NexSys
VAV-01 Controller
Installation Guide
13
Figure 5. Thermistor Wiring.
DIGITAL OUTPUTS
Digital outputs shown in Figure 6 below must be wired as follows:
• DO1 must be wired to Damper Increment.
• DO2 must be wired to Damper Decrement.
• DO3 must be wired to the fan, if one is used.
• DO4 must be wired to heating element 1 for staged reheat, incre-
ment for floating reheat, or the pulse width modulator.
• DO5 must be wired to heating element 2 (and heating element 3, if
it is used) for staged reheat, or decrement for floating reheat. If pulse
width modulation is used, DO5 is a spare output.