Operating manual – DualPAC with reciprocating compressors
0012201 en 2021.04
47/63
6. Maintenance instructions
6.1
Maintenance of DualPAC units
Read chapter
carefully before performing any maintenance on the DualPAC unit.
To ensure that the DualPAC unit operates without problems throughout a long service life, the
system of maintenance presented in the following instructions must be followed.
Daily maintenance is normally performed by operating personnel. Other maintenance and service
tasks, which require the refrigeration system to be opened, must be performed by competent
personnel.
Maintenance can be divided into:
1.
Daily maintenance
(minimum twice a week)
Daily maintenance consists of visual inspections.
•
Inspect the DualPAC unit, and check that both noise and vibrations are normal.
•
To observe trends, it is recommended to enter the observed operating data into a
logbook, see subsection
. Check that all operating val-
ues are within the permissible ranges. Compare them with previous values to de-
tect trends.
•
Check the oil level.
•
Check the refrigerant charge.
•
Observe for leaks of refrigerant (smell of ammonia), oil, glycol or water.
•
Check mechanical seal oil draining bottle.
•
Check the control system for alarms/shutdowns.
2.
Half yearly/yearly/major maintenance
•
Normally, only the compressor needs to be maintained. However, it is recommen-
ded to check that the DualPAC is running properly: check for fouling of heat ex-
changers, dirt in filters, etc.
Maintenance intervals are described in detail in the compressor manual.