TFP442

Page 3 of 6

Maximum  

Coverage 

Area 

1

ft x ft 

(m x m)

Maximum 

Spacing

ft 

(m)

DRY PIPE SYSTEM 

Minimum Flow

 

and Residual Pressure 

2, 3

Ordinary Temp. Rating 

160°F (71°C)

Deflector to 

Ceiling

Installation 

Type

Minimum 

Spacing

ft 

(m)

Flow

GPM 

(LPM)

Pressure

psi 

(bar)

12 x 12

(3,7 x 3,7)

12

(3,7)

13 

(49,2) 

7.0 

(0,48)

Smooth 

Ceilings  

7/8 to 1-1/8 in.

Beamed 

Ceilings per 

NFPA 13D or 

13R, or 13.  

Installed in 

beam  

7/8 to 1-1/8 in. 

below bottom 

of beam

Concealed

8

(2,4)

14 x 14

(4,3 x 4,3)

14

(4,3)

14 

(53,0)

8.2 

(0,57)

16 x 16

(4,9 x 4,9)

16

(4,9)

15 

(56,8)

9.4 

(0,65)

18 x 18

(5,5 x 5,5)

18

(5,5)

18 

(68,1)

13.5 

(0,93)

20 x 20

(6,1 x 6,1)

20

(6,1)

21 

(79,5)

18.4 

(1,27)

Notes:

1.  For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage 

area for which hydraulic design criteria are stated.

2.  Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated us-

ing the nominal K-factor. See Hydraulic Design under the Design Criteria section.

3.  For NFPA 13 residential applications, the greater of 0.1 GPM/ft

2

 over the design area or the flow in accordance with the criteria in 

this table must be used.

Maximum 

Coverage 

Area 

1

ft x ft  

(m x m)

Maximum 

Spacing

ft  

(m)

WET PIPE SYSTEM 

Minimum Flow and Residual Pressure

 2, 3

Temp. Rating 

160°F (71°C), 212

°

F (100

°

C)

Deflector to 

Ceiling

Installation 

Type

Minimum 

Spacing

ft  

(m)

Flow

GPM 

(LPM)

Pressure

psi  

(bar)

12 x 12  

(3,7 x 3,7)

12  

(3,7)

13 

(49,2) 

7.0 

(0,48)

Smooth 

Ceilings  

7/8 to 1-1/8 in.

Beamed 

Ceilings per 

NFPA 13D or 

13R, or 13.  

Installed in 

beam  

7/8 to 1-1/8 in. 

below bottom 

of beam

Concealed

8

(2,4)

14 x 14  

(4,3 x 4,3)

14  

(4,3)

13 

(49,2) 

7.0 

(0,48)

16 x 16  

(4,9 x 4,9)

16  

(4,9)

13 

(49,2)

7.0 

(0,48)

18 x 18  

(5,5 x 5,5)

18  

(5,5)

17 

(64,3)

12.0 

(0,83)

20 x 20 

(6,1 x 6,1)

20  

(6,1)

20 

(75,7)

16.7 

(1,15)

Notes:

1.  For coverage area dimensions less than or between those indicated, use the minimum required flow for the next highest coverage 

area for which hydraulic design criteria are stated.

2.  Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated  

using the nominal K-factor. See Hydraulic Design under the Design Criteria section.

3.  For NFPA 13 residential applications, the greater of 0.1 GPM/ft

2

 over the design area or the flow in accordance with the criteria in 

this table must be used.

TABLE A 

WET PIPE SYSTEM 

SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT PLATE CONCEALED PENDENT SPRINKLER (TY3596) 

NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA

TABLE B  

DRY PIPE SYSTEM 

 RAPID RESPONSE SERIES LFII RESIDENTIAL 4.9 K-FACTOR FLAT PLATE CONCEALED PENDENT (TY3596) 

NFPA 13D, 13R, AND 13 HYDRAULIC DESIGN CRITERIA