VFD68 Variable Frequency Drives
88
Appendix 3: Password Functions (P.296, P.297)
Registering a four-digit password can restrict parameter reading and writing. You can set these parameters
when P.160 = 0.
Note:
When P.296 is set to something other than 9999, then P.297 is always available to enter a password,
regardless of the setting for P.160.
Parameter Reading and Writing Restriction Level
P.296 controls the level of reading and writing restriction.
Table 82: Implement Password Protection
Parameter
Name
Default
Range
Description
P.296
Password Lock Level
9999
1 to 6, 101 to 106
Select the restriction level of parameter
reading and writing when a password is
required.
9999
No password lock
P.297
Password
Unlock/Lock
9999
1000 to 9998
Register a four-digit password
(0)
(reading only)
Valid when P.296 = 1 to 6
(0 to 5)
Displays password unlock error count
(reading only)
Valid when P.296 = 101 to 106
(9999)
No password lock (reading only)
Table 83: Parameter Reading and Writing Restriction (P.296)
P.296 Setting
PU Operation Mode Command
1
1.
Parameter access from a unit where the parameter is written in the PU Manual Operation mode is restricted.
NET Mode Operation Command
2
2.
Parameter access in NET Operation mode with RS-485 communication is restricted.
Read
3
3.
If the parameter reading is restricted by P.160, P.296 is unavailable for reading, even when enabled.
Write
4
4.
If the parameter writing is restricted by P.77, P.296 is unavailable for writing, even when enabled.
Write
9999
Enabled
Enabled
Enabled
Enabled
1, 101
Enabled
Restricted
Enabled
Restricted
2, 102
Enabled
Restricted
Enabled
Enabled
3, 103
Enabled
Enabled
Enabled
Restricted
4, 104
Restricted
Restricted
Restricted
Restricted
5, 105
Restricted
Restricted
Enabled
Enabled
6, 106
Enabled
Enabled
Restricted
Restricted