TFP621

Page 6 of 8

INSTALLATION

NOTE:

BUILDING

STRUCTURE

NON-OPERABLE

GLASS WINDOW

ORIENT SPRINKLER

WITH GUIDE PINS

ALIGNED PARALLEL

TO GLAZING AND

DEFLECTOR SPRAY

ARROW POINTED

TOWARD GLAZING

NO

MAXIMUM

HEIGHT

6" to 12"

(152 to

305 mm)

CENTERLINE

OF SPRINKLER

WATERWAY

13'-0"

(3,96 m)

MAXIMUM

EXPOSED

GLAZING

HEIGHT

SPRAY

FLUSH

OR EXPOSED

WINDOW

FRAME

2"±2"

(50,8 mm

±50,8 mm)

MODEL CWS

SPRINKLER

SHOWN ON ONE

SIDE OF GLAZING

FOR CLARITY

FOR GLASS

TYPES OTHER

THAN FIRELITE

PLUS CWS

CERAMIC GLASS

BY TGP, ALL

COMBUSTIBLE

MATERIALS

SHALL BE KEPT

2" (50,8 mm)

MINIMUM FROM

SPRINKLERED

FACE OF

GLAZING. THIS

MAY BE DONE

THROUGH USE

OF 3'-0" (0,9 m)

MINIMUM

PONY WALL

INSTALLATION

NOTE:

MODEL CWS

SPRINKLER

SHOWN ON ONE

SIDE OF GLAZING

FOR CLARITY

FOR GLASS

TYPES OTHER

THAN FIRELITE

PLUS CWS

CERAMIC GLASS

BY TGP, ALL

COMBUSTIBLE

MATERIALS

SHALL BE KEPT

2" (50,8 mm)

MINIMUM FROM

SPRINKLERED

FACE OF

GLAZING. THIS

MAY BE DONE

THROUGH USE

OF 3'-0" (0,9 m)

MINIMUM

PONY WALL

BUILDING

STRUCTURE

TYPICAL

WINDOW

COVERING

NON-OPERABLE

GLASS WINDOW

INSTALL MODEL

CWS SPRINKLERS

INTO RECESSED

CEILING SPACES.

DO NOT PLACE

BLINDS, CURTAINS

OR OTHER WINDOW

COVERINGS

BETWEEN

SPRINKLER

AND GLAZING

FLUSH

OR EXPOSED

WINDOW

FRAME

SPRAY

FIGURE 4C 

MODEL CWS CONCEALED PENDENT 

VERTICAL SIDEWALL WINDOW SPRINKLER 

TYPICAL INSTALLATION

FIGURE 4D 

MODEL CWS CONCEALED PENDENT 

VERTICAL SIDEWALL WINDOW SPRINKLER 

TYPICAL INSTALLATION WITH WINDOW COVERING

Содержание tyco CWS

Страница 1: ...Model CWS Window Sprinkler can be used as interior protection for windows or glazing in a sprinklered building or non sprinklered building in accordance with Section 104 of the IBC Alternate Material...

Страница 2: ...ORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING LEVER SADDLE CAP DEFLECTOR 3 3 16 DIA 81 0 mm 2 1 2 DIA 63 5 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING DEFLECTOR IN OPERATED POSITION DISPOSABL...

Страница 3: ...stem Protection Type Interior Wet Systems Glass Type The following types and thicknesses of glass are recognized for use with the Model CWS Window Sprinkler Non operable heat strengthened tempered sin...

Страница 4: ...ilized the linear length of the calculated window sprinklers may be reduced but in no case shall be less than 36 linear feet 1 2 x 900 If a single fire can be expected to operate Model CWS Window Spri...

Страница 5: ...listed to protect windows when intermediate horizontal mullions are present 4 0 1 22 m MAXIMUM 0 4 101 6 mm MINIMUM 8 0 2 44 m MAXIMUM MODEL CWS CONCEALED SPRINKLER 6 0 1 83 m MINIMUM MULLION Minimum...

Страница 6: ...E THROUGH USE OF 3 0 0 9 m MINIMUM PONY WALL INSTALLATION NOTE MODEL CWS SPRINKLER SHOWN ON ONE SIDE OF GLAZING FOR CLARITY FOR GLASS TYPES OTHER THAN FIRELITE PLUS CWS CERAMIC GLASS BY TGP ALL COMBUS...

Страница 7: ...nnot be engaged sufficiently to contact the ceiling the Sprinkler Fitting must be repositioned Care and Maintenance The TYCO Model CWS Specific Appli cation Window Sprinkler must be main tained and se...

Страница 8: ...temperature rating and P N specify 160 F 71 C 50 630 0 160 212 F 100 C 50 630 0 212 Note Sprinkler and Cover Plates are sepa rately sold See Cover Plate Assemblies subsection for ordering information...

Отзывы: