VFD68 Variable Frequency Drives
46
VFD68Dxx Drive Parameters
You can use the default parameter setting with the P499RxP-107C transducer and R410a refrigerant within a
range of operation that depends on the specific model of P499 transducer selected. All other applications
require some parameter changes and may require different transducers.
C 3
Analog Input 1 - Input voltage to start minimum speed ramp
0–300%
1.90 V (38%)
C 4
Analog Input 1 - Input voltage for setpoint (where motor
reaches maximum frequency or speed)
0–300%
2.74 V
(54.8%)
C 5
Analog Input 2 - Minimum speed (frequency)
0–400 Hz
12.5 Hz
C 6
Analog Input 2 - Input voltage or current to start minimum speed
ramp
0–300%
1.90 V or
7.6 mA (38%)
C 7
Analog Input 2 - Input voltage or current for setpoint (where
motor reaches maximum frequency or speed)
0–300%
2.74 V or
11 mA
(54.8%)
1.
A setting value of 0 indicates 0.7 kHz. A setting value of 1 indicates 1 kHz. A setting value of 15 indicates 15 kHz.
Table 35: Parameter Descriptions for VFD68Dxx Drives (Part 1 of 3)
Parameter
Indication
on Monitor
Description
Settings
Default
Setting
P. 0
Torque Boost:
Defines the voltage (% total V) applied to the
motor when the drive starts the motor at 0 Hz.
0–30%
4% or 3%
P. 1
Maximum Frequency:
Defines the maximum speed of the
motor in your application. See Figure 31.
0–120 Hz
60 Hz
P. 2
Minimum Frequency:
Defines the minimum speed of the
motor in your application.
1
See
0–120 Hz
12.5 Hz
P. 3
Base Frequency:
Set parameter to the rated frequency [Hz]
on motor rating plate.
0–400 Hz
60 Hz
P. 7
Acceleration Time:
Defines the time required to accelerate
from stop (0 Hz) to full rated RPM (60 Hz).
0–3600 seconds
15 seconds
P. 8
Deceleration Time:
Defines the time required to decelerate
from full rated RPM (60 Hz) to stop (0 Hz).
0–3600 seconds
15 seconds
P. 9
Motor Rated Current:
Set parameter to the rated FLA on
motor rating plate.
0–500 A
Rated VFD68
Output
P. 19
VFD Output Voltage:
Defines the maximum output voltage
relative to the drive's supply voltage.
2
•
9999: the maximum output voltage is the same as the
drive's power supply voltage
0–1000V, 9999
9999
P. 22
Stall Prevention Output Current Level:
Defines the current
level (as a % of motor FLA) at which the drive begins to
adjust the output frequency (Hz) to reduce the output current.
0–200%
150%
P. 31
Frequency Jump 1A:
Frequency Jump parameters (P. 31
and P. 32) are used to set the low speed behavior of the
drive. This parameter typically remains at 0 Hz
0–400 Hz, 9999
0 Hz
Table 34: Basic and Advanced Parameter Descriptions for VFD68Bxx and VFD68Cxx Drives
(Part 4 of 4)
Parameter
Indication
on Monitor
Description
Range
VFD68xxx-
2 Defaults