UNIT CONTROLS
M A N U A L O V E R R I D E M O D E
X X X X X X X X X
Displays whether manual override was Enabled or
Disabled.
C U R R E N T F E E D B A C K
X X X X X X X X X X X X X X X X
Displays type of Current Feedback utilized.
S O F T S T A R T
X X X X X X X
Displays whether the optional European Soft Start was
installed and selected.
D I S C H A R G E P R E S S U R E
C U T O U T = X X X X P S I G
Displays the programmed Discharge Pressure Cutout.
S U C T I O N P R E S S U R E
C U T O U T = X X X X P S I G
Displays the programmed Suction Pressure Cutout.
L O W A M B I E N T T E M P
C U T O U T = X X X . X ° F
Displays the programmed Low Ambient Cutout.
L E A V I N G L I Q U I D T E M P
C U T O U T = X X X . X ° F
Displays the Leaving Liquid Temp. Cutout pro-
grammed.
F A N C O N T R O L O N
P R E S S U R E = X X X P S I G
Displays the programmed Fan On Pressure.
F A N D I F F E R E N T I A L O F F
P R E S S U R E = P S I G
Displays the programmed Fan Off Differential.
The UP and DOWN arrows are used to scroll forward
and backward through the history buffer to display the
shutdown conditions stored at the instant the fault oc-
curred. The
↓
arrow key scrolls through the displays in
the order they appear below:
U N I T F A U L T :
L O W L I Q U I D T E M P
Displays the type of fault that occurred.
U N I T T Y P E
L I Q U I D C H I L L E R
Displays the type of chiller; Liquid, Condensing Unit
or Heat Pump.
C H I L L E D L I Q U I D
X X X X X
Displays the chilled liquid type; Water or Glycol.
A M B I E N T C O N T R O L
X X X X X X X X X X
Displays the type of ambient control; Standard or
Low Ambient. This message will not be displayed on
YCAL0287 – YCAL0377.
L O C A L / R E M O T E M O D E
X X X X X X X X X
Displays Local or Remote control selection.
C O N T R O L M O D E
L E A V I N G L I Q U I D
Displays the type of chilled liquid control; Leaving or
Return.
L E A D / L A G C O N T R O L
X X X X X X X X
Displays the type of lead/lag control; Manual System 1,
Manual System 2 or Automatic. This is only selectable
on 2-system chillers.
F A N C O N T R O L
D I S C H A R G E P R E S S U R E
Displays the type of fan control; Discharge Pressure or
Ambient and Discharge Pressure. This message will not
be displayed on YCAL0287 – YCAL0377.
Содержание YORK YCAL0043E Series
Страница 21: ...JOHNSON CONTROLS 21 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 102: ...JOHNSON CONTROLS 102 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 123: ...JOHNSON CONTROLS 123 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 125: ...JOHNSON CONTROLS 125 FORM 150 62 NM9 709 4 ...
Страница 127: ...JOHNSON CONTROLS 127 FORM 150 62 NM9 709 4 ...
Страница 129: ...JOHNSON CONTROLS 129 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 131: ...JOHNSON CONTROLS 131 FORM 150 62 NM9 709 4 LD08855 035 21627 000 REV B ...
Страница 133: ...JOHNSON CONTROLS 133 FORM 150 62 NM9 709 4 035 19213 106 REV C ...
Страница 135: ...JOHNSON CONTROLS 135 FORM 150 62 NM9 709 4 ...
Страница 137: ...JOHNSON CONTROLS 137 FORM 150 62 NM9 709 4 ...
Страница 139: ...JOHNSON CONTROLS 139 FORM 150 62 NM9 709 THIS PAGE INTENTIONALLY LEFT BLANK ...
Страница 141: ...JOHNSON CONTROLS 141 FORM 150 62 NM9 709 4 035 21628 000 REV B ...
Страница 143: ...JOHNSON CONTROLS 143 FORM 150 62 NM9 709 4 035 19213 105 REV C ...
Страница 145: ...JOHNSON CONTROLS 145 FORM 150 62 NM9 709 4 ...
Страница 147: ...JOHNSON CONTROLS 147 FORM 150 62 NM9 709 4 ...
Страница 149: ...JOHNSON CONTROLS 149 FORM 150 62 NM9 709 4 ...
Страница 151: ...JOHNSON CONTROLS 151 FORM 150 62 NM9 709 4 035 21625 000 REV B ...
Страница 153: ...JOHNSON CONTROLS 153 FORM 150 62 NM9 709 4 035 19213 104 REV C ...
Страница 155: ...JOHNSON CONTROLS 155 FORM 150 62 NM9 709 4 ...
Страница 157: ...JOHNSON CONTROLS 157 FORM 150 62 NM9 709 4 ...
Страница 159: ...JOHNSON CONTROLS 159 FORM 150 62 NM9 709 4 ...
Страница 161: ...JOHNSON CONTROLS 161 FORM 150 62 NM9 709 4 035 21626 000 REV B ...
Страница 163: ...JOHNSON CONTROLS 163 FORM 150 62 NM9 709 4 035 19213 103 REV C ...
Страница 165: ...JOHNSON CONTROLS 165 FORM 150 62 NM9 709 4 ...
Страница 167: ...JOHNSON CONTROLS 167 FORM 150 62 NM9 709 4 LD08833 ...
Страница 169: ...JOHNSON CONTROLS 169 FORM 150 62 NM9 709 4 035 21610 104 REV ...
Страница 171: ...JOHNSON CONTROLS 171 FORM 150 62 NM9 709 4 035 18150 102 REV D ...
Страница 173: ...JOHNSON CONTROLS 173 FORM 150 62 NM9 709 4 ...
Страница 175: ...JOHNSON CONTROLS 175 FORM 150 62 NM9 709 4 ...
Страница 177: ...JOHNSON CONTROLS 177 FORM 150 62 NM9 709 4 035 21606 104 REV ...