FORM 150.72-NM1 (1020)
145
JOHNSON CONTROLS
7
Program Key
There are several operating parameters under the
PROGRAM key that are programmable. These setpoints
can be changed by pressing the PROGRAM key, and
then the ENTER/ADV key to enter Program Mode.
Continuing to press the ENTER/ADV key will display
each operating parameter. While a particular parameter
is being displayed, the ↑ (UP) and ↓ (DOWN) arrow
keys can be used to change the value. After the value is
changed, the ENTER/ADV key must be pressed to enter
the data into memory. Table 11 shows the programmable
limits and default values for each operating parameter.
Following are the displays for the programmable values
in the order they appear:
DISCHARGE PRESSURE CUTOUT is the discharge
pressure at which the system will shutdown as monitored
by the optional discharge transducer. This is a software
shutdown that acts as a backup for the mechanical high
pressure switch located in the refrigerant circuit. The
system can restart when the discharge pressure drops
40 PSIG (2.76 barg) below the cutout point.
If the optional discharge pressure transducer is not
installed, this programmable safety would not apply.
It should be noted that every system has a mechanical
high pressure cutout that protects against excessive
high discharge pressure regardless of whether or not the
optional discharge pressure is installed.
The SUCTION PRESSURE CUTOUT protects the
chiller from an evaporator freeze-up. If the suction
pressure drops below the cutout point, the system will
shut down. Typically, the cutout should be set to 80 PSIG
(5.52 Bars) form water cooling.
There are some exceptions when the
suction pressure is permitted to tem
-
porarily drop below the cutout point.
Details are explained under the topic
of SYSTEM SAFETIES.
d
D I S C H A R G E P R E S S U R E
C U T O U T = 5 7 0 P S I G
S U C T I O N P R E S S U R E
C U T O U T = 80 . 0 P S I G
The LOW AMBIENT TEMP CUTOUT allows the user
to select the chiller outside ambient temperature cutout
point. If the ambient falls below this point, the chiller
will shut down. Restart can occur when temperature rises
2 °F (1.11 °C) above the cutout setpoint.
The LEAVING LIQUID TEMP CUTOUT protects
the chiller from an evaporator freeze-up. Anytime the
leaving chilled liquid temperature drops to the cutout
point, the chiller shuts down. Restart will be permitted
when the leaving chilled liquid temperature rises 2 °F
(1.11 °C) above the cutout setpoint.
When water cooling mode is programmed (Options
key), the value is fixed at 36.0 °F (2.22 °C) and cannot
be changed. Glycol cooling mode can be programmed
to values listed in Table 11.
The programmable anti-recycle timer assures that
systems do not short cycle, and the compressor motors
have sufficient time to dissipate heat after a start.
This timer is programmable under the PROGRAM
key between 300 – 600 seconds. Whenever possible,
to reduce cycling and motor heating, the anti-recycle
timer should be adjusted as high as possible. The
programmable anti-recycle timer starts the timer when
the first compressor in a system starts. The timer begins
to count down. If all the compressors in the circuit
cycle off, a compressor within the circuit will not be
permitted to start until the anti-recycle timer has timed
out. If the lead system has run for less than 5 minutes,
3 times in a row, the anti-recycle timer will be extended
to 10 minutes, if currently programmed for less than 10
minutes.
The Fan Control On-Pressure is the programmed
pressure value that is used to stage the condenser fans
on, in relation to discharge pressure.
Refer to Condenser
Fan Control in the UNIT OPERATION section and
Tables 17and 18.
L O W A M B I E N T T E M P
C U T O U T = 2 5 . 0 ° F
L E A V I N G L I Q U I D T E M P
C U T O U T = 3 6 . 0 ° F
A N T I R E C Y C L E T I M E R
= 6 0 0 S E C
F A N C O N T R O L O N
P R E S S U R E = X X X P S I G
Содержание YORK Tempo YLAA Series
Страница 4: ...JOHNSON CONTROLS 4 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 12: ...JOHNSON CONTROLS 12 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 14: ...JOHNSON CONTROLS 14 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 18: ...JOHNSON CONTROLS 18 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 36: ...JOHNSON CONTROLS 36 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 49: ...FORM 150 72 NM1 1020 49 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 71: ...FORM 150 72 NM1 1020 71 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 73: ...FORM 150 72 NM1 1020 73 JOHNSON CONTROLS 5 5...
Страница 75: ...FORM 150 72 NM1 1020 75 JOHNSON CONTROLS 5 5...
Страница 77: ...FORM 150 72 NM1 1020 77 JOHNSON CONTROLS 5 5...
Страница 79: ...FORM 150 72 NM1 1020 79 JOHNSON CONTROLS 5 5...
Страница 81: ...FORM 150 72 NM1 1020 81 JOHNSON CONTROLS 5 5...
Страница 83: ...FORM 150 72 NM1 1020 83 JOHNSON CONTROLS 5 5...
Страница 85: ...FORM 150 72 NM1 1020 85 JOHNSON CONTROLS 5 5 LD13901...
Страница 87: ...FORM 150 72 NM1 1020 87 JOHNSON CONTROLS 5 5...
Страница 89: ...FORM 150 72 NM1 1020 89 JOHNSON CONTROLS 5 5 LD13232...
Страница 90: ...JOHNSON CONTROLS 90 FORM 150 72 NM1 1020 Technical Data DUAL PUMP WIRING LD13237 FIG 21 DUAL PUMP WIRING...
Страница 91: ...FORM 150 72 NM1 1020 91 JOHNSON CONTROLS THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 92: ...JOHNSON CONTROLS 92 FORM 150 72 NM1 1020 Technical Data WIRING LD13238 FIG 22 WIRING...
Страница 93: ...FORM 150 72 NM1 1020 93 JOHNSON CONTROLS 5 5 LD13239...
Страница 160: ...JOHNSON CONTROLS 160 FORM 150 72 NM1 1020 Unit Operation FIG 28 CONDENSER FAN LOCATIONSWIRING DIAGRAMS...
Страница 176: ...JOHNSON CONTROLS 176 FORM 150 72 NM1 1020 THIS PAGE INTENTIONALLY LEFT BLANK...
Страница 191: ...FORM 150 72 NM1 1020 191 JOHNSON CONTROLS 10 NOTES...