![Johnson Controls Penn VFD68BBB Скачать руководство пользователя страница 33](http://html1.mh-extra.com/html/johnson-controls/penn-vfd68bbb/penn-vfd68bbb_technical-bulletin_2023903033.webp)
VFD68 Variable Frequency Drives
33
0.5–4.5 VDC Ratiometric P499 Transducer
The default parameter values (Table 34 on page 43) on the VFD68 drive are configured to operate a
condenser fan motor on an R410 condensing unit, using a P499RCP-107 or P499RAP-107 ratiometric
transducer (or transducers). Wire one transducer for single circuit condensing systems. Wire two transducers
for dual circuit condensing systems (Figure 23).
The VFD68 has the ability to control motor speed using the higher input signal value of two
voltage
inputs
when you configure AI1 and AI2 as the same model transducer. For the
high-input signal select
application
with two transducers (Figure 23 on page 33 or Figure 24 on page 34), use the parameter values in Table 28
Adjusting the Default Parameters
For high-pressure refrigerants other than R410a, you must calculate and change the
C x
parameters. For
medium and low pressure refrigerants, you must determine the proper P499R transducer and then calculate
and change the
C x
parameters.
For more information, see
on page 38 and
Parameter Setting Calculations for Motor
Table 27: Settings for Single or Dual 0.5–4.5 VDC Ratiometric Transducers
Setting
Single Transducer
Dual Transducer, High-Signal Select
P. 73
1
1.
For information on parameters, see Table 34 on page 43.
1 (0–5 V)
1 (0–5 V)
P.266
1 (voltage input)
1 (voltage input)
P.267
1 (0–5 V)
1 (0–5 V)
Analog Input Terminal
AI1 or AI2
AI1 and AI2
AI2 Mode Switch
2
2.
V
V
IMPORTANT:
If using two input devices, both devices must be identical.
Do not
use input devices with
different ranges and operating characteristics.
Figure 23: Wiring 0.5–4.5 VDC Ratiometric Input Signal Transducers