Model RFII - 5.6 K-factor Horizontal Sidewall

Flat Plate Concealed Sprinklers

Quick Response, Standard Coverage

Page 1 of 6 

JUNE 2020 

TFP185

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO Model RFII, 5.6 K-factor, 

Horizontal Sidewall (HSW), Flat Plate 

Concealed Sprinkler, Quick Response 

Standard Coverage is a decorative, link 

type sprinkler featuring a unique flat 

cover designed to conceal the sprin-

kler within a wall. The sprinkler is the 

best choice for architecturally sensi-

tive areas such as dormitories, hotel 

rooms, reception areas, office build-

ings, banquet facilities, conference 

rooms, and hospitals.
The flat profile of the cover plate design 

easily conforms to the surrounding sur-

faces leaving a very clean look. The 

plate, while being aesthetically appeal-

ing, also helps to prevent objects such 

as garment bags and clothes hangers 

from being hung from the sprinkler that 

may otherwise cause an inadvertent 

operation.
The Model RFII HSW Concealed Sprin-

kler is designed for installation along a 

wall or the side of a beam, and beneath 

a smooth level ceiling. Horizontal side-

wall sprinklers are commonly used in 

lieu of pendent or upright sprinklers 

because of aesthetics or building con-

struction considerations where piping 

across the ceiling is not desirable.
The Model RFII HSW Sprinklers are 

intended to be used in automatic 

sprinkler systems designed in accor-

dance with standard installation rules, 

for example, NFPA 13, for ordinary and 

light hazard occupancies. 
Cover Plate Assemblies are available in 

a variety of colors and ordered sepa-

rately. When properly installed, cover 

plates conceal operational parts of the 

sprinklers. Together, the sprinkler and 

cover plate form a complete assembly. 

The separable two-piece design of the 

sprinkler provides for 1/4 in. (6,4 mm) 

horizontal adjustment of the push-on 

and pull-off cover plate. With sprinklers 

installed but before cover plates are 

attached, pressure testing of the fire 

protection system may be performed 

prior to completing wall assemblies 

such as installation of gypsum board 

over stud framing, and surface finish-

ing such as painting or wallpapering.
The Model RFII HSW Concealed 

Sprinkler is factory assembled and 

shipped with a Protective Cap. The 

Protective Cap must remain in place 

to protect the sprinkler during instal-

lation, see Figure 4, and wall instal-

lation and finishing. The cap may be 

temporarily removed to verify proper 

orientation of the sprinkler deflector 

as necessary, but must be reinstalled 

and remain attached until the wall is fin-

ished. The cap features a convenient 

center marking tip. With the sprinkler 

installed and cap attached, see Figure 

3, align the wall covering material with 

the framing studs and gently press 

against the cap tip. The indentation 

left by this action marks the center for 

cutting a 2-5/8 in. (66,7 mm) diameter 

clearance hole for the sprinkler. After 

the wall installation and finishing are 

complete, the Protective Cap must be 

removed and the Cover Plate Assem-

bly installed. Removal of the Protective 

Cap is crucial to ensure proper perfor-

mance of the sprinkler.

NOTICE

The TYCO Model RFII HSW Concealed 

Sprinkler described herein must be 

installed and maintained in compliance 

with this document and with the appli-

cable standards of the NATIONAL FIRE 

PROTECTION ASSOCIATION (NFPA), 

in addition to the standards of any 

authorities having jurisdiction. Failure 

to do so may impair the performance 

of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Number

TY3521

Technical 

Data

Approvals

UL and C-UL Listed

Note:

 The listings apply only to the 

service conditions indicated in the 

Design Criteria section.

The TYCO Model RFII HSW Concealed 

Sprinkler is only listed and approved 

with the LFII/RFIII Concealed Cover 

Plates having a factory applied finish.
Sprinkler and Cover Plates are sepa-

rately ordered. See the Ordering Pro-

cedure section for more information.

Содержание tyco RFII

Страница 1: ... form a complete assembly The separable two piece design of the sprinkler provides for 1 4 in 6 4 mm horizontal adjustment of the push on and pull off cover plate With sprinklers installed but before cover plates are attached pressure testing of the fire protection system may be performed prior to completing wall assemblies such as installation of gypsum board over stud framing and surface finish ...

Страница 2: ...e UL Listed for Light and Ordinary Hazard Occupancies at a 4 to 12 in 100mm to 300mm top of deflector to ceiling distance 1 Body 6 Deflector Guide Pin 11 Plug 16 Retainer 2 1 2 in NPT 7 Frame 12 Lever 17 Retainer Friction Grip 3 Wrenching Notch 8 Button 13 Compression Screw 18 Cover Plate Solder Tab 4 Sprinkler Waterway 9 Sealing Assembly 14 Link 19 Cover Plate 5 Deflector 10 Bridge 15 Protective ...

Страница 3: ...rench contains an outer flat surface reference that correlates with the sprinkler deflec tor orientation The word UP on the installation wrench is to face towards the ceiling to ensure proper alignment as shown in Figure 4 NOTICE Do not remove the Protective Cap shown in Figure 1 until the Cover Plate Assembly is installed and or the fire protection sprinkler system is ready to be placed in servic...

Страница 4: ...f it becomes necessary to remove the Cover Plate it can be removed merely by gently pulling the Cover Plate Assembly away from the sprin kler body Note A Cover Plate Assembly not ade quately engaging the sprinkler body that is not securely attached indicates the sprinkler is positioned at a distance from the mounting surface greater than is described in Figure 3 A Cover Plate Assembly fully engage...

Страница 5: ...between the lip of the Cover Plate and the wall as shown in Figure 3 This air gap is necessary for proper oper ation of the sprinkler If the wall is to be repainted after the installation of the sprinkler care must be exercised to ensure that the new paint does not seal off any of the air gap Factory painted cover plates must not be repainted They should be replaced if necessary by factory painted...

Страница 6: ...rin kler Cover Plate Assembly tempera ture rating specify specify finish P N specify 139 F 59 C Ivory RAL1015 56 204 0 135 Beige RAL1001 56 204 2 135 Pure White RAL9010 56 204 3 135 Signal White RAL9003 56 204 4 135 Grey White RAL9002 56 204 5 135 Brown RAL8028 56 204 6 135 Black RAL9005 56 204 7 135 Brushed Brass 56 204 8 135 Brushed Chrome 56 204 9 135 Custom Paint 56 204 X 135 165 F 74 C Ivory ...