JOHNSON CONTROLS
83
FORM 150.62-NM9 (709)
2
d
D I S C H A R G E P R E S S U R E
C U T O U T = 3 9 5 P S I G
DISCHARGE PRESSURE CUTOUT is the discharge
pressure at which the system will shutdown as monitored
by the
optional
discharge transducer. This is a software
shutdown that acts as a backup for the mechanical high
pressure switch located in the refrigerant circuit. The
system can restart when the discharge pressure drops
40 PSIG (2.76 BARG) below the cutout point.
If the optional discharge pressure transducer is not
installed, this programmable safety would not apply.
It should be noted that every system has a
mechanical
high pressure cutout that protects against excessive
high discharge pressure regardless of whether or not the
optional discharge pressure is installed.
S U C T I O N P R E S S U R E
C U T O U T = 4 4 . 0 P S I G
The SUCTION PRESSURE CUTOUT protects the chiller
from an evaporator freeze-up. If the suction pressure drops
below the cutout point, the system will shut down.
There are some exceptions when the
suction pressure is permitted to tem
-
porarily drop below the cutout point.
Details are explained under the topic
of SYSTEM SAFETIES.
L O W A M B I E N T T E M P
C U T O U T = 2 5 . 0 ° F
The LOW AMBIENT TEMP CUTOUT allows the user
to select the chiller outside ambient temperature cutout
point. If the ambient falls below this point, the chiller
will shut down. Restart can occur when temperature
rises 2°F (1.11°C) above the cutout setpoint.
L E A V I N G L I Q U I D T E M P
C U T O U T = 3 6 . 0 ° F
The LEAVING LIQUID TEMP CUTOUT protects the
chiller from an evaporator freeze-up. Anytime the leav-
ing chilled liquid temperature drops to the cutout point,
the chiller shuts down. Restart will be permitted when
the leaving chilled liquid temperature rises 2°F (1.11°C)
above the cutout setpoint.
When water cooling mode is programmed (OPTIONS
key), the value is fixed at 36.0°F (2.22°C) and cannot
be changed. Glycol cooling mode can be programmed
to values listed in Table 14.
A N T I R E C Y C L E T I M E R
= 6 0 0 S E C
The programmable anti-recycle timer assures that sys-
tems do not cycle. This timer is programmable under the
PROGRAM key between 300 - 600 seconds. Whenever
possible, to reduce cycling and motor heating, the anti-
recycle timer should be adjusted as high as possible. The
programmable anti-recycle timer starts the timer when
the first compressor in a system starts. The timer begins
to count down. If all the compressors in the circuit cycle
off, a compressor within the circuit will not be permit-
ted to start until the anti-recycle timer has timed out. If
the lead system has run for less than 5 minutes, 3 times
in a row, the anti-recycle timer will be extended to 10
minutes maximum.
F A N C O N T R O L O N
P R E S S U R E = X X X P S I G
The Fan Control On-Pressure is the programmed pressure
value that is used to stage the condenser fans on, in relation
to discharge pressure. Refer to Condenser Fan Control in
the UNIT OPERATION section and Tables 21 - 26.
The microprocessor will not allow program
-
ming the “FAN CONTROL ON PRES
-
SURE” minus the “FAN CONTROL
DIFFERENTIAL OFF PRESSURE”
below 160PSIG. This assures discharge
pressure does not drop too low.
F A N D I F F E R E N T I A L O F F
P R E S S U R E = X X X P S I G
The Fan Differential Off Pressure is the programmed
differential pressure value that is used to stage the con-
denser fans off, in relation to discharge pressure. Refer
to Condenser Fan Control in the UNIT OPERATION
section and Tables 21 - 26.
The microprocessor will not allow program
-
ming the “FAN CONTROL ON PRES
-
SURE” minus the “FAN CONTROL
DIFFERENTIAL OFF PRESSURE”
below 160 PSIG. This assures discharge
pressure does not drop too low.
Содержание YORK YCAL0043E Series
Страница 21: ...JOHNSON CONTROLS 21 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 102: ...JOHNSON CONTROLS 102 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 123: ...JOHNSON CONTROLS 123 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 125: ...JOHNSON CONTROLS 125 FORM 150 62 NM9 709 4 ...
Страница 127: ...JOHNSON CONTROLS 127 FORM 150 62 NM9 709 4 ...
Страница 129: ...JOHNSON CONTROLS 129 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 131: ...JOHNSON CONTROLS 131 FORM 150 62 NM9 709 4 LD08855 035 21627 000 REV B ...
Страница 133: ...JOHNSON CONTROLS 133 FORM 150 62 NM9 709 4 035 19213 106 REV C ...
Страница 135: ...JOHNSON CONTROLS 135 FORM 150 62 NM9 709 4 ...
Страница 137: ...JOHNSON CONTROLS 137 FORM 150 62 NM9 709 4 ...
Страница 139: ...JOHNSON CONTROLS 139 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 141: ...JOHNSON CONTROLS 141 FORM 150 62 NM9 709 4 035 21628 000 REV B ...
Страница 143: ...JOHNSON CONTROLS 143 FORM 150 62 NM9 709 4 035 19213 105 REV C ...
Страница 145: ...JOHNSON CONTROLS 145 FORM 150 62 NM9 709 4 ...
Страница 147: ...JOHNSON CONTROLS 147 FORM 150 62 NM9 709 4 ...
Страница 149: ...JOHNSON CONTROLS 149 FORM 150 62 NM9 709 4 ...
Страница 151: ...JOHNSON CONTROLS 151 FORM 150 62 NM9 709 4 035 21625 000 REV B ...
Страница 153: ...JOHNSON CONTROLS 153 FORM 150 62 NM9 709 4 035 19213 104 REV C ...
Страница 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM9 709 4 ...
Страница 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM9 709 4 ...
Страница 159: ...JOHNSON CONTROLS 159 FORM 150 62 NM9 709 4 ...
Страница 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM9 709 4 035 21626 000 REV B ...
Страница 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM9 709 4 035 19213 103 REV C ...
Страница 165: ...JOHNSON CONTROLS 165 FORM 150 62 NM9 709 4 ...
Страница 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM9 709 4 LD08833 ...
Страница 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM9 709 4 035 21610 104 REV ...
Страница 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM9 709 4 035 18150 102 REV D ...
Страница 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM9 709 4 ...
Страница 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM9 709 4 ...
Страница 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM9 709 4 035 21606 104 REV ...