JOHNSON CONTROLS
90
FORM 150.62-NM9 (709)
UNIT CONTROLS
Incorrect programming may cause
damage to compressors.
Also see the UNIT KEYS PROGRAMMING QUICK
REFERENCE LIST in Table 17, Page 91.
CLOCK
The CLOCK display shows the current day, time, and
date. Pressing the CLOCK key will show the current
day, time, and date.
It is important that the date and time be correct, otherwise the
daily schedule will not function as desired if programmed.
In addition, for ease of troubleshooting via the History print-
outs, the day, time, and date should be correct.
To change the day, time, and date press the CLOCK
key. The display will show something similar to the
following:
T O D A Y I S F R I 0 8 : 5 1 A M
2 5 j A N 0 2
The line under the F is the cursor. If the day is correct,
press the ENTER/ADV key. The cursor will move under
the 0 in 08 hours. If the day is incorrect, press the UP
or DOWN
arrow keys until the desired day is displayed
and then press the ENTER/ADV key at which time the
day will be accepted and the cursor will move under
the first digit of the “2 digit hour”. In a similar manner,
the hour, minute, meridian, month, day, and year may
be programmed, whenever the cursor is under the first
letter/numeral of the item. Press the UP or DOWN ar-
row keys until the desired hour, minute, meridian, day,
month, and year are displayed. Pressing the ENTER/
ADV Key will save the valve and move the cursor on
to the next programmable variable.
S O F T S T A R T
D I S A B L E D
This MUST be selected on all chillers without the soft
start option.
Option 13 – Unit Type:
U N I T T Y P E
L I Q U I D C H I L L E R
The UNIT TYPE message cannot be modified under
the unit keys.
“LIqUID CHILLER” must be dis
-
played, or damage to compressors or
other components will occur if oper
-
ated in the HEAT PUMP or CON
-
DENSING UNIT modes.
If unit type needs to be changed to make the unit a
liquid chiller, remove the jumper between J11-7 and
J11-12 on the I/O Board and reapply power to the
micropanel.
Option 14 – Refrigerant Type:
R E F R I G E R A N T T Y P E
R - 2 2
Refrigerant type R-22 or R-407C may be selected un-
der Service Mode. Refrigerant type is displayed under
the Options Key, but is only programmable in Service
Mode.
Incorrect programming may cause
damage to compressors.
Option 15 – Expansion Valve Type:
E X P A N S I O N V A L V E T Y P E
T H E R M O S T A T I C
Expansion valve type, thermostatic or electronic
may be selected under Service Mode. Expansion valve
type is displayed under the Options key, but is only
programmable in Service Mode.
Содержание YORK YCAL0043E Series
Страница 21: ...JOHNSON CONTROLS 21 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 102: ...JOHNSON CONTROLS 102 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 123: ...JOHNSON CONTROLS 123 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 125: ...JOHNSON CONTROLS 125 FORM 150 62 NM9 709 4 ...
Страница 127: ...JOHNSON CONTROLS 127 FORM 150 62 NM9 709 4 ...
Страница 129: ...JOHNSON CONTROLS 129 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 131: ...JOHNSON CONTROLS 131 FORM 150 62 NM9 709 4 LD08855 035 21627 000 REV B ...
Страница 133: ...JOHNSON CONTROLS 133 FORM 150 62 NM9 709 4 035 19213 106 REV C ...
Страница 135: ...JOHNSON CONTROLS 135 FORM 150 62 NM9 709 4 ...
Страница 137: ...JOHNSON CONTROLS 137 FORM 150 62 NM9 709 4 ...
Страница 139: ...JOHNSON CONTROLS 139 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 141: ...JOHNSON CONTROLS 141 FORM 150 62 NM9 709 4 035 21628 000 REV B ...
Страница 143: ...JOHNSON CONTROLS 143 FORM 150 62 NM9 709 4 035 19213 105 REV C ...
Страница 145: ...JOHNSON CONTROLS 145 FORM 150 62 NM9 709 4 ...
Страница 147: ...JOHNSON CONTROLS 147 FORM 150 62 NM9 709 4 ...
Страница 149: ...JOHNSON CONTROLS 149 FORM 150 62 NM9 709 4 ...
Страница 151: ...JOHNSON CONTROLS 151 FORM 150 62 NM9 709 4 035 21625 000 REV B ...
Страница 153: ...JOHNSON CONTROLS 153 FORM 150 62 NM9 709 4 035 19213 104 REV C ...
Страница 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM9 709 4 ...
Страница 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM9 709 4 ...
Страница 159: ...JOHNSON CONTROLS 159 FORM 150 62 NM9 709 4 ...
Страница 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM9 709 4 035 21626 000 REV B ...
Страница 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM9 709 4 035 19213 103 REV C ...
Страница 165: ...JOHNSON CONTROLS 165 FORM 150 62 NM9 709 4 ...
Страница 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM9 709 4 LD08833 ...
Страница 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM9 709 4 035 21610 104 REV ...
Страница 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM9 709 4 035 18150 102 REV D ...
Страница 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM9 709 4 ...
Страница 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM9 709 4 ...
Страница 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM9 709 4 035 21606 104 REV ...