TROUBLESHOOTING (CONT’D)
PROBLEM
CAUSE
SOLUTION
LOW LIQUID TEMP FAULT
1. Improperly adjusted leaving
chilled liquid temp. cutout (glycol
only).
1. Re-program the leaving chilled liquid temp.
cutout.
2. Micro panel setpoint/range
values improperly programmed.
2. Re-adjust setpoint/range.
3. Chilled liquid flow too low.
3. Increase chilled liquid flow.
Refer to
Limitations in Installation section.
4. Defective LWT or RWT sensor
(assure the sensor is properly
installed in the bottom of the well
with a generous amount of heat)
conductive compound).
4. Compare sensor against a known good
Temperature sensing device.
Refer to
Service section for temp./voltage table.
MP / HPCO FAULT
1. Compressor internal motor
protector (MP) open.
1. Verify refrigerant charge is not low. Verify
superheat setting of 10 °F to 15 °F (5.6 °C to
8.3 °C). Verify correct compressor rotation.
Verify compressor is not overloaded.
2. External overload tripped.
2. Determine cause and reset.
3. HPCO switch open.
3.
See “High Press. Disch.” Fault.
4. Defective HPCO switch.
4. Replace HPCO switch.
5. Defective CR relay.
5. Replace relay.
COMPRESSOR(S) WON’T START
1. Demand not great enough.
1. No problem.
Consult “Installation” Manual to
aid in understanding compressor operation
and capacity control.
2. Defective water temperature
sensor.
2. Compare the display with a thermometer.
Should be /- 2 degrees.
Refer to
Service section for RWT/LWT temp./voltage
table.
3. Contactor/Overload failure.
3. Replace defective part.
4. Compressor failure.
4. Diagnose cause of failure and replace.
LACK OF COOLING EFFECT
1. Fouled evaporator surface.
Low suction pressure will be
observed.
1. Contact the local Johnson Controls service
representative.
2. Improper flow through the
evaporator.
2. Reduce flow to within chiller design specs.
See Limitations in Installation section.
3. Low refrigerant charge. Low
suction pressure will be
observed.
3. Check subcooling and add charge as
needed.
TABLE 27 (cont’d) – TROUBLESHOOTING
Содержание YORK Tempo YLAA Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Страница 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Страница 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Страница 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Страница 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Страница 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Страница 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Страница 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Страница 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Страница 90: ...JOHNSON CONTROLS 90 FORM 150 72 NM1 1020 Technical Data DUAL PUMP WIRING LD13237 FIG 21 DUAL PUMP WIRING...
Страница 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Страница 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Страница 160: ...JOHNSON CONTROLS 160 FORM 150 72 NM1 1020 Unit Operation FIG 28 CONDENSER FAN LOCATIONSWIRING DIAGRAMS...
Страница 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...