TFP621

Page 7 of 8

Installation

The TYCO Model CWS Specific 

Application Window Sprinkler must 

be installed in accordance with this 

section.

General Instructions

A leak-tight 1/2 in. NPT sprinkler joint 

should be obtained by applying a min-

imum-to-maximum  torque of 7 to 14 

lb-ft (9,5 to 19,0 N∙m). Higher levels of 

torque may distort the sprinkler inlet 

with consequent leakage or impairment 

of the sprinkler.
Do not attempt to compensate for 

insufficient adjustment in the Sprinkler 

by under- or over-tightening the Sprin-

kler/Support Cup Assembly. Re-adjust 

the position of the sprinkler fitting to 

suit.

Step 1.

 Install the Model CWS Window 

Sprinkler only in the pendent position 

with the center-line of the sprinkler 

parallel to the glass surface. Orient the 

sprinkler so that the direction of flow 

indicated on the sprinkler deflector is 

facing the window.

Step 2.

 Remove the Protective Cap.

Step 3.

 With pipe thread sealant 

applied to the pipe threads, and using 

the W-Type 39 Wrench, as shown in 

Figure 3, install and tighten the Sprin-

kler/Support Cup Assembly into the 

fitting. The W-Type 39 Wrench will 

accept a 1/2 in. ratchet drive.

Step 4.

 Replace the Protective Cap by 

pushing it upwards until it bottoms 

out against the Support Cup 

(see Figure 2). The Protective Cap 

helps prevent damage to the Deflector 

and Guide Pin Housing during ceiling 

installation and/or finish. You can also 

use the Protective Cap to locate the 

center of the clearance hole by gently 

pushing the ceiling material up against 

the center point of the Protective Cap.

NOTICE

As long as the Protective Cap remains 

in place, the system is considered “Out 

of Service”.

Step 5.

 After the ceiling has been 

completed with the 2 1/2 in. (63,5 mm) 

diameter clearance hole and in prep-

aration for installing the Cover Plate/

Retainer Assembly, remove and 

discard the Protective Cap. Verify that 

the Deflector moves up and down 

freely. If the Sprinkler is damaged and 

the Deflector does not move up and 

down freely, replace the entire Sprin-

kler. Do not attempt to modify or repair 

a damaged sprinkler.

Step 6.

 Push on the Cover Plate 

Assembly until its flange comes in 

contact with the ceiling.
Do not continue to push on the Cover 

Plate Assembly such that it lifts a 

ceiling panel out of its normal position.
If the Cover Plate Assembly cannot 

be engaged with the Mounting Cup 

or the Cover Plate Assembly cannot 

be engaged sufficiently to contact the 

ceiling, the Sprinkler Fitting must be 

repositioned.

Care and 

Maintenance

The TYCO Model CWS Specific Appli-

cation Window Sprinkler must be main-

tained and serviced in accordance with 

this section.
Before closing a fire protection system 

main control valve for maintenance 

work on the fire protection system 

that it controls, obtain permission to 

shut down the affected fire protection 

systems from the proper authorities 

and notify all personnel who may be 

affected by this action.
Absence of the Cover Plate Assem-

bly may delay sprinkler operation in a 

fire situation. When properly installed, 

there is a nominal 3/32 in. (2,4 mm) air 

gap between the lip of the Cover Plate 

and the ceiling, as shown in Figure 2. 

This air gap is necessary for proper 

operation of the sprinkler. If the ceiling 

is to be repainted after the installation 

of the Sprinkler, care must be exercised 

to ensure that the new paint does not 

seal off any of the air gap.

Factory painted Cover Plates must not 

be repainted. They should be replaced, 

if necessary, by factory painted 

units. Non-factory applied paint may 

adversely delay or prevent sprinkler 

operation in the event of a fire.
Do not pull the Cover Plate relative to 

the Enclosure. Separation may result.
Sprinklers which are found to be 

leaking or exhibiting visible signs of 

corrosion must be replaced.
Automatic sprinklers must never be 

painted, plated, coated, or other-

wise altered after leaving the factory. 

Modified sprinklers must be replaced. 

Sprinklers that have been exposed to 

corrosive products of combustion, but 

have not operated, should be replaced 

if they cannot be completely cleaned 

by wiping the sprinkler with a cloth or 

by brushing it with a soft bristle brush.
Care must be exercised to avoid 

damage to the sprinklers before, 

during, and after installation. Sprinklers 

damaged by dropping, striking, wrench 

twist/slippage, or the like, must be 

replaced. See the Installation section 

for additional information.
The owner is responsible for the 

inspection, testing, and maintenance 

of their fire protection system and 

devices in compliance with this doc-

ument, as well as with the applicable 

standards recognized by the Approval 

agency, such as NFPA 25, in addition 

to the standards of any authorities 

having jurisdiction. Contact the install-

ing contractor or product manufacturer 

regarding any questions.
Automatic sprinkler systems are rec-

ommended to be inspected, tested, 

and maintained by a qualified Inspec-

tion Service in accordance with local 

requirements and/or national codes.

Содержание tyco CWS

Страница 1: ...Model CWS Window Sprinkler can be used as interior protection for windows or glazing in a sprinklered building or non sprinklered building in accordance with Section 104 of the IBC Alternate Material...

Страница 2: ...ORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING LEVER SADDLE CAP DEFLECTOR 3 3 16 DIA 81 0 mm 2 1 2 DIA 63 5 mm MOUNTING SURFACE FACE OF SPRINKLER FITTING DEFLECTOR IN OPERATED POSITION DISPOSABL...

Страница 3: ...stem Protection Type Interior Wet Systems Glass Type The following types and thicknesses of glass are recognized for use with the Model CWS Window Sprinkler Non operable heat strengthened tempered sin...

Страница 4: ...ilized the linear length of the calculated window sprinklers may be reduced but in no case shall be less than 36 linear feet 1 2 x 900 If a single fire can be expected to operate Model CWS Window Spri...

Страница 5: ...listed to protect windows when intermediate horizontal mullions are present 4 0 1 22 m MAXIMUM 0 4 101 6 mm MINIMUM 8 0 2 44 m MAXIMUM MODEL CWS CONCEALED SPRINKLER 6 0 1 83 m MINIMUM MULLION Minimum...

Страница 6: ...E THROUGH USE OF 3 0 0 9 m MINIMUM PONY WALL INSTALLATION NOTE MODEL CWS SPRINKLER SHOWN ON ONE SIDE OF GLAZING FOR CLARITY FOR GLASS TYPES OTHER THAN FIRELITE PLUS CWS CERAMIC GLASS BY TGP ALL COMBUS...

Страница 7: ...nnot be engaged sufficiently to contact the ceiling the Sprinkler Fitting must be repositioned Care and Maintenance The TYCO Model CWS Specific Appli cation Window Sprinkler must be main tained and se...

Страница 8: ...temperature rating and P N specify 160 F 71 C 50 630 0 160 212 F 100 C 50 630 0 212 Note Sprinkler and Cover Plates are sepa rately sold See Cover Plate Assemblies subsection for ordering information...

Отзывы: