APPLICATION GUIDE
OVERVIEW
The
Simplicity
®
LINC Gateway operates as a Modbus® Client
providing an interface between a BACnet® MS/TP control system
and devices that communicate using the Modbus RTU protocol.
The
Simplicity
®
LINC allows monitoring and control by a third-party
BACnet Building Automation System (BAS).
The
Simplicity
®
LINC is preconfigured to provide an interface to UP
products equipped with
Simplicity
®
controllers manufactured after
4/2/2008 as well as prior
Simplicity
®
Elite™ and
Simplicity
®
with
Intelli-Comfort™ controllers.
The
Simplicity
®
LINC mounts inside the control panel of the UP
unit and utilizes 24 VAC power from the unit’s control transformer.
One port is connected to the UP controller. The other port must be
connected to the BACnet MS/TP network.
The
Simplicity
®
LINC Gateway is preconfigured to obtain
operational data points from the controller and expose them on a
BACnet MS/TP network.
NOTE:
Not all
Simplicity
®
operating parameters are controlled/
monitored by the
Simplicity
®
LINC.
FIGURE 1: WIRE CONNECTIONS
24 — must be grounded
close to the
Simplicity
LINC
®
The shield must be
connected to ground at
each device.
R
C
24V power is polarity sensitive, incorrect
wiring could result in board damage.
Simplicity
®
LINC GATEWAY
ConFig v1.01d