Operating manual – DualPAC with reciprocating compressors
58/63
0012201 en 2021.04
•
Press
Arrow up
(no. 4) until 1 has turned to 3, see Fig. 33.
Fig. 33
2.
Change the gas constant:
•
Press
Arrow right
(no. 1) – the bottom line is marked.
•
Change the digit to wanted number by pressing
Arrow right
(no. 1),
Arrow
down
(no. 3) and
Arrow up
(no. 4), see Fig. 34.
Fig. 34
•
Confirm with
Return
(no. 2), see Fig. 35.
Fig. 35
Return
(no. 2) always takes you up one level.
Change the following parameters in the same way:
•
+ 2.3.2 Blocking distance from 50 mm to 0 mm
•
+ 2.3.3 Time constant from 5 sec. to 1 sec.
•
+ 2.5.7 Level threshold from 200 mm to 150 mm
•
+ 4.1.1 Full area - confirm or change to 0 mm. Passcode for level 4.x.x = 4-3-4-2-4-1
•
+ 4.1.2 Empty Area from 280 mm to 260 mm.
After the last change, press
Return
(no. 2) until “STORE NO” is displayed, see Fig. 36.