JOHNSON CONTROLS
146
FORM 150.72-NM1 (1020)
Unit Controls
The Number of Fans Per System must be programmed as
needed to match the number of fans on each system.
Depending on the option, the trip voltage for a
specific system or unit high current trip can be
programmed. It also calibrates the current readout
under the OPER DATA key. The approximate
programmed value is calculated using the following
formulas:
System Trip Volts
For individual system high current trip programming
on chillers:
• Add the sum of the compressor and fan RLA’s in
the system
• Multiply the sum by 1.25
• Divide by 225A
• The resulting voltage is the value that should be
programmed
For example, if fan and compressor RLA’s total 100A:
The programmed value will be 2.8V. A similar
calculation and programming will be necessary for the
other system in a 2-system chiller.
N U
M
B E R
O F F A N S
P E R S Y S T E
M = X
S Y S X T R I P V O L T S
= X . X V O L T S
U N I T T R I P V O L T S
= X . X V O L T S
5V x 100A x 1.25 = 625VA
= 2.8V
225A 225A
The Fan Differential Off Pressure is the programmed
differential pressure value that is used to stage the
condenser fans off, in relation to discharge pressure.
Refer
to Condenser Fan Control in the UNIT OPERATION
section and Tables 17 and 18.
The TOTAL NUMBER OF COMPRESSORS is the total
quantity of compressors in the chiller, and determines
the stages of cooling available. Note in Table 11, the
chiller may have single or dual systems. Dual system
units may have 4, 5 or 6 compressors.
This MUST be programmed correctly
to assure proper chiller operation.
F A N D I F F E R E N T I A L O F F
P R E S S U R E = X X X P S I G
T O T A L N U M B E R O F
C O M P R E S S O R S = 6
Содержание YORK Tempo YLAA Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Страница 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Страница 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Страница 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Страница 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Страница 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Страница 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Страница 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Страница 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Страница 90: ...JOHNSON CONTROLS 90 FORM 150 72 NM1 1020 Technical Data DUAL PUMP WIRING LD13237 FIG 21 DUAL PUMP WIRING...
Страница 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Страница 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Страница 160: ...JOHNSON CONTROLS 160 FORM 150 72 NM1 1020 Unit Operation FIG 28 CONDENSER FAN LOCATIONSWIRING DIAGRAMS...
Страница 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...