NexSys
VAV-01 Controller
Installation Guide
17
Digital Outputs DO-4 and DO-5 can also be used for Floating Reheat
or Pulse Width Modulation. If you are using two stage reheat, each
heating element is wired to a digital output. If three heating elements
are used for three stage reheat, the first element is wired to DO-4,
and the second and third elements are wired to DO-5. If two heating
elements are used for three stage reheat, the smaller heating element
is wired to DO-4, and the larger heating element is wired to DO-5.
NOTE:
The rating for these outputs is 0.5 amps at 24VAC.