RAPID RESPONSE Series LFII Residential Sprinklers 

3.0 K-factor Pendent 

Wet Pipe Systems

Page 1 of 4 

DECEMBER 2018 

TFP402

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

The owner is responsible for maintain-

ing their fire protection system and 

devices in proper operating condition. 

The installing contractor or sprinkler 

manufacturer should be contacted with 

any questions.

Sprinkler  

Identification 

Number (SIN)

TY1234

General 

Description

The TYCO RAPID RESPONSE Series 

LFII Residential Pendent Sprinklers 

(TY1234) are decorative, fast response, 

frangible bulb sprinklers designed for 

use in residential occupancies such as 

homes, apartments, dormitories, and 

hotels. When aesthetics and optimized 

flow characteristics are key consider-

ations, the Series LFII (TY1234) should 

be the first choice.
The 3.0 K-factor of the Series LFII Res-

idential Pendent Sprinkler has been 

designed to optimize flows (that is, to 

avoid over discharging) specifically 

for small coverage areas up to 14 ft x  

14 ft (4,3 m x 4,3 m). The required resi-

dential flow rates can then be delivered 

with the use of smaller pipe sizes and 

reduced water supply requirements.
The Series LFII Residential Sprinklers 

are intended for use in the following 

scenarios:

•  wet pipe residential sprinkler 

systems for one-and two-family 

dwellings and mobile homes per 

NFPA 13D

•  wet pipe residential sprinkler 

systems for residential occupan-

cies up to and including four stories 

in height per NFPA 13R

•  wet pipe sprinkler systems for 

the residential portions of any 

occupancy per NFPA 13

The recessed version of the Series 

LFII Residential Pendent Sprinkler is 

intended for use in areas with finished 

ceilings. It employs a two-piece Style 

20 Recessed Escutcheon.
The Recessed Escutcheon provides 

1/4 in. (6,4 mm) of recessed adjust-

ment or up to 1/2 in. (12,7 mm) of total 

adjustment from the flush ceiling posi-

tion. The adjustment provided by the 

Recessed Escutcheon reduces the 

accuracy to which the pipe drops to 

the sprinklers must be cut.
The Series LFII Residential Pendent 

Sprinkler has been designed with heat 

sensitivity and water distribution char-

acteristics proven to help in the control 

of residential fires and to improve the 

chance for occupants to escape or be 

evacuated.
Corrosion-resistant coatings, where 

applicable, are utilized to extend the life 

of copper alloy sprinklers beyond that 

which would otherwise be obtained 

when exposed to corrosive atmo-

spheres. Although corrosion-resistant 

coated sprinklers have passed the 

standard corrosion tests of the appli-

cable Approval agencies, the testing is 

not representative of all possible cor-

rosive atmospheres. Consequently, 

it is recommended that the end user 

be consulted with respect to the suit-

ability of these coatings for any given 

corrosive environment. The effects of 

ambient temperature, concentration of 

chemicals, and gas/chemical velocity 

should be considered, as a minimum, 

along with the corrosive nature of the 

chemical to which the sprinklers will be 

exposed.

NOTICE

The Series LFII Residential Pendent 

Sprinklers (TY1234) described herein 

must be installed and maintained in 

compliance with this document and 

with the applicable standards of the 

NATIONAL FIRE PROTECTION ASSO-

CIATION (NFPA), in addition to the 

standards of any authorities having 

jurisdiction. Failure to do so may impair 

the performance of these devices.