Operating manual – DualPAC with reciprocating compressors
0012201 en 2021.04
19/63
Note:
Whenever a relief valve/safety valve has been activated, we recommend recalibrating it.
This must be carried out by competent personnel only. See also EN 378 and existing national
legislation.
2.3.3
Water system
Warning!
The recirculation water system may contain chemicals or biological contaminants, including le-
gionella, which can be harmful if inhaled or ingested. Water systems should only be operated with
an effective biological treatment programme.
2.3.4
Brine
In recent years alcohol, glycol and halogenated compounds have been used in the production of
brine.
In general, all brines must be considered harmful to nature and they must be used with caution.
Be very careful when charging or purging a refrigeration plant.
Never empty brines down a sewer or into the environment.
The brine must be collected in suitable containers clearly marked with the contents and sent to an
approved incineration plant.
2.3.5
Safety during maintenance and service
•
Personnel must be competent according to national safety rules and regulations and per-
form the maintenance work according to EN 378 and EN 13313/ISO 22712.
•
Read chapter
in this manual before opening the compressor and other parts of
the refrigeration plant. If the switch is not locked, all start buttons must be tagged with
“DO NOT START”
tags and an explanation: “Work on unit in progress”.
•
Make sure that the motor cannot start up inadvertently. Switch off all electric components
on the compressor/unit before starting the dismantling/servicing process. It is recom-
mended to remove all main fuses.
•
Make sure that there is no over-pressure and no refrigerant in the part to be dismantled.
Close all necessary stop valves.
•
Use the prescribed tools, and check that they are properly maintained and in good work-
ing condition. In explosion-proof areas, use tools suited for this specific purpose.
•
Use only Johnson Controls Denmark original spare parts; other parts may impair the
safety of the compressor/unit.
•
Use gloves and protective goggles, and make sure to have a gas mask close at hand.
2.3.6
Power supply
Danger!
•
The voltage used in the drive can cause severe electric shock and/or burns and may be le-
thal. Extreme care must be taken at all times when working with or close to the drive. Spe-
cific warnings are given wherever relevant in this manual.
•
The drive line is connected to voltage. Be aware of live circuits.
•
Pay close attention to the electrical installation and system maintenance to avoid hazards
both during normal operation or in the event of equipment malfunctioning.
Содержание SABROE DualPAC
Страница 1: ...NS HPAC DualPAC with reciprocating compressors Operating manual EN ...
Страница 2: ......