Model CC2 — 4.2 and 5.6 K-factor 

Combustible Concealed Space Sprinklers 

Specific Application, Upright

Page 1 of 8 

DECEMBER 2018 

TFP632

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The Model CC2 Combustible Con-

cealed Sprinklers are fast response, 

upright, specific application sprinklers 

designed to provide protection of spe-

cific light hazard combustible, as well 

as non-combustible, con cealed spaces 

requiring sprinkler protection. The CC2 

Sprinklers comply with the criterion for 

the protection of combustible con-

cealed spaces as de scribed in NFPA 

13.
The Model CC2 Sprinklers are designed 

for installation on BLAZEMASTER 

CPVC wet pipe systems, other UL 

Listed CPVC pipe products, and steel 

wet pipe or dry pipe sprinkler systems 

(refer to the respective Design Criteria 

sections). They provide the following 

features as compared to the 2.8K-fac-

tor Model CC1 Sprinklers described on 

Technical Data Sheet TFP630:
•  Can be used on steel dry pipe sprin-

kler systems

•  Increased spacing from 10 ft (3,1 m) 

to 12 ft (3,7 m)

•  Increased coverage area from 100 ft² 

(9,3 m²) to 144 ft² (13,4 m²)

The effectiveness of the Model CC2 

Sprinklers in combustible concealed 

spaces was clearly evident during the 

full scale fire testing for this product.

Concealed spaces between floors, as 

well as low pitch attics (slope of 2:12 

or less) are inherently shallow. Stan-

dard spray sprinklers, by design, have 

an umbrella like spray pattern that 

poses a difficult challenge when trying 

to achieve effective coverage within a 

shallow space. The Model CC2 Com-

bustible Concealed Space Sprinklers 

have addressed the difficult “above 

ceiling” fire challenge for both wet pipe 

and dry pipe sprinkler systems.

NOTICE 

The Model CC2 Combustible Con-

cealed Sprinklers described herein 

must be installed and maintained in 

compliance with this document, as well 

as with the applicable standards of the 

NATIONAL FIRE PROTECTION ASSO-

CIATION, in addition to the standards of 

any other authorities having jurisdiction. 

Failure to do so may impair the perfor-

mance of these devices.
The owner is responsible for main-

taining their fire protection system 

and de vices in proper operating con-

dition. Contact the installing contrac-

tor or product manufac turer with any 

questions.

Sprinkler 

Identification 

Number

TY2189 – Upright, 4.2K

TY3189 – Upright, 5.6K

Technical 

Data

Approvals

UL Listed 

(Listings and approvals only apply to the 

service conditions indicated in the Design 

Criteria sections.)

Maximum Working Pressure

175 psi (12,1 bar)

Pipe Thread Connection

1/2 in. NPT

Discharge Coefficient

K = 4.2 GPM/psi

½

 (60,5 LPM/bar

½

K = 5.6 GPM/psi

½

 (80,6 LPM/bar

½

)

Temperature Rating

175°F (79°C)

Finish

Natural Brass

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Sealing Assembly  . . . Stainless Steel w/TEFLON

Bulb  . . . . . . . . . . . . . . . . . . . . . . . . .Glass (3 mm)

Compression Screw . . . . . . . . . . . . . . . . . .Brass

Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Operation

The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb allowing the sprinkler to acti-

vate and flow water.

Design 

Criteria

Design criteria is provided as follows:
•  175°F (79°C), Model CC2 Combusti-

ble Concealed Sprinklers with CPVC 

Pipe and horizontal slope above 

sprinklers not exceeding 2:12 (Refer 

to Page 2).

•  175°F (79°C), Model CC2 Combusti-

ble Concealed Sprinklers with Steel 

Pipe and horizontal slope above 

sprinklers not exceeding 2:12 (Refer 

to Page 4).

Содержание tyco CC2

Страница 1: ...n dard spray sprinklers by design have an umbrella like spray pattern that poses a difficult challenge when trying to achieve effective coverage within a shallow space The Model CC2 Com bustible Conce...

Страница 2: ...4 1 2 in 114 mm Remote Area CPVC Pipe The remote area is 1000 ft 93 m NOTE The remote area does not include any additional sprinklers required for pro tection of BLAZE MASTER CPVC that is offset over...

Страница 3: ...DECK NON COMBUSTIBLE INSULATION 1 1 2 40 mm MINIMUM 6 152 mm MAXIMUM FOR CPVC PIPE COMPOSITE WOOD JOISTS SOLID WOOD JOISTS FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN WHEN OFFSETT...

Страница 4: ...eatest and run parallel with the joist spaced at 31 ft 9 4 m width maximum to limit the area to a max imum of 1000 ft 93 m The draft curtain may be constructed of 1 4 in 6 4 mm plywood to prevent heat...

Страница 5: ...MAXIMUM CEILING UPPER DECK FRAME ARMS OF SPRINKLER MUST BE INSTALLED IN LINE WITH PIPE RUN UPPER DECK CEILING FRAMING 54 1372 mm MAXIMUM 2x FLOOR SOLID WOOD JOISTS 6 152 mm MINIMUM 36 915 mm MAXIMUM M...

Страница 6: ...915 mm MAXIMUM UPPER DECK MODEL CC2 SPRINKLER CEILING FRAMING 54 1372 mm MAXIMUM CEILING TOP CHORD GREATER THAN 4 102 mm IN DEPTH 6 152 mm MINIMUM 36 915 mm MAXIMUM FRAME ARMS OF SPRINKLER MUST BE INS...

Страница 7: ...e 9 for installation of the Model CC2 Sprinklers by applying the wrench to the sprinkler wrench flats only WRENCH RECESS USE END A ONLY 0 2 1 2 63 5 mm 3 1 2 88 9 mm 5 1 2 139 7 mm 7 1 2 190 5 mm 9 1...

Страница 8: ...should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush Care must be exercised to avoid damage to the sprinklers before...

Отзывы: