2    A

—MS2 Two Stage Electronic Temperature Control Installation Bulletin 

 

Use this table, with function 

So

, to compensate for long 

sensor wire. 

Table 1: Sensor Wire Size and Length 

18 AWG 

20 AWG 

22 AWG 

Offset 

300-599 ft 
91-183 m 

190-374 ft 
58-114 m 

120 -239 ft 
36-73 m 

1F° 
1C° 

600-899 ft 
183-274 m 

375-564 ft 
114-172 m 

240-349 ft 
73-107 m 

2F° 
2C° 

900+ ft 
274+ m 

565+ ft 
172+ m 

350+ ft 
107+ m 

3F° 
3C° 

 

Table 2: Rating Table 

Rating Category 

120 
VAC 

240 
VAC 

24 
VDC 

Horsepower 

1/4 

1/2 

Full Load Amperes 

5.8 

4.9 

Locked Rotor Amperes 

34.8 

29.4 

Inductive (non-motor) 
Amperes 

Pilot Duty VA 

275 

450 

Relay outputs must not exceed 20 amperes total  
connected load. Power supply is 24 VAC. 

F

CC Compliance 

This equipment has been tested and found to comply 
with the limits for a Class A digital device pursuant to 
Part 15 of the FCC Rules. These limits are designed to 
provide reasonable protection against harmful 
interference when the equipment is operated in a 
commercial environment. This equipment generates, 
uses, and can radiate radio frequency energy and, if 
not installed and used in accordance with the 
instruction manual, may cause harmful interference to 
radio communications. Operation of this equipment in 
a residential area is likely to cause harmful 
interference, in which case the user will be required to 
correct the interference at his/her own expense. 

C

anadian DOC Compliance 

This digital apparatus does not exceed the Class A 
limits for radio noise emissions from digital apparatus 
set out in the Radio Interference Regulations of the 
Canadian Department of Communications. 

D

isplay 

Press Up and Down buttons to scroll through process 
temperature and binary input status (

On

 or 

OF

). After 

15 seconds of inactivity, the display shows the process 
temperature. 

S

etting Up the Stage Control 

To lock/unlock the unit for programming 

 

Press the Enter, Up, and Down buttons 
simultaneously and hold until “- - -” is displayed. 
Hold for about 10 seconds until the current 
temperature is displayed. This toggles the 
keypad between locked and unlocked. 

To run the self test procedure 

IMPORTANT: Disconnect loads before beginning self-test 

procedure. Cycle power to resume normal 
operation. 

 

Press the Up and Down buttons in sequence, 
and hold for 5 seconds. 

To select the mode of operation 

 

1.  Press and hold the Enter and Down buttons 

simultaneously for approximately 7 seconds. 

 

2.  Press the Up or Down button until the desired 

setting is shown. 

 

2d

 = Direct (cool) 

 

2r

 = Reverse (heat) 

2b

 = Deadband 

2i

 = Independent Setpoint 

 

3.  Press the Enter button to save the new mode 

of operation. 

To change the setpoint (modes b, d, and r only) 

 

1.  Hold the Enter button down for 3 seconds. 

The display will change to show the setpoint. 

 

2.  Press the Up or Down button until you reach 

the new setpoint. 

 

3.  Press the Enter button to save the new 

setpoint. 

Note:  If you do not press the Enter button after selecting the new 

setpoint, it is not saved. The control reverts to old setpoint. 

To program other settings (modes b, d, r only) or to 
program setpoints and settings (mode i only) 

 

1.  Hold the Enter button down for about 

10 seconds. The display will change to 

HY

(The display shows 

S1

 if in Mode i.) 

 

2.  Press the Up or Down button until the desired 

setting is shown. 

 

3.  Press the Enter button. The 

setting’s current 

value is displayed. 

 

4.  Press the Up or Down button until the desired 

value is shown. 

 

5.  Press the Enter button to save the new value. 

After 10 seconds of inactivity, the display will 
return to its normal function. 

Note:  If you do not press the Enter button after selecting the new 

Содержание MS2

Страница 1: ... version ensure that there is sufficient space behind the panel At least 2 3 4 inches 70 mm are needed Make a cutout 1 3 16 by 2 13 16 inches 29 by 71 mm Remove retaining clip from control Insert the control into the hole Install retaining clip and adjust for tightness Wiring WARNING Risk of Electrical Shock Disconnect power supply before making electrical connections to avoid possible electrical ...

Страница 2: ...input status On or OF After 15 seconds of inactivity the display shows the process temperature Setting Up the Stage Control To lock unlock the unit for programming Press the Enter Up and Down buttons simultaneously and hold until is displayed Hold for about 10 seconds until the current temperature is displayed This toggles the keypad between locked and unlocked To run the self test procedure IMPOR...

Страница 3: ...A MS2 Two Stage Electronic Temperature Control Installation Bulletin 3 value it is not saved The control reverts to the old value ...

Страница 4: ... degrees 10 AH High Temperature Alarm High temperature alarm setpoint relative to main setpoint 0 to 50F 0 to 50C above setpoint 15 AL Low Temperature Alarm Low temperature alarm setpoint relative to main setpoint 50 to 0F 50 to 0C below setpoint 15 Ad Alarm Differential Temperature difference relative to high and low alarms at which alarm output is switched Off 1 to 9F 1 to 9C 5 At Alarm Time Del...

Страница 5: ...set Ordering Information Table 6 Specifications Power Requirements 3 7 VA 24 VAC 50 60 Hz Class 2 20 30 VAC Ambient Conditions Operating 14 to 140 F 10 to 60 C 0 to 95 RH non condensing Storage 22 to 176 F 30 to 80 C 0 to 95 RH non condensing Accuracy 1 8 F 1C Agency Listings UL Recognized File E194024 CCN XAPX2 Canadian UL Recognized File E194024 CCN XAPX8 FCC Compliant per Class A Digital Device...

Отзывы: