TFP402

Page 4 of 4

1400 Pennbrook Parkway, Lansdale, PA 19446 | Tel1-215-362-0700

© 2019 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association; 

LOCTITE is a registered trademark of Henkel Corporation; 

TEFLON is a registered trademark of DuPont

Limited 

Warranty

For warranty terms and conditions, visit 

www.tyco-fire.com.

Ordering 

Procedure

Contact your local distributor for avail-

ability. When placing an order, indicate 

the full product name and Part Number 

(P/N).

Sprinkler Assembly

Specify: Series LFII (TY1234), K=3.0, 

Residen tial Pendent Sprinkler, (specify) 

temperature rating, (specify) finish, and 

P/N (specify):

155°F (68°C)

Natural Brass . . . . . . . . . . . . . . . . . 51-010-1-155

Signal White (RAL 9003)

Polyester

1

. . . . . . . . . . . . . . . . . . . . 51-010-4-155

Chrome Plated . . . . . . . . . . . . . . . . 51-010-9-155

175°F (79°C)

Natural Brass . . . . . . . . . . . . . . . . . 51-010-1-175

Signal White (RAL 9003)

Polyester

1

. . . . . . . . . . . . . . . . . . . . 51-010-4-175

Chrome Plated . . . . . . . . . . . . . . . . 51-010-9-175

1.  UL Listed as corrosion-resistant.

Recessed Escutcheon

Specify: Style 20 Recessed Escutch-

eon with (specify*) finish, and P/N 

(specify*)

*Refer to Technical Data Sheet TFP770.

Sprinkler Wrench

Specify: W-Type 6 Sprinkler Wrench 

for use with Series LFII Pendent Sprin-

klers, P/N 56-000-6-387
Specify: W-Type 7 Sprinkler Wrench for 

use with Series LFII Recessed Pendent 

Sprinklers, P/N 56-850-4-001

Series LFII Residential Pendent 

Sprinklers

The Series LFII Residential Pendent 

Sprinklers must be installed in accor-

dance with the following instructions.

Step 1.

 Install pendent sprinklers in the 

pendent position with the deflector par-

allel to the ceiling.

Step 2.

 With pipe-thread sealant 

applied to the pipe threads, hand-

tighten the sprinkler into the sprinkler 

fitting.

Step 3.

 Wrench-tighten the sprinkler 

into the sprinkler fitting using only the 

W-Type 6 Sprinkler Wrench (Figure 

3). With reference to Figure 1, apply 

the W-Type 6 Sprinkler Wrench to the 

wrench flats.

Series LFII Residential Recessed 

Pendent Sprinklers

The Series LFII Recessed Pendent

 

Sprinklers must be installed in accor-

dance with the following instructions.

Step A.

 Install recessed pendent sprin-

klers in the pendent position with the 

deflector parallel to the ceiling.

Step B.

 After installing the Style 20 

Mounting Plate over the sprinkler 

threads and with pipe thread sealant 

applied to the pipe threads, hand-

tighten the sprinkler into the sprinkler 

fitting.

Step C.

 Wrench-tighten the sprinkler 

into the sprinkler fitting using only the 

W-Type 7 Recessed Sprinkler Wrench 

(Figure 4). With reference to Figure 1, 

apply the W-Type 7 Recessed Sprinkler 

Wrench to the sprinkler wrench flats.

Step D.

 After installing the ceiling 

applying the finish coat, slide on the 

Style 20 Closure over the Series LFII 

Sprinkler and push the Closure over the 

Mounting Plate until the flange comes 

in contact with the ceiling.

Care and 

Maintenance

The TYCO RAPID RESPONSE Series 

LFII Residential Pendent Sprinklers 

(TY1234) must be maintained and ser-

viced in accordance with this section:
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

system from the proper authorities 

and notify all personnel who may be 

affected by this decision.
Absence of the outer piece of an 

escutcheon,which is used to cover 

a clearance hole, can delay sprinkler 

operation in a fire situation.
The owner must assure that the sprin-

klers are not used for hanging any 

objects and that the sprinklers are only 

cleaned by means of gently dusting 

with a feather-duster. Otherwise, non-

operation in the event of a fire or inad-

vertent operation may result.
Sprinklers which are found to be 

leaking or exhibiting visible signs of 

corrosion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers - before, 

during, and after installation. Sprin-

klers damaged by dropping, striking, 

wrench twist/slippage, or the like, must 

be replaced. Also, replace any sprinkler 

that has a cracked bulb or that has lost 

liquid from its bulb. See the Installation 

section for additional information.
The owner is responsible for the 

inspection, testing, and maintenance of 

their fire protection system and devices 

in compliance with this document, as 

well as with the applicable standards 

of the NATIONAL FIRE PROTECTION 

ASSOCIATION, for example, NFPA 25, 

in addition to the standards of any other 

authorities having jurisdiction. Contact 

the installing contractor or sprinkler 

manufacturer regarding any questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.