TFP621

Page 3 of 8

Operation

When exposed to heat from a fire, 

upon reaching the Cover Plate/Retainer 

Assembly temperature rating, the 

solder binding the Cover Plate to three 

tabs of the Retainer melts, allowing 

the Cover Plate to separate from the 

Retainer and exposing the Sprinkler/

Support Cup Assembly. The Deflector, 

supported by the Guide Pins, deploys 

downward into the Operated Position.
As the temperature from the fire 

reaches the Sprinkler temperature 

rating, the solder binding the halves of 

the Solder Link Element melts, allow-

ing the element to separate. With this 

linkage no longer holding the Sealing 

Assembly against the sprinkler orifice, 

water is allowed to flow through the 

waterway, spraying from the deflector 

in a pattern toward the window glazing.

Design Criteria

The TYCO Model CWS Specific Appli-

cation Concealed Pendent Vertical 

Sidewall Window Sprinkler is UL and 

C-UL Listed.
This sprinkler is also Listed by Under-

writers Laboratories of Canada (ULC) 

as providing a two-hour equivalency 

for a fire separation assembly when 

acceptable to the Authority Having 

Jurisdiction and installed in accor-

dance with this code.

Area of Use

When acceptable to the authority 

having jurisdiction, and unless modi-

fied by a local jurisdictional standard 

or code mentioned previously, the 

Model CWS Window Sprinkler may be 

used in either a sprinklered or unsprin-

klered building to protect non-operable 

window openings that are part of a fire 

separation provided:
•  in an interior fire separation, the win-

dow sprinklers are installed on both 

sides of the window in the fire sepa-

ration (Figure 4A-1),

•  in jurisdictions where exterior spatial 

separation (that is, separation from 

adjacent space) is defined as pro-

tecting an adjacent building from a 

fire in your building, window sprin-

klers are installed on the interior side 

of the building (Figure 4A-2).

System Protection Type

Interior: Wet Systems

Glass Type

The following types and thicknesses of 

glass are recognized for use with the 

Model CWS Window Sprinkler:
•  Non-operable, heat-strengthened, 

tempered, single-glazed (single 

pane), not less than 1/4 in. (6 mm) 

thick;

•  Non-operable, heat-strengthened, 

tempered, double-glazed (double 

pane or insulated), not less than 

1/4 in. (6 mm) thick;

•  Non-operable, UL Classified and 

labeled FIRELITE PLUS CWS 

ceramic glass by TECHNICAL 

GLASS PRODUCTS (TGP), not less 

than 5/16 in. (8 mm) thick; or,

Note:

 Refer to FIRELITE PLUS CWS ceramic 

glass technical data sheet for other classi-

fication limitations at www.fireglass.com.

•  Non-operable, stronger glass win-

dow assemblies, not less than ¼ in. 

(6 mm) thick.

Type of Window Frame/Mullion

Non-combustible Frame with a stan-

dard EPDM rubber gasket seal
Vertical joints of glass panes must be 

connected by butt-joints using a sili-

cone sealant between the individual 

panes or by Noncombustible Mullions.
(See Figures 4B-1 and 4B-2)

Maximum Length of 

Window Assembly

Unlimited

Maximum Height of 

Window Assembly

13 ft (3,96 m)
(See Figure 4B)

Maximum Distance Between 

Window Sprinklers

8 ft (2,44 m)
(See Figures 4B-1 and 4B-2)

Minimum Distance Between 

Window Sprinklers

6 ft (1,83 m) unless separated by a 

baffle or mullion of sufficient depth to 

act as a baffle.
A mullion will act as a baffle when the 

mullion extends to the back of the 

sprinkler deflector.
(See Figures 4B-1 and 4B-2)

Minimum Distance from 

Standard Sprinklers

6 ft (1,83 m) unless separated by a 

baffle 

Sprinkler Location

•  Mullioned Glazing Assemblies: 

Locate window sprinklers within 

each mullioned glazing segment. 

See Figure 4B-1.

•  Butt-Jointed Glazing Assem-

blies: Locate window sprinklers 

on maximum 8 ft (2,44 m) centers. 

See Figure 4B-2.

Maximum Distance from 

Vertical Mullion

4 ft (1,22 m)
(See Figure 4B-1)

ACCEPTS 1/2" DRIVE

OR 7/8" OPEN-END

WRENCH

SUPPORT

CUP

SPRINKLER

WRENCHING

HEX

WRENCH HEX

RECESS

SPRAY

DEFLECTOR

ARROW INDICATES

SPRINKLER SPRAY

DIRECTION TOWARD

WINDOW GLAZING

WRENCH FULLY

ENGAGED ON

SPRINKLER

FIGURE 3 

W-TYPE 39 

SPRINKLER WRENCH

Содержание tyco CWS

Страница 1: ...Model CWS Window Sprinkler can be used as interior protection for windows or glazing in a sprinklered building or non sprinklered building in accordance with Section 104 of the IBC Alternate Material...

Страница 2: ...ORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING LEVER SADDLE CAP DEFLECTOR 3 3 16 DIA 81 0 mm 2 1 2 DIA 63 5 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING DEFLECTOR IN OPERATED POSITION DISPOSABL...

Страница 3: ...stem Protection Type Interior Wet Systems Glass Type The following types and thicknesses of glass are recognized for use with the Model CWS Window Sprinkler Non operable heat strengthened tempered sin...

Страница 4: ...ilized the linear length of the calculated window sprinklers may be reduced but in no case shall be less than 36 linear feet 1 2 x 900 If a single fire can be expected to operate Model CWS Window Spri...

Страница 5: ...listed to protect windows when intermediate horizontal mullions are present 4 0 1 22 m MAXIMUM 0 4 101 6 mm MINIMUM 8 0 2 44 m MAXIMUM MODEL CWS CONCEALED SPRINKLER 6 0 1 83 m MINIMUM MULLION Minimum...

Страница 6: ...E THROUGH USE OF 3 0 0 9 m MINIMUM PONY WALL INSTALLATION NOTE MODEL CWS SPRINKLER SHOWN ON ONE SIDE OF GLAZING FOR CLARITY FOR GLASS TYPES OTHER THAN FIRELITE PLUS CWS CERAMIC GLASS BY TGP ALL COMBUS...

Страница 7: ...nnot be engaged sufficiently to contact the ceiling the Sprinkler Fitting must be repositioned Care and Maintenance The TYCO Model CWS Specific Appli cation Window Sprinkler must be main tained and se...

Страница 8: ...temperature rating and P N specify 160 F 71 C 50 630 0 160 212 F 100 C 50 630 0 212 Note Sprinkler and Cover Plates are sepa rately sold See Cover Plate Assemblies subsection for ordering information...

Отзывы: