TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
44
TEC26xx-0+PIR Thermostat Controllers
Mixed Air Setpoint
AV 80
50.0°F/10.0°C to
90.0°F/32.0°C
TEC2604-address
8
Device 76aaa
9
TEC2604-4 to TEC2604-127
1.
This MS/TP Bus object is readable and only writable if the corresponding override is set. (For
example,
Room Temp
has a corresponding override object of
Room Temp Override
. This
corresponding override object needs to be set to
1 = Override
to be able to write
Room Temp
to a
different value.)
2.
This MS/TP Bus object is readable and writable.
3.
This MS/TP Bus object may automatically release after 10 minutes with no BACnet traffic.
4.
This MS/TP Bus object is readable and only writable when out of service.
5.
This BI object type status is available even if the configuration is set to
None
.
6.
This MS/TP Bus object requires that
Frost Protection
be set to
1 = On
.
7.
If one setpoint of a pair of heating and cooling setpoints (for example,
Occupied Heat Setpoint
and
Occupied Cool Setpoint
) is overridden, the other setpoint of the pair may be automatically adjusted
by the thermostat controller to maintain the minimum deadband between the two setpoints.
8.
The address range actually displays from
0
to
254
. Only choose an address within the
4
to
127
range.
9.
The designation
aaa
is the address of the device (from
004
to
127
) on the MS/TP network.
Table 11: TEC26xx-0+PIR (Part 1 of 5)
Point Name
Thermostat Point
(Type/Address)
Range
Room Temp
AV 7
-40.0°F/-40.0°C to
122.0°F/50.0°C
Room Temp Override
BV 8
0 = Normal
1 = Override
Outdoor Temperature
AV 9
-40.0°F/-40.0°C to
122.0°F/50.0°C
Room Humidity
AV 10
5 to 90%
Room Humidity Override
BV 11
0 = Normal
1 = Override
Supply Temperature
AI 12
-40.0°F/-40.0°C to
122.0°F/50.0°C
Dehumidification Lockout
BV 13
0 = Disabled
1 = Enabled
Sequence of Operation
MSV 15
1 = Cooling Only
2 = Heating Only
3 = Cooling/Reheat
4 = Heating/Reheat
5 = Cooling/Heat4P
6 = Cool/Heat4P/Reheat
System Mode
MSV 16
1 = Off
2 = Auto
3 = Cool
4 = Heat
Table 10: TEC2604-4 and TEC2604-4+PIR MS/TP Bus Objects (Part 4 of 4)
Point Name
Thermostat Point
(Type/Address)
Range