APPLICATION GUIDE

OVERVIEW

The 

Simplicity

®

LINC Gateway operates as a Modbus® Client 

providing an interface between a BACnet® MS/TP control system 
and devices that communicate using the Modbus RTU protocol. 
The 

Simplicity

®

LINC allows monitoring and control by a third-party 

BACnet Building Automation System (BAS).

The 

Simplicity

®

LINC is preconfigured to provide an interface to UP 

products equipped with 

Simplicity

®

 controllers manufactured after 

4/2/2008 as well as prior 

Simplicity

®

Elite™ and 

Simplicity

®

 with 

Intelli-Comfort™ controllers.

The 

Simplicity

®

LINC mounts inside the control panel of the UP 

unit and utilizes 24 VAC power from the unit’s control transformer. 
One port is connected to the UP controller. The other port must be 
connected to the BACnet MS/TP network.

The 

Simplicity

®

LINC Gateway is preconfigured to obtain 

operational data points from the controller and expose them on a 
BACnet MS/TP network.

NOTE: 

Not all 

Simplicity

®

 operating parameters are controlled/

monitored by the 

Simplicity

®

LINC.

FIGURE 1: WIRE CONNECTIONS

24 — must be grounded
close to the 

Simplicity

   LINC

®

The shield must be
connected to ground at
each device.

R
C

24V power is polarity sensitive, incorrect
wiring could result in board damage.

Simplicity

®

LINC GATEWAY

ConFig v1.01d

Содержание Simplicity LINC

Страница 1: ...fort controllers The Simplicity LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit s control transformer One port is connected to the UP controller The other p...

Страница 2: ...and defaulted to 230 The combination of the DE Modifier and the default DIP switch setting creates a default DE of 23001 The default Unit Name is YORK_RTU FIGURE 2 MAC ADDRESS EXAMPLES DIP switches B...

Страница 3: ...URCE1 Toll free at 1 800 536 6112 SOFTWARE SETUP The control sequence is managed by the Simplicity controller The data points on these systems are mapped to standard BACnet Objects As a preconfigured...

Страница 4: ...ive R 5 BI 87 ALARM_3_ON n a n a n a Alarm Buffer 3 0 Alarm has cleared 1 Alarm is still active R 5 BI 88 ALARM_4_ON n a n a n a Alarm Buffer 4 0 Alarm has cleared 1 Alarm is still active R 5 BI 89 AL...

Страница 5: ...BI 31 ECONO_STATUS n a n a n a Economizer Output Status 0 not Free Cooling 1 Free Cooling R W 2 AV 22 ECON_OAEN_SP 27 10 50 Economizer Outside Air Enthalpy Setpoint R W 2 AV 23 ECON_OAT_ENA 55 40 80...

Страница 6: ...zed R 5 BI 64 E_GAS_VLVE3 n a n a n a Elite Gas Valve 3 Input Status 1 energized 0 not energized R 5 BI 44 E_HPS1 n a n a n a Elite High Pressure Switch for Compressor 1 Input Status 1 closed 0 open f...

Страница 7: ...Present R 5 BI 32 FRECOOL_STAT n a n a n a Free Cooling Mode Status 0 comps not overridden by Econo 1 comps overridden R 5 BI 104 FREEZE_STAT_1 n a n a n a Freeze Stat 1 R 5 BI 105 FREEZE_STAT_2 n a...

Страница 8: ...elli Comfort Compressor 2 Accumulated Run Time in hours R 5 BI 76 I_COMP2_STAT n a n a n a Intelli Comfort Compressor 2 Input Status 0 output is OFF 1 output is ON R 5 BI 79 I_CFAN_STAT n a n a n a In...

Страница 9: ...0 100 Maximum Demand Ventillation Economizer Position R W 5 BV 110 MIN_AMB_SEN n a n a n a Minimum Outdoor Air Sensor Enabled R W 2 AV 85 MIN_AMB_TEMP_SP 0 0 100 Minimum Outdoor Air Temperature Setpo...

Страница 10: ...1 REM_CONT_BAS_ECON n a n a n a Remote Control Third Party BAS Economizer Enable R 2 AI 13 RET_AIR_ENTH n a n a n a Return Air Enthalpy R W 2 AV 12 RET_AIR_HUM n a n a n a Return Air Humidity R 2 AI 5...

Страница 11: ...OFF Continuous Fan when Starting Heat Enabled 0 Continuous Fan ON R W 2 AV 2 UNOC_COOL_SP 85 46 99 Un Occupied Cooling Setpoint R W 2 AV 51 UNOC_HEAT_SP 60 45 98 Un Occupied Heating Setpoint R W 2 AV...

Страница 12: ...umidity R 2 AI 13 RET_AIR_ENTH n a n a n a Return Air Enthalpy R W 2 AV 14 ACC_OVER_TME n a n a n a Accumulated Unoccupied Override Time in hours R 2 AI 15 ACTIVE_ALARM n a n a n a Active Alarm R 2 AI...

Страница 13: ...te Compressor 2 Accumulated Run Time in hours R 2 AI 43 E_C3_ACM_HRS n a n a n a Elite Compressor 3 Accumulated Run Time in hours R 2 AI 44 E_C4_ACM_HRS n a n a n a Elite Compressor 4 Accumulated Run...

Страница 14: ...VAV_CL_HI_SP 60 41 70 VAV Cooling Supply Air Temperature Upper Setpoint degrees F R W 2 AV 65 VAV_CL_LO_SP 55 40 69 VAV Cooling Supply Air Temperature Lower Setpoint degrees F R W 2 AV 66 VAV_SAT_RSET...

Страница 15: ...V 90 FAN_SPD_NO_HEAT_C OOL 50 0 100 Fan Speed No Heating No Cooling R W 2 AV 91 FAN_SPD_1ST_COOL 70 0 100 Fan Speed 1st Stage Cooling R W 2 AV 92 FAN_SPD_1ST_HEAT 100 0 100 Fan Speed 1st Stage Heating...

Страница 16: ...Space Sensor Present Option Enabled R W 5 BV 22 SAT_COOLING n a n a n a Supply Air Temperature Limit for Cooling Enabled R W 5 BV 23 COOLING_ENA n a n a n a Cooling Mode Enabled R W 5 BV 24 SAT_HEATIN...

Страница 17: ...ut Status 1 closed 0 open fault R 5 BI 44 E_HPS1 n a n a n a Elite High Pressure Switch for Compressor 1 Input Status 1 closed 0 open fault R 5 BI 45 E_C1_OVRLOAD n a n a n a Elite Compressor 1 Overlo...

Страница 18: ...energized R 5 BI 61 E_LIMIT_ 1 n a n a n a Elite Limit Switch 1 Input Status 1 closed 0 open fault R 5 BI 62 E_GAS_VLVE2 n a n a n a Elite Gas Valve 2 Input Status 1 energized 0 not energized R 5 BI...

Страница 19: ...li Comfort High Pressure Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BI 79 I_CFAN_STAT n a n a n a Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5 BI...

Страница 20: ...n a n a Accept Comm Value for OAT R 5 BI 102 4_STG_EXP_PRES n a n a n a Four Stage Expansion board Present R 5 BI 103 VAV_INTELLI_2_PRES n a n a n a VAV Intelli Comfort 2 Expansion Board Present R 5...

Страница 21: ...l turn off after 5 seconds If the Node Offline LED stays on solid a node offline condition has occurred Unused 15 seconds after powering up the 4 unused LEDs will turn on solid for 5 seconds then turn...

Страница 22: ...ls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 FIGURE 3 SIMPLICITY LINC BOARD AND LED LAYOUT PWR RS485 PWR BACnet EOL Switch So Reset S...

Отзывы: