1031990-UAD-A-0313
20
Johnson Controls Unitary Products
R
(5) BI
89
ALARM_5_ON
n/a
n/a
n/a
Alarm Buffer #5 (0=Alarm has cleared,
1=Alarm is still active)
R / W
(5) BV
90
DF_SW_INST
n/a
n/a
n/a
Dirty Filter Switch Installed
R / W
(5) BV
93
OCC_COMS_ENA
n/a
n/a
n/a
Occupied Thermostat or
Communication Input Enabled
R / W
(5) BV
96
VAV_UNOCC_HEAT
n/a
n/a
n/a
VAV Unoccupied Heating Enabled
R / W
(5) BV
97
THERMO_CONTROL
n/a
n/a
n/a
Thermostat Only Control Enable
R / W
(5) BV
98
DIFF_ENTH_MODE
n/a
n/a
n/a
Differential enthalpy mode enabled
R / W
(5) BV
99
COMM_RH
n/a
n/a
n/a
Accept Comm Value for RH
R / W
(5) BV
100
COMM_OH
n/a
n/a
n/a
Accept Comm Value for OH
R / W
(5) BV
101
COMM_OAT
n/a
n/a
n/a
Accept Comm Value for OAT
R
(5) BI
102
4_STG_EXP_PRES
n/a
n/a
n/a
Four Stage Expansion board Present
R
(5) BI
103
VAV_INTELLI_2_PRES
n/a
n/a
n/a
VAV / Intelli-Comfort 2 Expansion
Board Present
R
(5) BI
104
FREEZE_STAT_1
n/a
n/a
n/a
Freeze Stat # 1
R
(5) BI
105
FREEZE_STAT_2
n/a
n/a
n/a
Freeze Stat # 2
R
(5) BI
106
FREEZE_STAT_3
n/a
n/a
n/a
Freeze Stat # 3
R
(5) BI
107
FREEZE_STAT_4
n/a
n/a
n/a
Freeze Stat # 4
R / W
(5) BV
108
COMM_ST
n/a
n/a
n/a
Accept Comm Value for Space
Temperature
R / W
(5) BV
109
COMM_IAQ
n/a
n/a
n/a
Accept Comm Value for Indoor Quality
Sensor
R / W
(5) BV
110
MIN_AMB_SEN
n/a
n/a
n/a
Minimum Outdoor Air Sensor Enabled
R / W
(5) BV
111
REM_CONT_BAS_ECO
N
n/a
n/a
n/a
Remote Control Third Party BAS
Economizer Enable
TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)
Read/
Write
BACnet
Object
Type
BACnet
Object
Inst
Descriptor
Default
Min
Max
Point Description