background image

TM-11x1 Series Room Temperature Module Installation Instructions 

3

Installing the TM-11x1

To install the TM-11x1 Series Room Temperature 
Module:

1.

Use the Allen-head tool to loosen the security 
screw located at the top center of the housing.

2.

Insert a screwdriver blade or coin into the slot on 
the top of the housing.

3.

Press down gently, and pry the housing away from 
the base. As the two parts separate, remove the 
blade or coin and continue to pull the housing away 
from the base until the housing is free.

4.

Pull the wires through the base. Locate the green 

terminal blocks in the upper right of the base and 

position the module on the wallbox with the 

terminal numbers right-side up.

5.

Mount the base to the wallbox using the two #6-32 
mounting screws (included).

6.

Wire the controller to the module. See the 

Wiring

 

section for correct wiring.

7.

Attach the housing to the base and tighten the 
security screw with the allen-head tool.

Mounting

Location Considerations

Mount the TM-11x1 Series Room Temperature Module 
on a wall in the room to be controlled. Locate it where 
the occupant can easily read and adjust the setpoint 
dial or fan speed override adjustment dial. Consider 
these additional guidelines to determine the best 
mounting location:

Avoid areas subject to excessive vibration, 
electrical noise, direct sunlight, or the effects of 
radiant heat.

Keep electrical wiring as short as possible to 
minimize temperature error.

Install modules in areas where the temperature is 
representative of the general room conditions.

Wiring

To wire a TC-9102 Controller to the TM-11x1 Series 
Room Temperature Module, see the appropriate wiring 
diagram (Figure 5 to Figure 9). 

Note:

Use 22 AWG (0.65 mm diameter) wire 

minimum. Do not exceed 164 ft (50 m) between the 
controller and the temperature module.

Table 1:  Nominal Values for Sensors

Temperature

Resistance

F

C

ohm

20

-7

10,595.0

30

-1

7,739.2

40

4

6,010.0

50

10

4,482.3

60

16

3,378.3

70

21

2,689.6

80

27

2,063.9

90

32

1,666.9

100

38

1,300.2

110

43

1,063.9

120

49

842.47

130

54

697.65

Содержание TM-11x1 series

Страница 1: ...speed fan override adjustment is available and models without a temperature sensor are provided for applications where the room temperature sensor is mounted inside the Fan Coil Unit Installation Parts Included Two 6 32 x 7 8 in 22 mm wallbox mounting screws are included with the TM 11x1 Module Special Tools Needed For tightening and loosening the TM 11x1 Series Room Temperature Module security sc...

Страница 2: ...141 Dimensions in mm 3 15 80 1 26 32 4 72 120 FIG TM41_dim Figure 2 TM 1151 Dimensions in mm FIG TM51_dim Mode LED Occupancy Button 3 15 80 1 26 32 4 72 120 Figure 3 TM 1161 Dimensions in mm FIG TM61_dim 1 38 35 4 72 120 3 15 80 Mode LED Occupancy Button Fan Speed Dial Setpoint Adjustment Dial Figure 4 TM 1191 Dimensions in mm FIG TM91_dim 3 15 80 1 38 35 4 72 120 Setpoint Adjustment Dial ...

Страница 3: ...th the allen head tool Mounting Location Considerations Mount the TM 11x1 Series Room Temperature Module on a wall in the room to be controlled Locate it where the occupant can easily read and adjust the setpoint dial or fan speed override adjustment dial Consider these additional guidelines to determine the best mounting location Avoid areas subject to excessive vibration electrical noise direct ...

Страница 4: ...e Setpoint Adjustment and Occupancy Override FIG TM61_WIR 15 14 21 20 NTC Sensor Common Mode LED Occupancy Button 23 22 15 14 21 20 23 22 Controller Room Temperature Module DC 5 V Temperature Setpoint Figure 8 Wiring to a Room Temperature Module Featuring an NTC Sensor with Temperature Setpoint Adjustment Occupancy Override and Three Speed Fan Override FIG TM61_WIR2 15 14 21 20 NTC Sensor Common M...

Страница 5: ...t ou de provoquer des dysfonctionnements du système CAUTION Risk of Property Damage Do not apply power to the system before checking all wiring connections Short circuited or improperly connected wires may result in permanent damage to the equipment Mise En Garde Risque de dégâts matériels Ne pas mettre le système sous tension avant d avoir vérifié tous les raccords de câblage Des fils formant un ...

Страница 6: ...k ohm potentiometer marked for 5F TM 11x1 0007 10k ohm potentiometer marked for 5F Fan Speed Adjustment Auto Off I II and III Accuracy 0 9 F 0 5 C Field Connection 18 to 22 AWG 1 00 to 0 65 mm diameter recommended Mounting Wallbox Mount Housing Material ABS PC Self Extinguishing HB UL94 Protection IP30 EN 60529 Ambient Operating Conditions Temperature 32 to 122 F 0 to 50 C Humidity 10 to 90 RH Non...

Отзывы: