—MS2 Two Stage Electronic Temperature Control Installation Bulletin    

5

 

F

ault/Alarm Codes 

Table 4: Status Codes (steady on display) 

Status Code 

Indicates 

On

 

Binary Input is closed. 

OF

 

Binary Input is open. 

 

Table 5: Fault/Alarm Codes 

Error Code (Flashing on Display) 

System Status 

EE

  Program failure; control must be replaced. 

Alarm message displays, other outputs off. 

FI

  Indicates an open or shorted temperature sensor. 

Alarm message displays. Correct problem and cycle 
power to reset. 

AI

  Binary input (

IF

) Option 1 selected and binary input open 

 

for longer than time delay (

id

). 

Control output is switched off; alarm message displays. 
Correct condition to reset. 

DF

  Binary input (

IF

) Option 3 is selected and binary input open. 

Control output is switched off. Close binary input to reset. 

HI

  Temperature has reached or exceeded (se 

AH

). 

Alarm message displays. Correct condition to reset. 

LO

  Temperature has reached or fallen below (setpoint - 

AL

). 

Alarm message displays. Correct condition to reset. 

O

rdering Information 

Table 6: Specifications 

Power Requirements 

3.7 VA @ 24 VAC, 50/60 Hz, Class 2 (20-30 VAC) 

Ambient Conditions 

Operating: 

+14 to +140°F (-10 to +60°C); 0 to 95% RH (non-condensing) 

Storage:  

-22 to +176°F (-30 to +80°C); 0 to 95% RH (non-condensing) 

Accuracy 

+1.8 F° (+1C°) 

Agency Listings 

UL Recognized: File E194024, CCN XAPX2  
Canadian UL Recognized: File E194024, CCN XAPX8 
FCC Compliant per Class A Digital Device, Part 15 
Canadian DOC Compliant per Class A, Radio Interference Regulations 

 

Table 7: Ordering Information 

Item Code 

Description 

MS2DR24T-11C 

MS2 DIN Rail Mount Control; A99BB-200C sensor included 

MS2PM24T-11C 

MS2 Panel Mount Control; A99BB-200C sensor included 

A99BB-200C 

A99B Temperature Sensor; Cable length 6-1/2 ft (2 m) 

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these 
specifications, consult Johnson Controls/Penn Refrigeration Application Engineering at (414) 274-5535. Johnson Controls, Inc. shall not be 
liable for damages resulting from misapplication or misuse of its products. 

 

Controls Group 

 

507 E. Michigan Street 

 

P.O. Box 423 

Printed in U.S.A 

Milwaukee, WI  53201 

www.johnsoncontrols.com 

Содержание MS2

Страница 1: ... version ensure that there is sufficient space behind the panel At least 2 3 4 inches 70 mm are needed Make a cutout 1 3 16 by 2 13 16 inches 29 by 71 mm Remove retaining clip from control Insert the control into the hole Install retaining clip and adjust for tightness Wiring WARNING Risk of Electrical Shock Disconnect power supply before making electrical connections to avoid possible electrical ...

Страница 2: ...input status On or OF After 15 seconds of inactivity the display shows the process temperature Setting Up the Stage Control To lock unlock the unit for programming Press the Enter Up and Down buttons simultaneously and hold until is displayed Hold for about 10 seconds until the current temperature is displayed This toggles the keypad between locked and unlocked To run the self test procedure IMPOR...

Страница 3: ...A MS2 Two Stage Electronic Temperature Control Installation Bulletin 3 value it is not saved The control reverts to the old value ...

Страница 4: ... degrees 10 AH High Temperature Alarm High temperature alarm setpoint relative to main setpoint 0 to 50F 0 to 50C above setpoint 15 AL Low Temperature Alarm Low temperature alarm setpoint relative to main setpoint 50 to 0F 50 to 0C below setpoint 15 Ad Alarm Differential Temperature difference relative to high and low alarms at which alarm output is switched Off 1 to 9F 1 to 9C 5 At Alarm Time Del...

Страница 5: ...set Ordering Information Table 6 Specifications Power Requirements 3 7 VA 24 VAC 50 60 Hz Class 2 20 30 VAC Ambient Conditions Operating 14 to 140 F 10 to 60 C 0 to 95 RH non condensing Storage 22 to 176 F 30 to 80 C 0 to 95 RH non condensing Accuracy 1 8 F 1C Agency Listings UL Recognized File E194024 CCN XAPX2 Canadian UL Recognized File E194024 CCN XAPX8 FCC Compliant per Class A Digital Device...

Отзывы: