VFD68 Variable Frequency Drives
103
Modbus Registers
Table 122: System Environment Variable
Register
Definition
Read/Write
Remarks
40002
VFD Reset
Write
Any value can be written.
40003
Parameter Clear
Write
Set H965A as a written value.
40004
All Parameters Clear
Write
Set H965A as a written value.
40006
Parameter Clear
1
1.
The communication parameter values are not cleared.
Write
Set H965A as a written value.
40007
All Parameters Clear
Write
Set H965A as a written value.
40009
VFD Status/Control Input Instruction
2
2.
For write, set data as the control input instruction. For read, data is read as a VFD operating status.
Read/Write
See below.
40010
Operation Mode/VFD Setting
3
3.
For write, set data as the operation mode setting. For read, data is read as the operation mode status.
Read/Write
See below.
40014
Running Frequency (RAM Value)
Read/Write
According to the P. 37 settings, the
frequency and selectable speed are in 1
rotation/minute increments.
40015
Running Frequency (EEPROM Value)
Write
Table 123: VFD Status
Bit
Definition
Control Input Instruction
VFD Status
0
Stop command
RUN (VFD operational)
1
1.
The signal within parenthesis is the initial setting. Definitions change according to the settings for P.180 to P182.
1
forward rotation command
Forward rotation
2
reverse rotation command
During reverse rotation
3
RH (high-speed operation command)
2
2.
The signal within the parenthesis is the initial setting. Definitions change according to the settings for P.190 and P.192.
SU (up-to-frequency)
4
RM (middle-speed operation command)
OL (overload)
5
RL (low-speed operation command)
0
6
0
FU (frequency detection)
7
RT (second function selection)
8
AU (terminal 4 input selection)
0
9
0
0
10
MRS (output stop)
0
11
0
0
12
0
0
13
0
0
14
0
0
15
0
Fault occurrence