FORM 155.21-W2 (1209)

DOWNLOADING HISTORIES TO A LAPTOP FROM 

AN OPTIVIEW CONTROL CENTER

Refer to details explained in FORM 155.21-O1.

 10.  Lead selector and cycling control to provide similar lead 

selection and cycling of lag units for three (3) units is 

available: Kit No. 366-44684D in NEMA I enclosure. 

Consult your YORK/Johnson Controls representative.

11.  Sequence control kits (see 

Fig

's 12, 13 and Note 10)  

assume a constant chilled water flow and a constant 

leaving chilled water temperature to sense the cooling 

load. Sequence control kits are not designed for variable 

chilled water flow or with reset of the leaving chilled 

water temperature (see Fig

s. 18 to 20 and Note 2).

 12.  Maximum allowable current draw between circuits for 

field installed devices is 2 amp holding and 10 amps 

inrush (see OptiView™ Control Center Wiring Diagram 

Form 155.21-W1).

 13.  For required field wiring connections of the chilled water 

pump contacts (terminals  44  and   45  on OptiView™ 

Control Center field wiring terminal block TB2) and 

chilled  water  flow  switch  (terminals  1  and  12  on 

OptiView™ Control Center field wiring terminal board 

(see Wiring Diagram Form 155.21-W1).

    The chilled water flow switch is a safety control. It must 

be connected to prevent operation of the chiller whenever 

chilled water flow is stopped. The use of the chilled water 

flow switch for purposes other than protection of the 

chiller may be accomplished in several ways. Two flow 

switches, a flow switch and a relay or separate contacts 

on the same flow switch.

 15.  Do not apply voltage on field wiring terminal blocks 

TB4 and TB6 in YORK OptiView™ Control Center, as 

115VAC source is fed from terminals  1  and  2  .

16.  Entering and Leaving Chilled and Condenser Water Tem

perature Sensors are supplied by YORK as a standard 

item on all YiA units.

  1.  This drawing shows recommended field control wiring 

modifications (by others) to the standard OptiView™ Con

trol Center Wiring Diagram. For additional single stage 

YIA OptiView wiring details see Form 155.21-W1.

  2.  If more than one of these modifications is to be utilized 

with a particular unit, additional consideration must be 

given to the application to insure proper functioning 

of  the  control  system.  Consult  your YORK/Johnson 

Controls representative.

  3.  The additional controls and wiring for these modifica

tions are to be furnished and installed in the field (by 

others) (see Warnings on page 2).

  4.  The controls specified are recommended for use, but 

other controls of equal specifications are acceptable.

  5.  All wiring shall be in accordance with the National Elec

trical Code, and applicable State and Local Codes.

  6.  Each 115VAC field connected inductive load, i.e. relay 

coil, motor starter coil, etc., shall have a transient sup‑

pressor wired (by others) in parallel with its coil, physi

cally located at the coil. Spare transient suppressors are 

furnished in a bag in the OptiView™ Control Center.

  7.  The OptiView™ Control Center is factory furnished 

for Manual Restart After Power Failure as a standard 

function. The control center can be field changed from 

Manual restart to Auto restart after a power failure, For 

details  consult  a  qualified YORK/Johnson  Controls 

service technician.

  8.  Two (2) unit controls schemes are suitable for 8° – 12°F 

water range. Constant chilled water flow is assumed at 

all loads. For other requirements contact your YORK/

Johnson Controls representative.

NOTES

Содержание York YIA Series

Страница 1: ...nnection for the following operations Remote Stop Contacts See Fig 8 Remote Start Contacts See Fig 8 Remote Local Cycling Devices See Fig 9 Multi unit sequence See Fig 10 1 The OptiView Control Center...

Страница 2: ...ndividual shall also be familiar with and comply with all applicable governmental standards and regula tions pertaining to the task in question safety symbols The following symbols are used in this do...

Страница 3: ...L OPERATION INDIVIDUAL UNIT PUMPS 9 FIG 15 MULTIPLE UNITS TWO PARALLEL OpERATION SINGLE CHILLED WATER PUMP 9 FIG 16 REMOTE Steam Hot Water Limit SETPOINT with 0 10vdc signal 10 FIG 17 REMOTE Steam Hot...

Страница 4: ...R14 2 R58 R52 R50 R40 R38 R22 C8 R16 CR5 R56 R60 R54 R44 R42 R34 R36 R32 R26 R28 R24 R20 R18 R17 R1 R13 U1 U4 U3 R3 R15 R11 U5 R5 C1 CR2 CR3 CR8 RV7 CR7 RV6 CR6 RV3 RV2 R30 R2 Q2 R10 R4 U2 R12 R6 U6...

Страница 5: ...View Control Center is in digital analog or ISN remote op erating mode allow ing for energy management system or remote start stop control Fig 8 2 All chiller safety cut out controls are in the normal...

Страница 6: ...D06824 N O CONTACTS IN CONTROL CENTER RATED 2 AMPS INDUC TION AT 250VAC 30VDC 5 AMPS RESISTIVE AT 250VAC 30VDC closure of the Energy Management System Remote Stop Contacts causes the chiller to shutdo...

Страница 7: ...l type flow switch is used the flow switch uses the cooling effect of liquid to sense flow When the flow of liquid is sensed the solid state relay output is turned on conducting current through the mi...

Страница 8: ...tat RWTwill automatically cycle either 1 or 2 unit Timer 3TR is an additional feature which prevents simultaneous starting of lead and lag unit following a power failure and eliminates nuisance starti...

Страница 9: ...p is avoided When one unit is cut out by the sequence control Fig 12 the temperature of the supply chilled water does not change MULTIPLE UNITS TWO PARALLEL OpERATION SINGLE CHILLED WATER PUMP For thi...

Страница 10: ...inputs as follows Example if the input is 3VDC the setpoint would be set to 73 as follows SETPOINT 100 3 x 9 100 27 73 Therefore a 2 second pulse 10 3 sec 20 4 sec 30 up to 11 sec which will 100 Calc...

Страница 11: ...rammed a setpoint for 44 F base into the OptiView control center and the Remote Reset Range is programmed to be 10 F then the energy management system can remotely reset the setpoint over the range of...

Страница 12: ...et Range setpoint is for 10 F and the local Leaving Chilled Liquid Temperature Setpoint is programmed for 40 F the setpoint would be set to 44 F as follows OFFSET F 5 1 10 10 4 10 10 40 10 4 F SETPOIN...

Страница 13: ...following message SAFETYSHUTDOWN MANUALRESTART and the cause of shutdown RUN CONTACTS REMOTE RUN LIGHT AND SHUTDOWN INDICATOR PLUS EMS When run contacts are required for a Remote Run Light and or Shu...

Страница 14: ...is flowing the flow switch con tact will close If the flow switch opens for 2 seconds the unit shuts down GENERATOR BACKUP TRANSFER During a prolonged power failure the unit will shutdown without goin...

Страница 15: ...and TB6 in YORK OptiView Control Center as 115VAC source is fed from terminals 1 and 2 16 Entering and Leaving Chilled and CondenserWaterTem perature Sensors are supplied by YORK as a standard item on...

Страница 16: ...861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by Johnson Controls Inc 2009 ALL RIGHTS RESERVED Form 155 21 W2 1209 NEW...

Отзывы: