TM-11x1 Series Room Temperature Module Installation Instructions 

5

The following messages apply to wiring this product.     

Setup and Adjustments

Make temperature or fan speed adjustments to the 
appropriate modules using the rotating dial, shown in 
Figure 3 and Figure 4.

Repair Information

Do not field repair the TM-11x1 Series Room 
Temperature Module. As with any electrical device, 
keep the air vents clean and free from dust and 
obstruction. To order replacement parts, contact the 
nearest Johnson Controls representative.

Technical Specifications 

!

CAUTION: Risk of Electric Shock. 

Disconnect power supply before making 
electrical connections to avoid electric 
shock. 

Mise En Garde: Risque de décharge 
électrique.

 Débrancher l'alimentation 

avant de réaliser tout raccordement 
électrique afin d'éviter tout risque de 
décharge électrique.

!

CAUTION: Risk of Property Damage.

 

Do not run low voltage cable in the same 
conduit or wiring troughs with high 
voltage wires. Running low and high 
voltage wires in the same conduit or 
wiring troughs may damage the 
equipment or cause system malfunction.

 
MISE EN GARDE : Risque de dégâts 
matériels.

Ne pas faire courir un câble basse 
tension dans les mêmes gaines ou 
goulottes électriques que des câbles 
haute tension. L'installation de fils basse 
tension et haute tension dans les mêmes 
gaines ou goulottes électriques risque 
d'endommager l'équipement ou de 
provoquer des dysfonctionnements du 
système.  

!

CAUTION: Risk of Property Damage.

 

Do not apply power to the system before 
checking all wiring connections. Short 
circuited or improperly connected wires 
may result in permanent damage to the 
equipment. 

Mise En Garde: Risque de dégâts 
matériels. 

Ne pas mettre le système 

sous tension avant d'avoir vérifié tous les 
raccords de câblage. Des fils formant un 
court-circuit ou connectés de façon 
incorrecte risquent d'endommager 
irrémédiablement l'équipement.

IMPORTANT:

Use copper conductors only. Make 

all wiring connections in accordance with local, 
national, and regional regulations. Do not exceed 
the Command Module electrical ratings.

TM-11x1 Series

 

Room Temperature Module (Part 1 of 2

)

Models

TM-1141-0000

Temperature Output Only

TM-1151-0000

Temperature Output with Occupancy Override

TM-1161-000x

Temperature Output with Setpoint Adjustment and Occupancy 
Override and Optional Fan Speed Adjustment

TM-1191-000x

Temperature Output with Setpoint  Adjustment

Power Requirements

Powered from TC-9102 Controller.

Power Consumption

N/A: Refer to individual component specification.

Inputs

None

Adjustments

Temperature Setpoint, Fan Speed (Optional by Model)

Mode Indicator

Green LED (5 V, 4 mA)

Occupancy Button 

Momentary Contact (Switches 5 V at 1 mA)

Output

Temperature Sensing 
Element

Resistance Temperature Device (RTD) Thermistor Negative 
Temperature Coefficient (NTC) 2,252 ohm at 77°F (25°C) 

Fan Speed

10k ohm Potentiometer, with Mechanically-Guided Positions 
at 0, 25, 50, 75, and 100% for Auto, Off, I (Low Speed), 
II (Medium Speed), and III (High Speed)

Содержание TM-11x1 series

Страница 1: ...speed fan override adjustment is available and models without a temperature sensor are provided for applications where the room temperature sensor is mounted inside the Fan Coil Unit Installation Parts Included Two 6 32 x 7 8 in 22 mm wallbox mounting screws are included with the TM 11x1 Module Special Tools Needed For tightening and loosening the TM 11x1 Series Room Temperature Module security sc...

Страница 2: ...141 Dimensions in mm 3 15 80 1 26 32 4 72 120 FIG TM41_dim Figure 2 TM 1151 Dimensions in mm FIG TM51_dim Mode LED Occupancy Button 3 15 80 1 26 32 4 72 120 Figure 3 TM 1161 Dimensions in mm FIG TM61_dim 1 38 35 4 72 120 3 15 80 Mode LED Occupancy Button Fan Speed Dial Setpoint Adjustment Dial Figure 4 TM 1191 Dimensions in mm FIG TM91_dim 3 15 80 1 38 35 4 72 120 Setpoint Adjustment Dial ...

Страница 3: ...th the allen head tool Mounting Location Considerations Mount the TM 11x1 Series Room Temperature Module on a wall in the room to be controlled Locate it where the occupant can easily read and adjust the setpoint dial or fan speed override adjustment dial Consider these additional guidelines to determine the best mounting location Avoid areas subject to excessive vibration electrical noise direct ...

Страница 4: ...e Setpoint Adjustment and Occupancy Override FIG TM61_WIR 15 14 21 20 NTC Sensor Common Mode LED Occupancy Button 23 22 15 14 21 20 23 22 Controller Room Temperature Module DC 5 V Temperature Setpoint Figure 8 Wiring to a Room Temperature Module Featuring an NTC Sensor with Temperature Setpoint Adjustment Occupancy Override and Three Speed Fan Override FIG TM61_WIR2 15 14 21 20 NTC Sensor Common M...

Страница 5: ...t ou de provoquer des dysfonctionnements du système CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment Mise En Garde Risque de dégâts matériels Ne pas mettre le système sous tension avant d avoir vérifié tous les raccords de câblage Des fils formant un ...

Страница 6: ...k ohm potentiometer marked for 5F TM 11x1 0007 10k ohm potentiometer marked for 5F Fan Speed Adjustment Auto Off I II and III Accuracy 0 9 F 0 5 C Field Connection 18 to 22 AWG 1 00 to 0 65 mm diameter recommended Mounting Wallbox Mount Housing Material ABS PC Self Extinguishing HB UL94 Protection IP30 EN 60529 Ambient Operating Conditions Temperature 32 to 122 F 0 to 50 C Humidity 10 to 90 RH Non...

Отзывы: