TFP442

Page 5 of 6

for installing the Cover Plate Assembly, 

remove and discard the Protective Cap, 

and verify that the Deflector moves up 

and down freely.
If the sprinkler has been damaged and 

the Deflector does not move up and 

down freely, replace the entire sprinkler 

assembly. Do not attempt to modify or 

repair a damaged sprinkler.

Step 6.

 Push on the Cover Plate 

Assembly until its flange comes in 

contact with the ceiling.
Do not continue to push on the Cover 

Plate Assembly such that it lifts a 

ceiling panel out of its normal position.
If the Cover Plate Assembly cannot 

be engaged with the Mounting Cup 

or the Cover Plate Assembly cannot 

be engaged sufficiently to contact the 

ceiling, the Sprinkler Fitting must be 

repositioned.

Care and 

Maintenance

The TYCO RAPID RESPONSE

 

Series LFII Residential Concealed 

Pendent Sprinklers (TY3596) must be 

maintained and serviced in accordance 

with this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

which it controls, permission to shut 

down the affected fire protection 

system must be obtained from the 

proper authorities and all personnel 

who may be affected by this action 

must be notified.
Absence of a Cover Plate may delay the 

sprinkler operation in a fire situation.
When properly installed, there is an air 

gap between the lip of the Cover Plate 

and the ceiling. The Ordinary Tem-

perature Cover Plate assembly has a 

nominal 1/8 in. (3,2 mm) air gap. The 

Intermediate Temperature Cover Plate 

has a nominal 3/32 (2,4 mm) air gap,  

as shown in Figure 2. This air gap is 

necessary for proper operation of the 

sprinkler by allowing heat flow from a 

fire to pass below and above the Cover 

Plate to help assure appropriate release 

of the Cover Plate in a fire situation. If 

the ceiling is to be repainted after the 

installation of the Sprinkler, care must 

be exercised to ensure that the new 

paint does not seal off any of the air 

gap.

Factory painted Cover Plates must not 

be repainted. They should be re placed, 

if necessary, by factory painted 

units.  Non-factory applied paint may 

adversely delay or prevent sprinkler 

operation in the event of a fire.
Do not pull the Cover Plate relative to 

the Enclosure. Separation may result.
Sprinklers which are found to be 

leaking or exhibiting visible signs of 

corrosion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or otherwise 

altered after leaving the factory. Modi-

fied or over heated sprinklers must be 

replaced.
Care must be exercised to avoid 

damage before, during, and after instal-

lation. Sprinklers damaged by drop-

ping, striking, wrench twist/slippage, 

or the like, must be replaced.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION, for example, NFPA 25, 

in addition to the standards of any other 

authorities having jurisdiction. Contact 

the installing contractor or product 

manufacturer with any questions.
The owner must assure that the sprin-

klers are not used for hanging any 

objects and that the sprinklers are only 

cleaned by means of gently dusting 

with a feather duster; otherwise, non-

operation in the event of a fire or inad-

vertent operation may result.
Automatic sprinkler systems should be 

inspected, tested, and maintained by a 

qualified Inspection Service in accor-

dance with local requirements and/or 

national codes.

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product name and part number 

(P/N).

Sprinkler Assemblies

Specify: Series LFII (TY3596) 4.9K Res-

idential Concealed Pendent Sprinkler,  

P/N (specify):

160

°

F (71

°

C) . . . . . . . . . . . . . . . . . . .51-112-1-160 

212

°

F (100

°

C) . . . . . . . . . . . . . . . . . .51-112-1-212

Note: Sprinkler and Cover Plates are 

separately sold. See below for Cover 

Plate ordering information.

Cover Plate Assemblies

Specify: LFII Concealed Sprinkler 

Cover Plate Assembly, temperature 

rating (specify), (specify) finish, P/N 

(specify):

139

°

F (59

°

C)

Ivory (RAL1015)  . . . . . . . . . . . . . . .56-204-0-135

Bright Chrome  . . . . . . . . . . . . . . . . 56-204-1-135

Beige (RAL1001)  . . . . . . . . . . . . . . 56-204-2-135

Pure White (RAL9010)*  . . . . . . . . . 56-204-3-135

Signal White (RAL9003)**  . . . . . . . 56-204-4-135

Grey White (RAL9002) . . . . . . . . . . 56-204-5-135

Brown (RAL8028). . . . . . . . . . . . . .56-204-6-135

Black (RAL9005)  . . . . . . . . . . . . . . 56-204-7-135

Brushed Brass . . . . . . . . . . . . . . . . 56-204-8-135

Brushed Chrome  . . . . . . . . . . . . . . 56-204-9-135

Custom Paint . . . . . . . . . . . . . . . . . 56-204-X-135

165

°

F (74

°

C)

Ivory (RAL1015)  . . . . . . . . . . . . . . .56-204-0-165

Bright Chrome  . . . . . . . . . . . . . . . . 56-204-1 165

Beige (RAL1001)  . . . . . . . . . . . . . . 56-204-2-165

Pure White (RAL9010)*  . . . . . . . . . 56-204-3-165

Signal White (RAL9003)**  . . . . . . .56-204-4-165

Grey White (RAL9002) . . . . . . . . . .56-204-5-165

Brown (RAL8028). . . . . . . . . . . . . .56-204-6-165

Black (RAL9005)  . . . . . . . . . . . . . . 56-204-7-165

Brushed Brass . . . . . . . . . . . . . . . .56-204-8-165

Brushed Chrome  . . . . . . . . . . . . . .56-204-9-165

Custom Paint . . . . . . . . . . . . . . . . . 56-204-X-165

*Eastern Hemisphere sales only 
**Previously known as Bright White

Note:  All Custom Cover Plates are 

painted using SHERWIN-WILLIAMS 

Interior Latex Paint. Contact Johnson 

Controls Customer Service with any 

questions related to custom orders.

Sprinkler Wrench

Specify: W-Type 18 Sprinkler Wrench, 

P/N 56-000-1-265

Отзывы: