TEC3000 Series On/Off or Floating Fan Coil and Individual Zone Thermostat Controllers with Dehumidification
Capability Installation Instructions
19
16. Press to
return
to the previous screen.
17. Press
N2 Address
.
18. Enter the N2 address through the keypad.
19. Press
Save
.
Configuring the Thermostat Controller
Use the Menu icon on the home screen to access and change the basic operating parameters of the thermostat
controller. During normal operation, press the
Menu
icon once to access the following parameters:
Installer Configuration Menu
The thermostat controller comes from the factory with default settings for all configuration parameters. The UI
menu navigation and default settings are shown in Table 10. Before any outputs turn on, the controller must be
configured for the equipment connected. You need to start from the home screen to perform any of the following
tasks.
Screen Reset
The current screen returns to the home screen if the current screen is not touched for 3 minutes.
Selecting the Unit Type
There are three unit types. They are:
•
4-pipe—This unit type has both heating and cooling coils plus a supply fan. This configuration can also be used
on configurations that are heating or cooling only.
•
2-pipe—This unit type has a single set of pipes that can serve hot or chilled water plus a supply fan. The
Supply Temp Type allows for the connection of an analog sensor or an aquastat to a binary input. Based on the
water temperature or aquastat state, the unit controls heating or cooling.
•
VAV—This unit type is designed for a pressure-dependent zone damper and the supply fan outputs are
disabled. The TEC senses the supply air temperature coming from the unit. The Supply Temp Type setting
allows for the connection of an analog sensor or binary duct thermostat. Based on the air temperature or duct
thermostat state, the zone damper controls for heating or cooling. The TEC does not control the unit delivering
the air. The logic needs to be part of another controller.
By default, the thermostat controller is configured for 4-pipe fan coil mode. To change to a 2-pipe or
Pressure-Dependent VAV mode:
1.
Press the
Menu
icon.
2.
Press
Equipment Setup
.
3.
Press
General
.
4.
Press
Unit Type
and select
2-pipe
,
4-pipe
, or
VAV
.
5.
Press
to save and
to return to the previous screen.
Note:
Selecting VAV reboots the controller in order to apply the change.
• Faults
Status
• Display
Settings
• Equipment Setup
• Controller Information
• Setpoints
• Control
Setup
• System
Status
• Commissioning
• Schedule
• Network
Setup
• Control
Status
• Update