5566020-JIM-C-1019
32
Johnson Controls Ducted Systems
Condenser fan data
Quantity of fans
2
2
2
2
4
Fan diameter (inches)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive type
Direct
Direct
Direct
Direct
Direct
Quantity of motors
2
2
2
2
4
Motor HP each
1/3
1/3
3/4
3/4
3/4
No. of speeds
1
1
1
1
1
RPM
850
850
1110
1110
1110
Total CFM
6200
7600
9500
9500
11200
Belt drive evap. fan data
Quantity
1
1
1
1
1
Fan size (inches)
12 x 12
12 x 12
15 x 15
15 x 15
15 x 15
Type
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor sheave
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower sheave
AK74
AK64
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A49
A49
A49
A49
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
2
1-1/2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
Frame size
56
56
56
56
56
56
56
56
56
184T
Filters
Quantity - size
4 - (24 x 16 x 2)
6
,
7
4 - (24 x 16 x 2)
6,7
4 - (24 x 20 x 2)
6,7
4 - (24 x 20 x 2)
6,7
4 - (24 x 20 x 2)
6,7
4 - (24 x 16 x 4)
8
4 - (24 x 16 x 4)
8
4 - (24 x 20 x 4)
8
4 - (24 x 20 x 4)
8
4 - (24 x 20 x 4)
8
1. Cooling only unit or cooling unit with electric heat
2. Cooling unit with gas heat
3. Does not meet DOE 2018 minimum efficiency requirements.
4. First stage 60% of second stage
5. All J**ZF units have crankcase heaters as standard
6. 2 in. throwaway, standard, MERV (Minimum Efficiency Reporting Value) 3
7. 2 in. pleated, optional, MERV 8
8. 4 in. pleated, optional, MERV 13
Table 14:J06 through 12ZF physical data (continued)
Component
Models
J06ZF
J07ZF
J08ZF
J10ZF
J12ZF
Nominal tonnage
6.5
7.5
8.5
10
12.5