TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
36
Control Setup
(Cont)
Fan Off Delay*
30 seconds
0 to 120 seconds
* Fan coil units only
Frost Protection
Yes
Yes or No
Dehumidification Enable*
No
Yes or No
* Fan coil units with humidity sensor
Aux Mode
Not Used
Not Used, Occupied NO, Occupied NC,
Occupied Fan NO, Occupied Fan NC, On,
Off
Load Shed Rate Limit
0.066°F
0 to 1°F (0 to 0.5°C)
Load Shed Adjust
4°F
0 to 8°F (0 to 4°C)
Fan Alarm Delay
0 seconds
0 to 300 seconds
Fan Alarm Delay
0 seconds
0 to 300 seconds
Fan Alarm Action*
Enable
Enable or Shutdown
* When Fan Alarm Delay is greater than 0
Fan Alarm Reset*
No
Yes or No
* When Fan Alarm Delay is greater than 0
Fan Runtime Limit
0 hours
0 to 9,000 hours
Fan Runtime Reset*
No
Yes or No
* When Fan Runtime Limit is greater than
0
Supply Air Temperature Alarm Offset
0°F
0 to 10°F (0 to 5.5°C)
Supply Air Temperature Alarm Delay*
300 seconds
300 to 3,600 seconds
* When Supply Air Temp Alarm Offset is
greater than 0
Unocc Low Speed Fan
Disable
Enable or Disable
*When Fan Type = Multi-Speed Fan
(only available in versions 3.0.4 or
greater)
Inputs
BI1 Configuration
Disabled
Disabled, Open Window, Open Door, Fan
Lock, Service, Dirty Filter, Motion NC,
Motion NO, Temp Occ, Occupancy
BI2 Configuration
Disabled
Disabled, Open Window, Open Door, Fan
Lock, Service, Dirty Filter, Motion NC,
Motion NO, Temp Occ, Occupancy
Supply Temp Type*
Analog Sensor
Analog Sensor, Heating NC, Cooling NC
* Non four-pipe units only
Supply Temp Sensor*
Nickel
Nickel, Platinum, A99B, 2.25k ohm
negative temperature coefficient (NTC),
10k ohm NTC, 10k ohm NTC Type 3
* SAT Mode = Analog Sensor,
non four-pipe
Supply Temp Offset*
0
-5 to 5 (°F or °C based on Units setting
under Display Settings menu)
* Analog Sensor
Zone Temp Sensor
Nickel
Nickel, Platinum, A99B, 2.25k ohm NTC,
10k ohm NTC, 10k ohm NTC Type 3
Zone Temp Offset
0
-5 to 5 (°F or °C based on Units setting
under Display Settings menu)
Table 10: Menus and Submenus (Part 3 of 9)
Level 1
Level 2
(LCD Screen Name)
Level 3
(Default Values)
Available Values
1