Operating manual – DualPAC with reciprocating compressors
50/63
0012201 en 2021.04
8. Appendices
8.1
Monitoring of operation
To ensure satisfactory operation, it is required that you enter certain routines in a logbook on a
regular basis. You can use the items listed in the
Start-up log
, which is page 2 of the
Checklist
il-
lustrated in Fig. 24. The service engineer will need this information in connection with, for exam-
ple, error reports.
In addition to the items listed in the start-up log, all other activities of service, maintenance or re-
pair work must be entered into your logbook as required by EN 378 and national laws.
Checklist
Along with this Operating manual we have provided a
Checklist
, as shown in Fig. 24, which will
serve as a help to the service engineer and
must be filled in during commissioning and
start-up
.
Keep the filled-in checklist, and send a copy to SABROE Factory as documentation that the unit
has been installed and commissioned correctly. The checklist will be required in case of a warranty
issue.
Fig. 24: The checklist which MUST be filled in during commissioning and start-up
Start-up log: Monitoring of operation at start-up
Compressor serial no.:
Date:
Name:
Observation
Value
Operation time
[hours
]
Suction pressure
[
°
C/R]
Suction temperature
[
°
C]
Superheating, suction gas
[K
]
Discharge pressure
[
°
C/R]
Discharge temperature
[
°
C]
Oil pressure, compressor
[bar
]
Oil pressure, filter
[bar
]
Oil temperature
[
°
C]
Oil temperature, separator
[
°
C]
Oil collection from shaft seal
[ml
]
Oil level
[0,
1
/
4
,
1
/
2
,
3
/
4
, Full]
Charged oil
[Litre
]
Motor 1/1 load
[amp.
]
Capacity load
[%
]
Noise level
[OK/not OK
]
Vibrations (0-100% capacity)
[OK/not OK
]
Brine temperature, outlet - Evaporator
[
°
C]
Brine temperature, outlet - Condenser
[
°
C]
Refrigerant charge
[Kg
]
Please fill in this form, file it, and send a copy to: [email protected].
Checklist
2/ 2
011198 en 2014.10
Checklist for commissioning of compressor, chiller and heat pump units
Compressor serial no.:
Date:
Name:
Check before start-up
Read and understand all Sabroe manuals (compressor, Unisab, chiller, etc.)
Read and understand manuals for third party components (electric motors, valves,
etc.)
Check unit installation and vibration damper adjustment
Carry out functional testing of safety equipment
Read the opening pressures on all safety valves, and check that they are correct
Carry out vacuum test
Check Unisab set-up (see list of settings), and check VSD set-up, as applicable
Check oil level
Check that the heating element in the oil has been on for 6-8 hours before start
Take a sample of the primary refrigerant (must be free from water, air, etc.)
Check that the motor rotation direction is correct
Check that the coupling is aligned
Check that compressor cooling is connected correctly
Check that the plant is not leaking
Check that the valves are in the correct position for operation
Check after start-up
Check that the capacity regulation system is working correctly
Check the refrigerant charge (at full load)
Check the unit for vibrations
Check the unit for vibrations using VibraGuard (variable speed)
Make a start-up log at full load (on the back of this form)
Take out a representative lubricating oil sample after about 1 hour of operation, and
save it for minimum 1 year from commissioning date
This form is also available on the Sabroe SUPPORT site on www.sabroe.com.
Go to ‘Document search’ and search for
Checklist
.
Checklist
011198 en 2014.10