JOHNSON CONTROLS
19
FORM 150.62-NM9 (709)
1
ELECTRICAL NOTES AND LEGEND
NOTES:
1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of
the rated load amps for all other loads included in the circuit, per N.E.C. Article 430.33. If the Factory-mounted
Control Transformer is provided, add the following to the system MCA values in the electrical tables for the
system supplying power to the optional transformer. -17, add 2.5 amps; -28, add 2.3 amps; -40, add 1.5 amps,
-46, add 1.3 amps; -58, add 1 amp.
2. The minimum recommended disconnect switch is based on 115% of the rated load amps for all loads included
in the circuit, per N.E.C. Article 440.12 (A) 1.
3. Minimum fuse size is based upon 150% of the rated load amps for the largest motor plus 100% of the rated load
amps for all other loads included in the circuit to avoid nuisance trips at start-up due to lock rotor amps. It is not
recommended in applications where brown outs, frequent starting and stopping of the unit, and/or operation at
ambient temperatures in excess of 95°F is anticipated.
4. Maximum fuse size is based upon 225% of the rated load amps for the largest motor plus 100% of the rated
load amps for all other loads included in the circuit, per N.E.C. Article 440.22.
5. Circuit breakers must be U.L. listed and CSA certified and maximum size is based on 225% of the rated load
amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit. Excep-
tion: YCAL0043 and YCAL0057 must have the optional factory overloads installed to use a standard circuit
breaker. Otherwise, an HACR-type circuit breakers must be used. Maximum HACR circuit breaker rating is
based on 225% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads
included in the circuit.
6. The “INCOMING WIRE RANGE” is the minimum and maximum wire size that can be accommodated by
the unit wiring lugs. The (2) preceding the wire range indicates the number of termination points available per
phase of the wire range specified. Actual wire size and number of wires per phase must be determined based on
the National Electrical Code, using copper connectors only. Field wiring must also comply with local codes.
7. A ground lug is provided for each compressor system to accommodate a field grounding conductor per N.E.C.
Table 250.122. A control circuit grounding lug is also supplied.
8. The supplied disconnect is a “Disconnecting Means” as defined in the N.E.C. 100.I, and is intended for isolat
-
ing the unit for the available power supply to perform maintenance and troubleshooting. This disconnect is not
intended to be a Load Break Device.
9. Field Wiring by others which complies to the National Electrical Code and Local Codes.
VOLTAGE CODE
-50 = 380/415-3-50
LEGEND
ACR-LINE
ACROSS -THE-LINE START
C.B.
CIRCUIT BREAKER
D.E.
DUAL ELEMENT FUSE
DISC SW
DISCONNECT SWITCH
FACT MOUNT CB
FACTORY-MOUNTED CIRCUIT BREAKER
FLA
FULL LOAD AMPS
HZ
HERTZ
MAX
MAXIMUM
MCA
MINIMUM CIRCUIT AMPACITY
MIN
MINIMUM
MIN NF
MINIMUM NON FUSED
RLA
RATED LOAD AMPS
S.P. WIRE
SINGLE-POINT WIRING
UNIT MTD SERV SW
UNIT MOUNTED SERVICE (NON-FUSED
DISCONNECT SWITCH)
LRA
LOCKED ROTOR AMPS
Field Wiring
Factory Wiring
LEGEND:
Содержание YORK YCAL0043E Series
Страница 21: ...JOHNSON CONTROLS 21 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 102: ...JOHNSON CONTROLS 102 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 123: ...JOHNSON CONTROLS 123 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 125: ...JOHNSON CONTROLS 125 FORM 150 62 NM9 709 4 ...
Страница 127: ...JOHNSON CONTROLS 127 FORM 150 62 NM9 709 4 ...
Страница 129: ...JOHNSON CONTROLS 129 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 131: ...JOHNSON CONTROLS 131 FORM 150 62 NM9 709 4 LD08855 035 21627 000 REV B ...
Страница 133: ...JOHNSON CONTROLS 133 FORM 150 62 NM9 709 4 035 19213 106 REV C ...
Страница 135: ...JOHNSON CONTROLS 135 FORM 150 62 NM9 709 4 ...
Страница 137: ...JOHNSON CONTROLS 137 FORM 150 62 NM9 709 4 ...
Страница 139: ...JOHNSON CONTROLS 139 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 141: ...JOHNSON CONTROLS 141 FORM 150 62 NM9 709 4 035 21628 000 REV B ...
Страница 143: ...JOHNSON CONTROLS 143 FORM 150 62 NM9 709 4 035 19213 105 REV C ...
Страница 145: ...JOHNSON CONTROLS 145 FORM 150 62 NM9 709 4 ...
Страница 147: ...JOHNSON CONTROLS 147 FORM 150 62 NM9 709 4 ...
Страница 149: ...JOHNSON CONTROLS 149 FORM 150 62 NM9 709 4 ...
Страница 151: ...JOHNSON CONTROLS 151 FORM 150 62 NM9 709 4 035 21625 000 REV B ...
Страница 153: ...JOHNSON CONTROLS 153 FORM 150 62 NM9 709 4 035 19213 104 REV C ...
Страница 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM9 709 4 ...
Страница 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM9 709 4 ...
Страница 159: ...JOHNSON CONTROLS 159 FORM 150 62 NM9 709 4 ...
Страница 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM9 709 4 035 21626 000 REV B ...
Страница 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM9 709 4 035 19213 103 REV C ...
Страница 165: ...JOHNSON CONTROLS 165 FORM 150 62 NM9 709 4 ...
Страница 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM9 709 4 LD08833 ...
Страница 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM9 709 4 035 21610 104 REV ...
Страница 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM9 709 4 035 18150 102 REV D ...
Страница 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM9 709 4 ...
Страница 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM9 709 4 ...
Страница 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM9 709 4 035 21606 104 REV ...