TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
41
TEC2604-4 and TEC2604-4+PIR Thermostat Controllers
Table 10: TEC2604-4 and TEC2604-4+PIR MS/TP Bus Objects (Part 1 of 4)
Point Name
Thermostat Point
(Type/Address)
Range
Room Temp
1
AV 7
-40.0°F/-40.0°C to
122.0°F/50.0°C
Room Temp Override
2,
3
BV 8
0 = Normal
1 = Override
Outdoor Temperature
AV 9
-40.0°F/-40.0°C to
122.0°F/50.0°C
Outdoor Temp Override
BV 10
0 = Normal
1 = Override
Occupancy
MV 12
1 = Local Occupancy
2 = Occupied
3 = Unoccupied
System Mode RTU
MV 14
1 = Off
2 = Auto
3 = Cool
4 = Heat
Fan Mode
MV 15
1 = On
2 = Auto
3 = Smart
Supply Temperature
4
AI 16
-40.0°F/-40.0°C to
122.0°F/50.0°C
Keypad Lockout
MV 18
1 = Level 0
2 = Level 1
3 = Level 2
PI Heating Demand
AV 20
0 to 100%
PI Cooling Demand
AV 21
0 to 100%
Economizer Output
AV 22
0 to 100%
Aux
BI 24
0 = Off
1 = On
G Fan
BI 25
0 = Off
1 = On
Y1 Cool
BI 26
0 = Off
1 = On
Y2 Cool
BI 27
0 = Off
1 = On
W1 Heat
BI 28
0 = Off
1 = On
W2 Heat
BI 29
0 = Off
1 = On
DI1 Status
5
BI 31
0 = Not Activated
1 = Activated
DI2 Status
BI 32
0 = Not Activated
1 = Activated
Local Motion
BI 33
0 = No Motion
1 = Motion
Effective Occupancy
MV 34
1 = Occupied
2 = Unoccupied
3 = Temporary Occupied
Frost Alarm
6
BI 36
0 = Off
1 = On