background image

TFP442

Page 2 of 6

Technical 

Data

Approvals

UL and C-UL Listed 

NYC Approved under MEA 44-03-E-2NSF 

Certified to all requirements of 

NSF/ANSI 61

The TYCO RAPID RESPONSE Series LFII 

Residential Concealed Pendent Sprinklers 

are Listed only when installed with LFII Con-

cealed Cover Plates having factory-applied 

finishes.
Sprinklers and Cover Plates are separately 

ordered. See the Ordering Procedure 

section for more information.

Maximum Working Pressure

175 psi (12,1 bar)

Discharge Coefficient

K=4.9 GPM/psi

½

 (70,6 LPM/bar

½

)

Temperature Rating

Ordinary

160°F (71°C) Sprinkler/ 

139°F (59°C) Cover Plate

NOTE: 

Maximum Ambient Ceiling Temperature for the 

ordinary temperature configuration is 100°F (38°C)

Intermediate

*

212

°

F (100

°

C) Sprinkler/ 

165

°

F (74

°

C) Cover Plate

*For wet pipe systems only 

NOTE: 

Maximum Ambient Ceiling Temperature for the 

intermediate temperature configuration is 150°F (65°C)

Vertical Adjustment

1/2 in. (12,7 mm)

Finishes

See the Ordering Procedure section

Physical Characteristics

Body  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Cap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Saddle . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Sealing Assembly  . .Beryllium Nickel w/TEFLON

Soldered Link Halves . . . . . . . . . . . . . . . .  Nickel

Lever . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Compression Screw . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . Copper or Brass

Guide Pin Housing  . . . . . . . . . . . . . . . . . .Bronze

Guide Pins   . . . . . . . . . Stainless Steel or Bronze

Support Cup   . . . . . . . . . . . . . . . . . . . . . . .  Steel

Cover Plate  . . . . . . . . . . . . . . . . .Copper/Brass**

Retainer  . . . . . . . . . . . . . . . . . . . . . . . . .  Copper

Cover Plate Ejection Spring  . . . . Stainless Steel

** Brass Cover Plate is offered for Intermediate Tem-
perature 165°F (74°C) only.

Operation

When exposed to heat from a fire, the 

Cover Plate, which is normally soldered 

to the Retainer at three points, falls 

away to expose the sprinkler assembly. 

At this point the Deflector supported by 

the Arms drops down to its operated 

position. The fusible link of the sprin-

kler assembly is comprised of two link 

halves that are soldered together with 

a thin layer of solder. When the rated 

temperature is reached, the solder 

melts and the two link-halves separate 

allowing the sprinkler to activate and 

flow water.

Design Criteria

The TYCO RAPID RESPONSE Series 

LFII Residential Concealed Pendent 

Sprinklers (TY3596) are UL and C-UL 

Listed for installation in accordance 

with this section.

Note: When conditions exist that are 

outside the scope of the provided cri-

teria, refer to the Residential Sprinkler 

Design Guide TFP490 for the manu-

facturer's recommendations that may 

be acceptable to the authority having 

jurisdiction.

System Types

Per the UL and C-UL Listing, the 

160

°

F (71

°

C) and 212

°

F (100

°

C) LFII 

Residential Concealed Pendent Sprin-

klers may be utilized in wet pipe 

systems. Only the 160

°

F (71

°

C) LFII Res-

idential Concealed Pendent Sprinklers 

may be utilized in dry pipe systems, per 

the UL and C-UL Listing.

Refer to Technical Data Sheet TFP485 

about the use of residential sprinklers 

in residential dry pipe systems.

Ceiling Types

Smooth flat horizontal, beamed, or 

sloped in accordance with NFPA 13D, 

13R, or 13 as applicable.

Hydraulic Design 

(NFPA 13D and 13R)

For systems designed to NFPA 13D or 

NFPA 13R, the minimum re quired sprin-

kler flow rates are given in Tables A and 

B as a function of temperature rating 

and the maximum allowable coverage 

areas.
The sprinkler flow rate is the minimum 

required discharge from each of the 

total number of “design sprinklers” as 

specified in NFPA 13D or NFPA 13R. 

The number of “design sprinklers” 

specified in NFPA 13D and 13R for wet 

pipe systems is to be applied when 

designing dry pipe systems.

SPRINKLER

ASSEMBLY

COVER PLATE

ASSEMBLY

COVER

PLATE

EJECTION

SPRING

RETAINER

WITH THREAD

DIMPLES

SEALING

ASSEMBLY

COMPRESSION

SCREW

DEFLECTOR

(OPERATED

POSITION)

SPRINKLER

WRENCHING

AREA

SOLDER LINK

ELEMENT

LEVER

SOLDER

TAB

DEFLECTOR

CAP

BODY

(1/2" NPT)

SADDLE

SUPPORT

CUP WITH

ROLL FORMED

THREADS

GUIDE

PIN

GUIDE PIN

HOUSING

THREAD INTO

SUPPORT

CUP UNTIL

MOUNTING

SURFACE IS

FLUSH WITH

CEILING

FIGURE 1 

RAPID RESPONSE SERIES LFII RESIDENTIAL 

CONCEALED PENDENT SPRINKLER (TY3596)