background image

 1

TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers

Technical Bulletin

Refer to the 

QuickLIT Web site

 for the most up-to-date version of this document.

Introduction  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Product Overview  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

Connecting the MS/TP Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

MS/TP Controller Mapping  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

Adding a Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

Adding Point Objects  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  9

Troubleshooting  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

MS/TP Bus Objects Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers . . . . . . . . . . . . . .  11

TEC2645-4 Thermostat Controller  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  18

TEC26x7-4 and TEC26x7-4+PIR Series Thermostat Controllers   . . . . . . . . . . . . . . . . .  22

TEC2601-4 and TEC2601-4+PIR Thermostat Controllers   . . . . . . . . . . . . . . . . . . . . . . .  26

TEC2602-4 and TEC2602-4+PIR Thermostat Controllers   . . . . . . . . . . . . . . . . . . . . . . .  29

TEC2603-4 and TEC2603-4+PIR Thermostat Controllers   . . . . . . . . . . . . . . . . . . . . . . .  33

TEC2613-4 and TEC2613-4+PIR Temperature and Humidity Controllers   . . . . . . . . . .  37

TEC2604-4 and TEC2604-4+PIR Thermostat Controllers   . . . . . . . . . . . . . . . . . . . . . . .  41

TEC262xx-0+PIR Thermostat Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  44

TEC Series BACnet® MS/TP Network Temperature and 
Humidity Controllers

Technical Bulletin

Code No. LIT-12011592

Issued March 4, 2013

Supersedes May 13, 2011

Содержание TEC2645-4

Страница 1: ...4 PIR Series Thermostat Controllers 11 TEC2645 4 Thermostat Controller 18 TEC26x7 4 and TEC26x7 4 PIR Series Thermostat Controllers 22 TEC2601 4 and TEC2601 4 PIR Thermostat Controllers 26 TEC2602 4...

Страница 2: ...TEC Series BACnet MS TP Network Temperature and Humidity Controllers Technical Bulletin 2...

Страница 3: ...in Introduction This document describes how to configure the various TEC Series Network Temperature and Humidity Controllers for BACnet Master Slave Token Passing MS TP networked applications includin...

Страница 4: ...x 4 PIR Series BACnet MS TP Networked Thermostat Controllers Product Bulletin LIT 12011585 TEC2613 4 and TEC2613 4 PIR BACnet MS TP Network Temperature and Humidity Controllers Product Bulletin LIT 12...

Страница 5: ...net MS TP Network Multi Stage Temperature and Humidity Controllers Installation Instructions Part No 24 9890 1389 TEC2604 4 and TEC2604 4 PIR BACnet MS TP Networked Multi Stage Economizer Thermostat C...

Страница 6: ...fication and dehumidification equipment two or four pipe fan coils cabinet unit heaters local hydronic reheat valves pressure dependent Variable Air Volume VAV equipment with or without local reheat o...

Страница 7: ...upervisory controller is at the end of the segment then the end of line terminator switch on the supervisory controller must be set in the ON position Note Refer to the controller product bulletin for...

Страница 8: ...hey should only be mapped if the operator is fully familiar with their use 2 Verify that a Field Bus is defined in the NAE BACnet MS TP devices attach to a Field Bus Refer to the BACnet MS TP Integrat...

Страница 9: ...esignates the address selected from 004 to 127 on the MS TP network for example 73004 73005 If this ID needs to be changed by writing a new one into the controller device object that ID change should...

Страница 10: ...he probable causes listed previously in the Multiple Symptoms section of this table Excessive bus traffic may exist bus overload The baud rate may be set too low There may be too many devices on the n...

Страница 11: ...dity TEC2636 4 TEC2636H 4 TEC2636H 4 PIR TEC2656 4 TEC2656H 4 and TEC2656H 4 PIR Models AV 10 5 to 90 RH Room Humidity Override TEC2636 4 TEC2636H 4 TEC2636H 4 PIR TEC2656 4 TEC2656H 4 and TEC2656H 4...

Страница 12: ...g Demand5 AV 22 0 to 100 Dehumidification Status TEC2636 4 TEC2636H 4 TEC2636H 4 PIR TEC2656 4 TEC2656H 4 and TEC2656H 4 PIR Models BI 23 0 Off 1 On AUX BO5 Status5 BI 25 0 Off 1 On Heating BO3 and BO...

Страница 13: ...Window Alarm5 BI 35 0 Off 1 On Filter Alarm5 BI 36 0 Off 1 On Service Alarm5 BI 37 0 Off 1 On Occupied Heat Setpoint3 AV 39 40 0 F 4 5 C to 90 0 F 32 0 C Occupied Cool Setpoint3 7 AV 40 54 0 F 12 0 C...

Страница 14: ...guration3 MSV 52 1 Two Pipe 2 Four Pipe AUX BO5 Configuration3 MSV 54 1 Not Used 2 NO with Occ 3 NC with Occ 4 NO with Occ and Fan 5 NC with Occ and Fan 6 Networked Controlled Password Value AV 56 0 t...

Страница 15: ...64 0 15 Minutes 1 10 Seconds Proportional Band MSV 65 1 3 3 F 1 7 C 2 4 4 F 2 2 C 3 5 5 F 2 8 C 4 6 6 F 3 3 C 5 7 7 F 3 9 C 6 8 8 F 4 4 C 7 9 9 F 5 0 C 8 10 10 F 5 6 C Auto Fan BV 66 0 Auto Speed 1 A...

Страница 16: ...g Motor Timing3 TEC2626 4 TEC2626H 4 TEC2626H 4 PIR TEC2636 4 TEC2636H 4 and TEC2636H 4 PIR Models MSV 76 1 0 5 Minutes 2 1 0 Minute 3 1 5 Minutes 4 2 0 Minutes 5 2 5 Minutes 6 3 0 Minutes 7 3 5 Minut...

Страница 17: ...ent value 2 This MS TP Bus object may automatically release after 10 minutes with no BACnet traffic 3 This MS TP Bus object is readable and writable 4 This MS TP Bus object is valid only if it is writ...

Страница 18: ...Cooling and Reheat 3 Heating and Reheat System Mode3 MSV 16 1 Off 2 Auto 3 Cool 4 Heat Fan Mode3 MSV 17 1 On 2 Auto Occupancy Command3 MSV 18 1 Resume Schedule 2 Occupied 3 Unoccupied 4 Temporary Occ...

Страница 19: ...Motion NO 4 Motion NC 5 Window BI2 Configuration3 MSV 47 1 None 2 Door Dry 3 Override 4 Filter 5 Service UI3 Configuration3 MSV 48 1 None 2 COC NH 3 COC NC 4 COS 5 SS Menu Scroll3 BV 49 0 No Scroll 1...

Страница 20: ...ours 21 20 Hours 22 21 Hours 23 22 Hours 24 23 Hours 25 24 Hours Deadband3 AV 63 2F 1C to 5F 3C Reheat Time Base BO5 3 BV 64 0 15 Minutes 1 10 Seconds Proportional Band MSV 65 1 3 3 F 1 7 C 2 4 4 F 2...

Страница 21: ...traffic 3 This MS TP Bus object is readable and writable 4 This MS TP Bus object is valid only if it is written via the network 5 This MS TP Bus object is readable only 6 The BI object type status is...

Страница 22: ...ating Only 3 Cooling and Reheat 4 Heating and Reheat 5 Cool Heat Four Pipe 6 Cool Heat Four Pipe and Reheat System Mode3 MSV 16 1 Off 2 Cool 3 Heat 4 Auto Occupancy Command3 MSV 18 1 Resume Schedule 2...

Страница 23: ...5 C Stand by Heat Setpoint3 7 AV 41 40 0 F 4 5 C to 90 0 F 32 0 C Stand by Cool Setpoint3 7 AV 42 54 0 F 12 0 C to 100 0 F 37 5 C Unoccupied Heat Setpoint3 7 AV 43 40 0 F 4 5 C to 90 0 F 32 0 C Unocc...

Страница 24: ...8 Hours 10 9 Hours 11 10 Hours 12 11 Hours 13 12 Hours 14 13 Hours 15 14 Hours 16 15 Hours 17 16 Hours 18 17 Hours 19 18 Hours 20 19 Hours 21 20 Hours 22 21 Hours 23 22 Hours 24 23 Hours 25 24 Hours D...

Страница 25: ...rride This corresponding override object needs to be set to 1 Override to be able to write Room Temp to a different value 2 This MS TP Bus object may automatically release after 10 minutes with no BAC...

Страница 26: ...cy 2 Occupied 3 Unoccupied System Mode RTU2 MV 14 1 Off 2 Auto 3 Cool 4 Heat Fan Mode2 MV 15 1 On 2 Auto 3 Smart Supply Temperature4 AI 16 40 0 F 40 0 C to 122 0 F 50 0 C Keypad Lockout2 MV 18 1 Level...

Страница 27: ...emperature2 AV 50 15 0 F 26 0 C to 120 0 F 49 0 C Cooling Lockout Temperature2 AV 51 40 0 F 40 0 C to 95 0 F 35 0 C Deadband2 AV 52 2 0F 1 0C to 4 0F 2 0C Heating CPH2 MV 53 1 3 CPH 2 4 CPH 3 5 CPH 4...

Страница 28: ...needs to be set to 1 Override to be able to write Room Temp to a different value 2 This MS TP Bus object is readable and writable 3 This MS TP Bus object may automatically release after 10 minutes wi...

Страница 29: ...Occupied 3 Unoccupied System Mode HPU2 MV 13 1 Off 2 Auto 3 Cool 4 Heat 5 Emergency Fan Mode2 MV 15 1 On 2 Auto 3 Smart Supply Temperature4 AI 16 40 0 F 40 0 C to 122 0 F 50 0 C Keypad Lockout2 MV 18...

Страница 30: ...AV 48 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Setpoint Limit2 AV 49 54 0 F 12 0 C to 100 0 F 37 5 C Heating Lockout Temperature2 AV 50 15 0 F 26 0 C to 120 0 F 49 0 C Cooling Lockout Temperature2 AV 51...

Страница 31: ...4 Filter 5 Service 6 Fan Lock DI2 Configuration2 MV 66 1 None 2 Rem NSB 3 RemOVR 4 Filter 5 Service 6 Fan Lock Proportional Band MSV 67 1 2 2 F 1 1 C 2 3 3 F 1 7 C 3 4 4 F 2 2 C 4 5 5 F 2 8 C 5 6 6 F...

Страница 32: ...This MS TP Bus object is readable and only writable when out of service 5 This BI object type status is available even if the configuration is set to None 6 This MS TP Bus object requires that Frost...

Страница 33: ...cupancy 2 Occupied 3 Unoccupied System Mode RTU2 MV 14 1 Off 2 Auto 3 Cool 4 Heat Fan Mode2 MV 15 1 On 2 Auto 3 Smart Supply Temperature4 AI 16 40 0 F 40 0 C to 122 0 F 50 0 C Keypad Lockout2 MV 18 1...

Страница 34: ...AV 48 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Setpoint Limit2 AV 49 54 0 F 12 0 C to 100 0 F 37 5 C Heating Lockout Temperature2 AV 50 15 0 F 26 0 C to 120 0 F 49 0 C Cooling Lockout Temperature2 AV 51...

Страница 35: ...3 1 0 Minutes 2 1 Minute 3 2 Minutes 4 3 Minutes 5 4 Minutes 6 5 Minutes Fan Purge Delay2 BV 64 0 Off 1 On DI1 Configuration2 MV 65 1 None 2 Rem NSB 3 RemOVR 4 Filter 5 Service 6 Fan Lock DI2 Configur...

Страница 36: ...y release after 10 minutes with no BACnet traffic 4 This MS TP Bus object is readable and only writable when out of service 5 This BI object type status is available even if the configuration is set t...

Страница 37: ...erride Room Humidity AV 11 0 to 100 Occupancy2 MV 12 1 Local Occupancy 2 Occupied 3 Unoccupied System Mode RTU2 MV 14 1 Off 2 Auto 3 Cool 4 Heat Fan Mode2 MV 15 1 On 2 Auto 3 Smart Supply RH AI 17 0 t...

Страница 38: ...AV 48 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Setpoint Limit2 AV 49 54 0 F 12 0 C to 100 0 F 37 5 C Heating Lockout Temperature2 AV 50 15 0 F 26 0 C to 120 0 F 49 0 C Cooling Lockout Temperature2 AV 51...

Страница 39: ...1 2 2 F 1 1 C 2 3 3 F 1 7 C 3 4 4 F 2 2 C 4 5 5 F 2 8 C 5 6 6 F 3 3 C 6 7 7 F 3 9 C 7 8 8 F 4 4 C Unoccupied Time4 AV 68 0 5 Hours to 24 0 Hours Heating Stages2 MV 73 1 One Stage 2 Two Stages Cooling...

Страница 40: ...TP Bus object is readable and writable 3 This MS TP Bus object may automatically release after 10 minutes with no BACnet traffic 4 This MS TP Bus object is readable and only writable when out of servi...

Страница 41: ...ed 3 Unoccupied System Mode RTU2 MV 14 1 Off 2 Auto 3 Cool 4 Heat Fan Mode2 MV 15 1 On 2 Auto 3 Smart Supply Temperature4 AI 16 40 0 F 40 0 C to 122 0 F 50 0 C Keypad Lockout2 MV 18 1 Level 0 2 Level...

Страница 42: ...AV 48 40 0 F 4 5 C to 90 0 F 32 0 C Cooling Setpoint Limit2 AV 49 54 0 F 12 0 C to 100 0 F 37 5 C Heating Lockout Temperature2 AV 50 15 0 F 26 0 C to 120 0 F 49 0 C Cooling Lockout Temperature2 AV 51...

Страница 43: ...SB 3 RemOVR 4 Filter 5 Service 6 Fan Lock DI2 Configuration2 MV 66 1 None 2 Rem NSB 3 RemOVR 4 Filter 5 Service 6 Fan Lock Proportional Band MSV 67 1 2 2 F 1 1 C 2 3 3 F 1 7 C 3 4 4 F 2 2 C 4 5 5 F 2...

Страница 44: ...ooling setpoints for example Occupied Heat Setpoint and Occupied Cool Setpoint is overridden the other setpoint of the pair may be automatically adjusted by the thermostat controller to maintain the m...

Страница 45: ...to 100 Dehumidification Status BI 23 0 Off 1 On Fan Status MSV 28 1 Off 2 Low 3 Medium 4 High BI 1 Status BI 29 0 Deactivated 1 Activated B1 2 Status BI 30 0 Deactivated 1 Activated Local Motion BI 3...

Страница 46: ...uto Mode Enable BV 50 0 Disabled 1 Enabled Temperature Scale BV 51 0 C 1 F Pipe Number MSV 52 1 2 Pipe 2 4 Pipe Password Value AV 56 0 to 1000 Fan Mode Sequence MSV 57 1 Low Medium High 2 Low High 3 L...

Страница 47: ...l Band MSV 65 1 3 3 F 1 2 C 2 4 4 F 1 7 C 3 5 5 F 2 2 C 4 6 6 F 2 8 C 5 7 7 F 3 3 C 6 8 8 F 3 9 C 7 9 9 F 5 0 C 8 10 10 F 5 6 C Auto Fan BV 66 0 Auto Speed 1 Auto Speed Auto Demand Stand by Time AV 67...

Страница 48: ...PH 6 6 CPH 7 7 CPH 8 8 CPH Cool CPH MSV 85 3 3 CPH 4 4 CPH 5 5 CPH 6 6 CPH 7 7 CPH 8 8 CPH Heat NO NC BV 86 0 Normally Open 1 Normally Closed Cool No NC BV 87 0 Normally Open 1 Normally Closed Heat De...

Отзывы: