5566020-JIM-C-1019
26
Johnson Controls Ducted Systems
J10
(10)
208
15.6
110
24
3.03
9.6
5.5
None
-
-
-
50.8
56.3
60
70
E18
13.5
2
37.5
58.9
65.8
60
70
E24
18
2
50
74.5
81.4
80
90
E36
25.5
2
70.8
100.5
107.4
110
110
E54
40.6
2
112.7
152.9
159.8
175
175
230
15.6
110
24
3.03
9.6
5.5
None
-
-
-
50.8
56.3
60
70
E18
18
2
43.3
66.1
73
70
80
E24
24
2
57.7
84.1
91
90
100
E36
34
2
81.8
114.3
121.1
125
125
E54
54
2
129.9
141.9
148.8
175
175
460
7.8
52
12
1.6
4.7
2.2
None
-
-
-
25.5
27.7
30
35
E18
18
2
21.7
33
35.8
35
40
E24
24
2
28.9
42
44.8
45
45
E36
34
2
40.9
57
59.8
60
60
E54
54
2
65
70.9
73.6
80
80
575
5.8
38.9
9
1.35
3.6
1.8
None
-
-
-
19.4
21.2
25
25
E18
18
2
17.3
26.1
28.4
30
30
E24
24
2
23.1
33.4
35.6
35
40
E36
34
2
32.7
45.4
47.6
50
50
E54
54
2
52
56.5
58.8
70
70
J12
(12.5)
208
23.1
160
36
3.03
14
5.5
None
-
-
-
78.1
83.6
100
100
E18
13.5
2
37.5
78.1
83.6
100
100
E24
18
2
50
80
86.9
100
100
E36
25.5
2
70.8
106
112.9
110
125
E54
40.6
2
112.7
158.4
165.3
175
175
230
23.1
160
36
3.03
14
5.5
None
-
-
-
78.1
83.6
100
100
E18
18
2
43.3
78.1
83.6
100
100
E24
24
2
57.7
89.6
96.5
100
100
E36
34
2
81.8
119.8
126.6
125
150
E54
54
2
129.9
147.4
154.3
175
175
460
12.2
87
19
1.6
6.6
2.2
None
-
-
-
40.5
42.7
50
50
E18
18
2
21.7
40.5
42.7
50
50
E24
24
2
28.9
44.4
47.1
50
50
E36
34
2
40.9
59.4
62.1
60
70
E54
54
2
65
73.3
76
80
90
575
8.7
62
14
1.35
5.2
1.8
None
-
-
-
30.2
32
35
40
E18
18
2
17.3
30.2
32
35
40
E24
24
2
23.1
35.4
37.6
40
40
E36
34
2
32.7
47.4
49.6
50
50
E54
54
2
52
58.5
60.8
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
J06 through 12ZF high static motor - without powered convenience outlet (continued)
Size
(tons)
Volt
Compressors
(each)
OD fan
motors
(each)
Supply
blower
motor
Pwr exh
motor
Pwr
conv
outlet
Electric heat option
MCA
1
(amps)
MCA
1
with pwr
exh (amps)
Max fuse
2
/
breaker
3
size (amps)
Max fuse
2
/
breaker
3
size with
pwr exh
(amps)
RLA LRA MCC
FLA
FLA
FLA
FLA
Model
kW