1031990-UAD-A-0313

10

Johnson Controls Unitary Products

R / W

(2) AV

69

OP_STPT_DIF

1

1

5

Operating Setpoint Differential

R / W

(2) AV

74

OAT_COOL_L_O

45

0

100

Outdoor Air Temperature Cooling 
Lockout Temperature

R / W

(2) AV

54

OAT_HEAT_L_O

75

0

100

Outdoor Air Temperature 
HeatingLockout Temperature

R (2) 

AI

11

AMB_AIR_ENTH

n/a

n/a

n/a

Outside Air Enthalpy

R / W

(2) AV

10

AMB_AIR_HUM

n/a

n/a

n/a

Outside Air Humidity

R / W

(5) BV

37

OAH_SENSOR

n/a

n/a

n/a

Outside Air Humidity Sensor Enabled

R / W

(2) AV

7

AMB_TEMP

n/a

n/a

n/a

Outside Air Temperature

R

(2) AI

9

OAQ_VALUE

n/a

0

5000

Outside Demand Ventilation (OAQ) 
Value (PPM)

R / W

(5) BV

8

PWR_EX_INST

n/a

n/a

n/a

Power Exhaust Installed

R / W

(5) BV

20

POP_ENABLED

n/a

n/a

n/a

Pre-Occupancy Purge Enabled

R / W

(2) AV

81

POP_HOURS

4

0

23

Pre-Occupancy Purge Time (hours)

R / W

(2) AV

82

POP_MINUTES

0

0

59

Pre-Occupancy Purge Time (minutes)

R

(5) BI

17

PURGE_SWITCH

n/a

n/a

n/a

Purge Switch Status (0=open,1=closed)

R / W

(5) BV

12

REDLINE

n/a

n/a

n/a

Redline (0=clear redline, 1=set redline 
operation)

R

(5) BI

4

REM_CONT_ENA

n/a

n/a

n/a

Remote Control Enabled

R / W

(5) BV

111

REM_CONT_BAS_ECON

n/a

n/a

n/a

Remote Control Third Party BAS 
Economizer Enable

R

(2) AI

13

RET_AIR_ENTH

n/a

n/a

n/a

Return Air Enthalpy

R / W

(2) AV

12

RET_AIR_HUM

n/a

n/a

n/a

Return Air Humidity

R

(2) AI

5

RET_AIR_TEMP

n/a

n/a

n/a

Return Air Temperature

R / W

(5) BV

38

RAH_SENSOR

n/a

n/a

n/a

Return/Inside Air Humidity Sensor 
Enabled

R / W

(2) AV

6

SPACE_TEMP

n/a

n/a

n/a

Space (Indoor) Air Temperature 

R / W

(2) AV

71

SPCE_ALM_TMP

0

0

25

Space Sensor Alarm Temperature 
(degrees F, 0 = disabled)

R / W

(2) AV

72

SPCE_ALM_TIM

0

0

120

Space Sensor Alarm Time (minutes F, 0 
= disabled)

R / W

(5) BV

26

SEN_FAULT_EN

n/a

n/a

n/a

Space Sensor Fault Override 
(Construction Mode) Enabled

R / W

(2) AV

73

SP_OFF_RANGE

3

0

5

Space Temprature Sensor Offset Range 
(0-5 degrees)

R

(2) AI

4

SUP_AIR_TEMP

n/a

n/a

n/a

Supply Air Temperature

R / W

(2) AV

70

SAT_ALM_COOL

0

0

80

Supply Air Temperature Alarm Setpoint 
for Cooling

R / W

(2) AV

53

SAT_ALM_HEAT

0

0

120

Supply Air Temperature Alarm Setpoint 
for Heating

R / W

(5) BV

22

SAT_COOLING

n/a

n/a

n/a

Supply Air Temperature Limit for 
Cooling Enabled

R / W

(2) AV

3

SAT_COOL_SP

50

40

65

Supply Air Temperature Limit for 
Cooling Setpoint (degrees F)

TABLE 2: POINTS LIST IN DESCRIPTION ORDER  (CONTINUED)

Read/ 

Write

BACnet 

Object 

Type

BACnet 

Object 

Inst

Descriptor

Default Min

Max Point Description

Содержание Simplicity LINC

Страница 1: ...fort controllers The Simplicity LINC mounts inside the control panel of the UP unit and utilizes 24 VAC power from the unit s control transformer One port is connected to the UP controller The other p...

Страница 2: ...and defaulted to 230 The combination of the DE Modifier and the default DIP switch setting creates a default DE of 23001 The default Unit Name is YORK_RTU FIGURE 2 MAC ADDRESS EXAMPLES DIP switches B...

Страница 3: ...URCE1 Toll free at 1 800 536 6112 SOFTWARE SETUP The control sequence is managed by the Simplicity controller The data points on these systems are mapped to standard BACnet Objects As a preconfigured...

Страница 4: ...ive R 5 BI 87 ALARM_3_ON n a n a n a Alarm Buffer 3 0 Alarm has cleared 1 Alarm is still active R 5 BI 88 ALARM_4_ON n a n a n a Alarm Buffer 4 0 Alarm has cleared 1 Alarm is still active R 5 BI 89 AL...

Страница 5: ...BI 31 ECONO_STATUS n a n a n a Economizer Output Status 0 not Free Cooling 1 Free Cooling R W 2 AV 22 ECON_OAEN_SP 27 10 50 Economizer Outside Air Enthalpy Setpoint R W 2 AV 23 ECON_OAT_ENA 55 40 80...

Страница 6: ...zed R 5 BI 64 E_GAS_VLVE3 n a n a n a Elite Gas Valve 3 Input Status 1 energized 0 not energized R 5 BI 44 E_HPS1 n a n a n a Elite High Pressure Switch for Compressor 1 Input Status 1 closed 0 open f...

Страница 7: ...Present R 5 BI 32 FRECOOL_STAT n a n a n a Free Cooling Mode Status 0 comps not overridden by Econo 1 comps overridden R 5 BI 104 FREEZE_STAT_1 n a n a n a Freeze Stat 1 R 5 BI 105 FREEZE_STAT_2 n a...

Страница 8: ...elli Comfort Compressor 2 Accumulated Run Time in hours R 5 BI 76 I_COMP2_STAT n a n a n a Intelli Comfort Compressor 2 Input Status 0 output is OFF 1 output is ON R 5 BI 79 I_CFAN_STAT n a n a n a In...

Страница 9: ...0 100 Maximum Demand Ventillation Economizer Position R W 5 BV 110 MIN_AMB_SEN n a n a n a Minimum Outdoor Air Sensor Enabled R W 2 AV 85 MIN_AMB_TEMP_SP 0 0 100 Minimum Outdoor Air Temperature Setpo...

Страница 10: ...1 REM_CONT_BAS_ECON n a n a n a Remote Control Third Party BAS Economizer Enable R 2 AI 13 RET_AIR_ENTH n a n a n a Return Air Enthalpy R W 2 AV 12 RET_AIR_HUM n a n a n a Return Air Humidity R 2 AI 5...

Страница 11: ...OFF Continuous Fan when Starting Heat Enabled 0 Continuous Fan ON R W 2 AV 2 UNOC_COOL_SP 85 46 99 Un Occupied Cooling Setpoint R W 2 AV 51 UNOC_HEAT_SP 60 45 98 Un Occupied Heating Setpoint R W 2 AV...

Страница 12: ...umidity R 2 AI 13 RET_AIR_ENTH n a n a n a Return Air Enthalpy R W 2 AV 14 ACC_OVER_TME n a n a n a Accumulated Unoccupied Override Time in hours R 2 AI 15 ACTIVE_ALARM n a n a n a Active Alarm R 2 AI...

Страница 13: ...te Compressor 2 Accumulated Run Time in hours R 2 AI 43 E_C3_ACM_HRS n a n a n a Elite Compressor 3 Accumulated Run Time in hours R 2 AI 44 E_C4_ACM_HRS n a n a n a Elite Compressor 4 Accumulated Run...

Страница 14: ...VAV_CL_HI_SP 60 41 70 VAV Cooling Supply Air Temperature Upper Setpoint degrees F R W 2 AV 65 VAV_CL_LO_SP 55 40 69 VAV Cooling Supply Air Temperature Lower Setpoint degrees F R W 2 AV 66 VAV_SAT_RSET...

Страница 15: ...V 90 FAN_SPD_NO_HEAT_C OOL 50 0 100 Fan Speed No Heating No Cooling R W 2 AV 91 FAN_SPD_1ST_COOL 70 0 100 Fan Speed 1st Stage Cooling R W 2 AV 92 FAN_SPD_1ST_HEAT 100 0 100 Fan Speed 1st Stage Heating...

Страница 16: ...Space Sensor Present Option Enabled R W 5 BV 22 SAT_COOLING n a n a n a Supply Air Temperature Limit for Cooling Enabled R W 5 BV 23 COOLING_ENA n a n a n a Cooling Mode Enabled R W 5 BV 24 SAT_HEATIN...

Страница 17: ...ut Status 1 closed 0 open fault R 5 BI 44 E_HPS1 n a n a n a Elite High Pressure Switch for Compressor 1 Input Status 1 closed 0 open fault R 5 BI 45 E_C1_OVRLOAD n a n a n a Elite Compressor 1 Overlo...

Страница 18: ...energized R 5 BI 61 E_LIMIT_ 1 n a n a n a Elite Limit Switch 1 Input Status 1 closed 0 open fault R 5 BI 62 E_GAS_VLVE2 n a n a n a Elite Gas Valve 2 Input Status 1 energized 0 not energized R 5 BI...

Страница 19: ...li Comfort High Pressure Switch for Compressor 2 Input Status 1 closed 0 open fault R 5 BI 79 I_CFAN_STAT n a n a n a Intelli Comfort Condenser Fan 1 Input Status 0 output is OFF 1 output is ON R 5 BI...

Страница 20: ...n a n a Accept Comm Value for OAT R 5 BI 102 4_STG_EXP_PRES n a n a n a Four Stage Expansion board Present R 5 BI 103 VAV_INTELLI_2_PRES n a n a n a VAV Intelli Comfort 2 Expansion Board Present R 5...

Страница 21: ...l turn off after 5 seconds If the Node Offline LED stays on solid a node offline condition has occurred Unused 15 seconds after powering up the 4 unused LEDs will turn on solid for 5 seconds then turn...

Страница 22: ...ls Inc All rights reserved Supersedes Nothing Johnson Controls Unitary Products 5005 York Drive Norman OK 73069 FIGURE 3 SIMPLICITY LINC BOARD AND LED LAYOUT PWR RS485 PWR BACnet EOL Switch So Reset S...

Отзывы: