background image

1031990-UAD-A-0313

4

Johnson Controls Unitary Products

TABLE 2: POINTS LIST IN DESCRIPTION ORDER  

Read/ 

Write

BACnet 

Object 

Type

BACnet 

Object 

Inst

Descriptor

Default Min

Max Point Description

R / W

(5) BV

109

COMM_IAQ

n/a

n/a

n/a

Accept Comm Value for Indoor Quality 
Sensor

R / W

(5) BV

101

COMM_OAT

n/a

n/a

n/a

Accept Comm Value for OAT

R / W

(5) BV

100

COMM_OH

n/a

n/a

n/a

Accept Comm Value for OH

R / W

(5) BV

99

COMM_RH

n/a

n/a

n/a

Accept Comm Value for RH

R / W

(5) BV

108

COMM_ST

n/a

n/a

n/a

Accept Comm Value for Space 
Temperature

R / W

(2) AV

14

ACC_OVER_TME

n/a

n/a

n/a

Accumulated Unoccupied Override 
Time (in hours)

R

(2) AI

15

ACTIVE_ALARM

n/a

n/a

n/a

Active Alarm

R

(2) AI

86

AIR_MON_INPUT

0

0

10

Air Monitor Station Input

R

(5) BI

16

AIR_PROOF_SW

n/a

n/a

n/a

Air Proving Switch Status (1=closed, 
0=open / no air flow)

R / W

(2) AV

79

OAQ_STPT

1000

0

5000

Air Quality Setpoint Outside

R

(5) BI

85

ALARM_1_ON

n/a

n/a

n/a

Alarm Buffer #1 (0=Alarm has cleared, 
1=Alarm is still active)

R

(5) BI

86

ALARM_2_ON

n/a

n/a

n/a

Alarm Buffer #2 (0=Alarm has cleared, 
1=Alarm is still active)

R

(5) BI

87

ALARM_3_ON

n/a

n/a

n/a

Alarm Buffer #3 (0=Alarm has cleared, 
1=Alarm is still active)

R

(5) BI

88

ALARM_4_ON

n/a

n/a

n/a

Alarm Buffer #4 (0=Alarm has cleared, 
1=Alarm is still active)

R

(5) BI

89

ALARM_5_ON

n/a

n/a

n/a

Alarm Buffer #5 (0=Alarm has cleared, 
1=Alarm is still active)

R

(2) AI

33

BLDG_STATIC

n/a

n/a

n/a

Building Static Pressure

R / W

(5) BV

29

BP_SENS_INST

n/a

n/a

n/a

Building Static Pressure Sensor 
Installed

R / W

(2) AV

57

BLDG_SP_STPT

0.15

-0.25 0.25

Building Static Pressure Setpoint

R / W

(2) AV

25

COM_V_LOW_SP

70

60

80

Comfort Ventilation LowerSetpoint 
(degrees F)

R / W

(5) BV

34

CVM_COOLING

n/a

n/a

n/a

Comfort Ventilation Mode for Cooling 
Enabled

R / W

(5) BV

35

CVM_HEATING

n/a

n/a

n/a

Comfort Ventilation Mode for Heating 
Enabled

R

(5) BI

33

COM_VENT_STA

n/a

n/a

n/a

Comfort Ventilation Mode Status 
(1=control is in Comfort Vent mode, 0= it 
is not)

R / W

(2) AV

24

COM_V_HI_SP

80

65

85

Comfort Ventilation Upper Setpoint 
(degrees F)

R / W

(5) BV

23

COOLING_ENA

n/a

n/a

n/a

Cooling Mode Enabled

R

(2) AI

56

CV_VAV_SELEC

n/a

n/a

n/a

CV / VAV Selected (0= Valid CV, 
1=Valid VAV, 2= Invalid Value)

R / W

(5) BV

21

FAN_ON_W_SEN

n/a

n/a

n/a

CV-Indoor Fan Operates with Space 
Sensor Present Option Enabled

R / W

(2) AV

8

IAQ_VALUE

n/a

0

5000

Demand Ventilation (IAQ) Value (PPM)

Содержание Simplicity LINC

Страница 1: ...fort controllers The Simplicity LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit s control transformer One port is connected to the UP controller The other p...

Страница 2: ...and defaulted to 230 The combination of the DE Modifier and the default DIP switch setting creates a default DE of 23001 The default Unit Name is YORK_RTU FIGURE 2 MAC ADDRESS EXAMPLES DIP switches B...

Страница 3: ...URCE1 Toll free at 1 800 536 6112 SOFTWARE SETUP The control sequence is managed by the Simplicity controller The data points on these systems are mapped to standard BACnet Objects As a preconfigured...

Страница 4: ...ive R 5 BI 87 ALARM_3_ON n a n a n a Alarm Buffer 3 0 Alarm has cleared 1 Alarm is still active R 5 BI 88 ALARM_4_ON n a n a n a Alarm Buffer 4 0 Alarm has cleared 1 Alarm is still active R 5 BI 89 AL...

Страница 5: ...BI 31 ECONO_STATUS n a n a n a Economizer Output Status 0 not Free Cooling 1 Free Cooling R W 2 AV 22 ECON_OAEN_SP 27 10 50 Economizer Outside Air Enthalpy Setpoint R W 2 AV 23 ECON_OAT_ENA 55 40 80...

Страница 6: ...zed R 5 BI 64 E_GAS_VLVE3 n a n a n a Elite Gas Valve 3 Input Status 1 energized 0 not energized R 5 BI 44 E_HPS1 n a n a n a Elite High Pressure Switch for Compressor 1 Input Status 1 closed 0 open f...

Страница 7: ...Present R 5 BI 32 FRECOOL_STAT n a n a n a Free Cooling Mode Status 0 comps not overridden by Econo 1 comps overridden R 5 BI 104 FREEZE_STAT_1 n a n a n a Freeze Stat 1 R 5 BI 105 FREEZE_STAT_2 n a...

Страница 8: ...elli Comfort Compressor 2 Accumulated Run Time in hours R 5 BI 76 I_COMP2_STAT n a n a n a Intelli Comfort Compressor 2 Input Status 0 output is OFF 1 output is ON R 5 BI 79 I_CFAN_STAT n a n a n a In...

Страница 9: ...0 100 Maximum Demand Ventillation Economizer Position R W 5 BV 110 MIN_AMB_SEN n a n a n a Minimum Outdoor Air Sensor Enabled R W 2 AV 85 MIN_AMB_TEMP_SP 0 0 100 Minimum Outdoor Air Temperature Setpo...

Страница 10: ...1 REM_CONT_BAS_ECON n a n a n a Remote Control Third Party BAS Economizer Enable R 2 AI 13 RET_AIR_ENTH n a n a n a Return Air Enthalpy R W 2 AV 12 RET_AIR_HUM n a n a n a Return Air Humidity R 2 AI 5...

Страница 11: ...OFF Continuous Fan when Starting Heat Enabled 0 Continuous Fan ON R W 2 AV 2 UNOC_COOL_SP 85 46 99 Un Occupied Cooling Setpoint R W 2 AV 51 UNOC_HEAT_SP 60 45 98 Un Occupied Heating Setpoint R W 2 AV...

Страница 12: ...umidity R 2 AI 13 RET_AIR_ENTH n a n a n a Return Air Enthalpy R W 2 AV 14 ACC_OVER_TME n a n a n a Accumulated Unoccupied Override Time in hours R 2 AI 15 ACTIVE_ALARM n a n a n a Active Alarm R 2 AI...

Страница 13: ...te Compressor 2 Accumulated Run Time in hours R 2 AI 43 E_C3_ACM_HRS n a n a n a Elite Compressor 3 Accumulated Run Time in hours R 2 AI 44 E_C4_ACM_HRS n a n a n a Elite Compressor 4 Accumulated Run...

Страница 14: ...VAV_CL_HI_SP 60 41 70 VAV Cooling Supply Air Temperature Upper Setpoint degrees F R W 2 AV 65 VAV_CL_LO_SP 55 40 69 VAV Cooling Supply Air Temperature Lower Setpoint degrees F R W 2 AV 66 VAV_SAT_RSET...

Страница 15: ...V 90 FAN_SPD_NO_HEAT_C OOL 50 0 100 Fan Speed No Heating No Cooling R W 2 AV 91 FAN_SPD_1ST_COOL 70 0 100 Fan Speed 1st Stage Cooling R W 2 AV 92 FAN_SPD_1ST_HEAT 100 0 100 Fan Speed 1st Stage Heating...

Страница 16: ...Space Sensor Present Option Enabled R W 5 BV 22 SAT_COOLING n a n a n a Supply Air Temperature Limit for Cooling Enabled R W 5 BV 23 COOLING_ENA n a n a n a Cooling Mode Enabled R W 5 BV 24 SAT_HEATIN...

Страница 17: ...ut Status 1 closed 0 open fault R 5 BI 44 E_HPS1 n a n a n a Elite High Pressure Switch for Compressor 1 Input Status 1 closed 0 open fault R 5 BI 45 E_C1_OVRLOAD n a n a n a Elite Compressor 1 Overlo...

Страница 18: ...energized R 5 BI 61 E_LIMIT_ 1 n a n a n a Elite Limit Switch 1 Input Status 1 closed 0 open fault R 5 BI 62 E_GAS_VLVE2 n a n a n a Elite Gas Valve 2 Input Status 1 energized 0 not energized R 5 BI...

Страница 19: ...li Comfort High Pressure Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BI 79 I_CFAN_STAT n a n a n a Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5 BI...

Страница 20: ...n a n a Accept Comm Value for OAT R 5 BI 102 4_STG_EXP_PRES n a n a n a Four Stage Expansion board Present R 5 BI 103 VAV_INTELLI_2_PRES n a n a n a VAV Intelli Comfort 2 Expansion Board Present R 5...

Страница 21: ...l turn off after 5 seconds If the Node Offline LED stays on solid a node offline condition has occurred Unused 15 seconds after powering up the 4 unused LEDs will turn on solid for 5 seconds then turn...

Страница 22: ...ls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 FIGURE 3 SIMPLICITY LINC BOARD AND LED LAYOUT PWR RS485 PWR BACnet EOL Switch So Reset S...