSOR OPERATION AND MAINTENANCE Supersedes 160 77 O1 1111 Form 160 77 O1 1020 R 134a Issue Date October 22 2020 MODEL YKEP 2700 3200 TON...

Страница 2: ...This individual shall also be familiar with and comply with all applicable governmental standards and regulations pertaining to the task in question SAFETY SYMBOLS The following symbols are used in th...

Страница 3: ...ior to performing any work on the chiller ASSOCIATED LITERATURE MANUAL DESCRIPTION FORM NUMBER YKEP Installation Re assembly 160 77 N1 YKEP Unit Operation Maintenance 160 77 O1 YKEP Control Center Ope...

Страница 4: ...c needs for the chiller operating conditions and annualized impact realized by the chiller Your lo cal Johnson Controls Branch can propose a customized Planned Service Agreement that leverages real ti...

Страница 5: ...vice 18 Stopping The System 18 Prolonged Shutdown 18 SECTION 3 MAINTENANCE 19 Renewal Parts 19 Oil Return System 19 Checking System For Leaks 21 Conducting An R 22 Pressure Test 22 Vacuum Testing 23 V...

Страница 6: ...am 13 FIGURE 6 Oil Livel Indicator 15 FIGURE 7 Liquid Chiller Log Sheets 17 FIGURE 8 Oil Return System 19 FIGURE 9 Charging Oil Reservoir With Oil 20 FIGURE 10 Evacuation of Chiller 21 FIGURE 11 Satur...

Страница 7: ...city COMPONENTS YKEP chillers are equipped with Single Stage Flash Economizer Primary Compressor K7 Model YDHA119 Economizer Compressor Q3 Model HF416 YORK Unit Mounted Low Voltage Solid State Starter...

Страница 8: ...plied by the customer Available YORK starters include a Floor Mounted Medium Voltage Variable Speed Drive MV VSD Figure 3 on Page 8 and a Unit Mounted MV SSS Figure 4 on Page 8 Customer supplied start...

Страница 9: ...t load ef ficiency by analyzing information fed to it by sensors located throughout the chiller Operational information for the VSD can be found in MV VSD 2300v 6600v Operation Form 160 00 O6 and MV V...

Страница 10: ...sig 16 2 barg Water Boxes The removable water boxes are fabricated of steel The design working pressure is 150 psig 10 3 barg and the boxes are tested at 225 psig 15 5 barg Integral steel water baffle...

Страница 11: ...a combination of prerotation vanes PRV located at the entrance to the compressor impeller op tional hot gas bypass and variable compressor speed to control capacity The position of the vanes is automa...

Страница 12: ...high pressure re frigerant vapor rejects heat to the cooling liquid that is passing through the tubes The cooling liquid will reject its heat to the environment in a cooling tower When the refrigerant...

Страница 13: ...JOHNSON CONTROLS 13 FORM 160 77 O1 ISSUE DATE 10 22 2020 Section 1 System Fundamentals Figure 5 YKEP SYSTEM FLOW DIAGRAM LD15103 1 2 3 4 5 1...

Страница 14: ...FORM 160 77 O1 ISSUE DATE 10 22 2020 JOHNSON CONTROLS 14 This page intentionally left blank...

Страница 15: ...rging Procedure page 20 Always comply with EPAand Local regu lations when removing or disposing of Refrigeration System Oil Figure 6 OIL LIVEL INDICATOR LD08647 PRE STARTING Prior to starting the chil...

Страница 16: ...temperature Pressure and motor current overrides also apply as necessary to maintain operating limits CONDENSERWATERTEMPERATURECONTROL The YKEP chiller is designed to use less power by tak ing advant...

Страница 17: ...3 Inspect the Compressor Drive Motors see motor manufacturers maintenance and service instruc tion supplied with the unit a Meg motor windings Refer to Figure 12 on Page 26 for details 4 Inspect and...

Страница 18: ...ll er is not running brine should not be run through the evaporator However if there is brine running through the evaporator there must be flow through the condenser to prevent tubes from freezing 3 O...

Страница 19: ...inducing the low pressure oil rich liquid to flow from the evaporator through the dehy drator to the compressor sump Changing The Dehydrator To change the dehydrator use the following procedure 1 Iso...

Страница 20: ...onnection to the oil charg ing valve located on the remote oil reservoir cover plate see Figure 8 on Page 19 Do not tighten the connection at the charging valve until after the air is forced out by pu...

Страница 21: ...at section in the fol lowing manner if the location is not definite all the tubes will need to be checked 2 Wash off both tube heads and the ends of all tubes with water Do not use carbon tetrachlorid...

Страница 22: ...ely 75 to 100 PSIG 517 to 690 kPa To be sure that the concentration of refrigerant has reached all parts of the system test for the pres ence of refrigerant with a leak detector at an ap propriate ser...

Страница 23: ...f gauge plus atmospheric pressure Water Freezes bulb temperature of 32 F 0 C or a pressure of 5 mm Hg is reached Refer to Table 1 on Page 23 for corresponding pressure values 4 To improve evacuation c...

Страница 24: ...le vacuum on the system OPERATION Dehydration of a refrigerant system can be obtained by this method because the water present in the sys tem reacts similar to refrigerant By pulling down the pressure...

Страница 25: ...the freezing point is 29 PSIG 200 kPa for R 134a at sea level While charging every precaution must be taken to pre vent moisture laden air from entering the system Fab ricate a suitable charging conn...

Страница 26: ...um during the megging procedure CONDENSERS AND EVAPORATORS Maintenance of condenser and evaporator shells is im portant to provide trouble free operation of the chiller The water side of the tubes in...

Страница 27: ...JOHNSON CONTROLS 27 FORM 160 77 O1 ISSUE DATE 10 22 2020 Section 3 Maintenance Figure 13 MOTOR STARTER TEMPERATURE AND INSULATION RESISTANCES LD00476 3...

Страница 28: ...chilled water remove the heads and thoroughly clean each tube with a soft bristle bronze or nylon brush DO NOT USE A STEEL BRISTLE BRUSH A steel brush may damage the tubes Improved results can be obta...

Страница 29: ...er side of the condenser and evaporator in a clean condi tion The use of untreated water in cooling towers closed water systems etc frequently results in one or more of the following Scale Formation C...

Страница 30: ...nalysis 1 X Perform vibration analysis X Clean tubes X 2 Perform Eddy current testing and inspect tubes 2 5 Years Lubricate motor Refer to motor manufacturer s recommendations 1 2 MAINTENANCE REQUIREM...

Страница 31: ...rough the condenser to proper value Abnormally Low Suction Pressure Temperature difference between leaving chilled water and refrigerant in evapo rator greater than normal with high discharge temperat...

Страница 32: ...y inlet Check oil inlet for blockage Symptom Oil Pressure Gradually Decreases Noted by Observation of Daily Log Sheets When oil pump VSD frequency in creases to 55 hz to maintain target oil pressure O...

Страница 33: ...elsius multiply by 5 9 or 0 5556 Example 10 0 F range x 0 5556 5 6 C range Table 4 ANALOG INPUT RANGES LOW PRESSURE CHILLERS MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity...

Страница 34: ...ennsylvania USA 17349 Subject to change without notice Printed in USA Copyright by Johnson Controls 2020 ALL RIGHTS RESERVED Form 160 77 O1 1020 Issue Date October 22 2020 Supersedes 160 77 O1 1111 1...

Отзывы: