1083163-UIM-J-0918
32
Johnson Controls Unitary Products
ADJUSTMENT OF TEMPERATURE RISE
After about 5 minutes of operation, determine the furnace temperature
rise. Take readings of both the return air and the heated air in the ducts,
about six feet (1.83 m) from the furnace where they will not be affected
by radiant heat. Increase the blower speed to decrease the temperature
rise; decrease the blower speed to increase the rise.
This furnace has a standard ECM motor. The blower motor speed taps
are located on the furnace control board in the blower compartment.
Refer to Figures 34-35 and the unit wiring label to change the blower
speed. Place all unused motor leads on the PARK terminal. One PARK
terminal is provided. To use the same speed tap for heating and cool-
ing, the terminals must be jumpered together. This control has a contin-
uous fan speed jumper. On a fan call only (G), the control will energize
which ever blower tap is selected by the jumper. This control will
change blower speeds based on other 24V thermostat inputs (Y1, Y/Y2,
W) respectively.
ADJUSTMENT OF FAN CONTROL SETTINGS
This furnace is equipped with a time-on/time-off heating fan control. The
fan on delay is fixed at 30 seconds. The fan off delay has 4 settings (60,
90, 120 and 180 seconds). The fan off delay is factory set to 120 sec-
onds. The fan-off setting must be long enough to adequately cool the
furnace, but not so long that cold air is blown into the heated space.
The fan-off timing may be adjusted by positioning the jumper on two of
the four pins as shown in Figure 34.
TAKING A FLUE GAS SAMPLE
If it becomes necessary to obtain a flue gas sample for analysis, it is
permissible to drill a small hole in the plastic flue pipe for a sample
probe, provided that the vent piping is PVC and the hole is properly
sealed afterwards. If using a polypropylene vent system, the vent sys-
tems manufacturer test port fitting must be used.
DO NOT
drill a test
port hole in polypropylene piping. Use the following procedure:
1. Drill a 11/32” hole in the side wall of the PVC vent pipe. If the hole is
in a horizontal section of the vent pipe, ensure that it is located
away from the bottom where condensation may be flowing back
toward the furnace.
2. Operate the furnace a minimum of (10 minutes) to ensure stable
operation of the combustion process.
3. Sample the flue gas as necessary to obtain CO readings.
4. Using a 1/8” pipe tap, cut threads into the sampling hole of the PVC
pipe.
5. Use high temp RTV as a sealant on the threads of a 1/8” brass
MPT plug and insert it 3 turns into the hole to correctly seal it.
DANGER
The temperature rise, or temperature difference between the return
air and the supply (heated) air from the furnace, must be within the
range shown on the furnace rating plate and within the application
limitations shown in Table 5.
The supply air temperature cannot exceed the “Maximum Supply
Air Temperature” specified in these instructions and on the furnace
rating plate. Under NO circumstances can the furnace be allowed to
operate above the Maximum Supply Air Temperature. Operating the
furnace above the Maximum Supply Air Temperature will cause pre-
mature heat exchanger failure, high levels of Carbon Monoxide, a fire
hazard, personal injury, property damage, and/or death.
!
FIGURE 35:
Furnace Control Board
ELECTRONIC AIR
CLEANER TERMINAL
HUMIDIFIER TERMINAL
DIAGNOSTIC ERROR CODE
RETRIEVAL BUTTON
BLOWER OFF DELAY JUMPER
CONTINUOUS FAN SPEED
JUMPER