background image

JOHNSON CONTROLS

14

FORM 155.21-W2 (1209)

EVAPORATOR FLOW SENSORS

The  Thermal‑type  flow  sensor  interfaces  with  the 

Microboard  and  Paddle-type  flow  sensor  interfaces 

with the I/O board.

FIG. 23 ‑

 EVAPORATOR FLOW SENSORS

Flash Memory Card Version C.OPT.15.01.XXX and 

later allows the use of either the Thermal-type or Paddle-

type flow sensors on the Style D and later chillers.  

For the program to read the appropriate inputs for the 

flow sensor status, the actual flow sensor type used must 

be  entered  at  the  keypad  SALES  ORDER/CONFIG 

Screen using 

SERVICE access level.  Enter "ANALOG" 

for Thermal-type or "DIGITAL" for Paddle-type.  

When  flow  is  sensed,  the  flow  sensor  contacts  are 

closed.  Opening of the flow sensor contacts (no flow) 

for  2  continuous  seconds  causes  a  cycling  shutdown 

displaying  "CHILLED  LIQUID  FLOW  SWITCH 

OPENED".

THERMAL TYPE FLOW SENSOR

When the Thermal-type flow switch is used, the flow 

switch uses the cooling effect of liquid to sense flow.  

When the flow of liquid is sensed, the relay output is 

turned on conducting current through the microboard 

load  resistor  to  the  +5VDC  applying  greater  than 

+4VDC to the microboard input J14-5.  

When no flow of liquid is sensed, the relay output is 

turned off, this results in less than 1VDC to the micro

board input. 

LD09134

J7-

MICROBOARD

THERMAL-TYPE FLOW SENSOR

12

1

TB4

I/O BOARD

PADDLE-TYPE FLOW SENSOR

EVAPORATOR

PADDLE TYPE FLOW SENSOR

When Evaporator Water is flowing, the flow switch con-

tact will close. If the flow switch opens for 2 seconds, the 

unit shuts down.

GENERATOR BACKUP TRANSFER

During a prolonged power failure the unit will shutdown 

without going through a dilution cycle. This could cause 

the  unit  to  crystallize  depending  on  the  duration  of 

power failure. By adding a small standby AC 3-phase 

power supply, the solution pump can perform a limited 

dilution cycle.

During a power failure a subsequent limited dilution 

cycle, the system will NOT be able to produce chilled 

water.

If unit experiences a power failure, the input (95) on 

the I/O board is checked for a closed contact (indicating 

that a standby power supply is online). No matter what 

the solution concentration is at the time of the power 

failure or what the dilution cycle to last NO longer than 

4 hours. The generator will supply power to the unit 

mounted  power  panel,  which  will  supply  OptiView 

control panel and solution pump for the dilution period. 

During this period, the unit will continue to monitor if 

the fault condition has been cleared to switch to a normal 

dilution cycle. If condenser flow is sensed through the 

flow switch during the limited dilution cycle, the dilu

tion cycle will cease.

Refer to 155.21-O1 for additional details on the limited 

dilution cycle.

Refer to 155.21-EG1 for minimum power requirements 

for standby power supply.

FIG. 24 – 

 PADDLE TYPE FLOW SENSOR

FIG. 25 – 

GENERATOR BACK-UP TRANSFER

LD04400

95

BACKUP GENERATOR TRANSFER 

CONTACT CLOSES ON POWER FAILURE 

(SUPPLIED BY OTHERS)

LD14446

I/O BOARD

PADDLE-TYPE FLOW SENSOR

(DIGITAL)

MICROBOARD

THERMAL-TYPE FLOW SENSOR

(ANALOG)

Содержание York YIA Series

Страница 1: ...nnection for the following operations Remote Stop Contacts See Fig 8 Remote Start Contacts See Fig 8 Remote Local Cycling Devices See Fig 9 Multi unit sequence See Fig 10 1 The OptiView Control Center...

Страница 2: ...ndividual shall also be familiar with and comply with all applicable governmental standards and regula tions pertaining to the task in question safety symbols The following symbols are used in this do...

Страница 3: ...L OPERATION INDIVIDUAL UNIT PUMPS 9 FIG 15 MULTIPLE UNITS TWO PARALLEL OpERATION SINGLE CHILLED WATER PUMP 9 FIG 16 REMOTE Steam Hot Water Limit SETPOINT with 0 10vdc signal 10 FIG 17 REMOTE Steam Hot...

Страница 4: ...R14 2 R58 R52 R50 R40 R38 R22 C8 R16 CR5 R56 R60 R54 R44 R42 R34 R36 R32 R26 R28 R24 R20 R18 R17 R1 R13 U1 U4 U3 R3 R15 R11 U5 R5 C1 CR2 CR3 CR8 RV7 CR7 RV6 CR6 RV3 RV2 R30 R2 Q2 R10 R4 U2 R12 R6 U6...

Страница 5: ...View Control Center is in digital analog or ISN remote op erating mode allow ing for energy management system or remote start stop control Fig 8 2 All chiller safety cut out controls are in the normal...

Страница 6: ...D06824 N O CONTACTS IN CONTROL CENTER RATED 2 AMPS INDUC TION AT 250VAC 30VDC 5 AMPS RESISTIVE AT 250VAC 30VDC closure of the Energy Management System Remote Stop Contacts causes the chiller to shutdo...

Страница 7: ...l type flow switch is used the flow switch uses the cooling effect of liquid to sense flow When the flow of liquid is sensed the solid state relay output is turned on conducting current through the mi...

Страница 8: ...tat RWTwill automatically cycle either 1 or 2 unit Timer 3TR is an additional feature which prevents simultaneous starting of lead and lag unit following a power failure and eliminates nuisance starti...

Страница 9: ...p is avoided When one unit is cut out by the sequence control Fig 12 the temperature of the supply chilled water does not change MULTIPLE UNITS TWO PARALLEL OpERATION SINGLE CHILLED WATER PUMP For thi...

Страница 10: ...inputs as follows Example if the input is 3VDC the setpoint would be set to 73 as follows SETPOINT 100 3 x 9 100 27 73 Therefore a 2 second pulse 10 3 sec 20 4 sec 30 up to 11 sec which will 100 Calc...

Страница 11: ...rammed a setpoint for 44 F base into the OptiView control center and the Remote Reset Range is programmed to be 10 F then the energy management system can remotely reset the setpoint over the range of...

Страница 12: ...et Range setpoint is for 10 F and the local Leaving Chilled Liquid Temperature Setpoint is programmed for 40 F the setpoint would be set to 44 F as follows OFFSET F 5 1 10 10 4 10 10 40 10 4 F SETPOIN...

Страница 13: ...following message SAFETYSHUTDOWN MANUALRESTART and the cause of shutdown RUN CONTACTS REMOTE RUN LIGHT AND SHUTDOWN INDICATOR PLUS EMS When run contacts are required for a Remote Run Light and or Shu...

Страница 14: ...is flowing the flow switch con tact will close If the flow switch opens for 2 seconds the unit shuts down GENERATOR BACKUP TRANSFER During a prolonged power failure the unit will shutdown without goin...

Страница 15: ...and TB6 in YORK OptiView Control Center as 115VAC source is fed from terminals 1 and 2 16 Entering and Leaving Chilled and CondenserWaterTem perature Sensors are supplied by YORK as a standard item on...

Страница 16: ...861 1001 www york com P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in USA Copyright by Johnson Controls Inc 2009 ALL RIGHTS RESERVED Form 155 21 W2 1209 NEW...

Отзывы: